SPEC 45410

AL 2000V XLPE Insulation. RHH/RHW-2 PV

Single Conductor Photovoltaic (Type PV) Power Cable 2000 Volt Aluminum Conductor XLPE Insulation. Sizes 6AWG through 1000 kcmil. Heat, Moisture, and Sunlight Resistant RoHS. 90°C

...

Construction:

  1. Conductor:AlumaFlex® Compact Stranded Aluminum Alloy (AA-8176)
  2. Insulation: Cross-linked Polyethylene (XLPE)

Applications and Features:

The cable is available in sizes 6 AWG through 1000 kcmil. The product is approved for use in solar power applications per the NEC article 690 and is rated 90°C for exposed or concealed wiring in wet or dry locations. Individual conductors are stranded aluminum alloy covered with a cross-linked polyethylene (XLPE) insulation and is rated for direct burial. The cable is sunlight resistant, oil resistant PRI and PRII, RoHS compliant, passes -40°C cold bend.

Specifications:

  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 854 Service Entrance Cable
  • UL 4703 Standard for Photovoltaic Wire
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • VW-1 Vertical-Wire Flame Test (Optional)
  • AA 8176 Stranded Aluminum Alloy Conductors
  • Sample Print Legend:

    SOUTHWIRE E316464 {UL} PV WIRE XXX KCMIL (XXX.XXX{mm2}) COMPACT AL. --- AlumaFlex® AA8176 2000V 90°C WET OR DRY -40°C SUN RES DIRECT BURIAL OR RHH-RHW-2 2000V --- RoHS {MMM/DD/YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorInsul. ThicknessApprox. ODAluminum WeightApprox. Weight
    AWG/KcmilNo. of Strandsinchmilinchlb/1000ftlb/1000ft
    585843670.169850.3492459
    586673470.212850.3833977
    586672260.268850.43862104
    619879180.2981050.51978146
    5912561/0100.3361050.54699164
    5836732/0120.3761050.586125195
    5771003/0160.4221050.633158235
    5836784/0190.4741050.685199284
    577101250220.5201200.760235350
    584290300210.5691200.810282397
    582174350350.6151200.856329462
    584291400350.6591200.899376518
    582267500340.7351200.978471615
    585499600370.8121351.083565745
    586013750610.9081351.178706904
    6413871000581.0601351.3309421168
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 60°CAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    58584361.41570.6740.8120.051405055
    58667341.52500.4240.5100.048556575
    58667221.83980.2670.3210.0457590100
    61987912.15020.2110.2540.04685100115
    5912561/02.26330.1680.2010.044100120135
    5836732/02.37980.1330.1600.043115135150
    5771003/02.510060.1050.1260.042130155175
    5836784/02.712690.0840.1000.041150180205
    5771012503.015000.0710.0860.041170205230
    5842903003.218000.0590.0710.041195230260
    5821743503.421000.0500.0620.040210250280
    5842914003.624000.0440.0540.040225270305
    5822675003.930000.0350.0440.039260310350
    5854996005.436000.0290.0370.039285340385
    5860137505.945000.0240.0310.038320385435
    64138710006.760000.0180.0250.037375445500
    * Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
    * Inductive Reactance is based on non-ferrous conduit with one diameter spacing.

    Stock Codes and Colors

    SizeBlackBrownOrangeYellowWhiteRedGreen
    AWG/KcmilBlackBrownOrangeYellowWhiteRedGreen
    6585843
    4586673
    2586672589171
    1619879589051
    1/0591256591241
    2/0583673
    3/0577100669515669516669517577843669518
    4/0583678597698607400591242
    250577101577844668535
    300584290589170675225
    350582174597996592618
    400584291596689652801
    500582267591243591244591245586671588797591246
    600585499591247588799
    750586013589375592619
    1000641387641386