SPEC 70070

600V SEOPRENE® SEOOW Cord Control with Black Jacket 105°C. Silicone-Free

600 Volt Cord. 105°C Premium Oil Resistance, Sunlight, Water Resistance and Flame Retardant

...

Construction:

  1. Conductor:Class K stranded bare copper per ASTM B-174
  2. Insulation:Heat, moisture and oil resistant TPE
  3. Filler:Non-wicking polypropylene fillers, with a tissue-paper separator wrapped around the assembly
  4. Jacket:Black TPE (other colors available upon request)

Applications and Features:

Southwire Type SEOOW Flexible Cords UL/ CSA listed are permitted for use as specified by Article 400 and related articles of the 2020 National Electrical Code. The cable is rated -40°C to 105°C, water, oil, and weather resistant. Southwire Type SEOOW Flexible Cords are designed for extra hard usage on industrial equipment, heavy tools, battery chargers, portable lights, welding leads, marine dockside power, power extensions and mining applications.

Specifications:

  • UL 62 Flexible Cords and Cables
  • CSA C22.2 No. 49 Flexible Cords and Cables
  • Passes CSA FT2 Flame Test
  • RoHS-3 Complies with European Directive 2015/863
  • NEC Article 400 Flexible Cords, Cables and Fixture Wire
  • NEC Article 501.140 Class I Division 2
  • Sample Print Legend:

    SOUTHWIRE® SEOPRENE® CORD X/C XX AWG (X.XXmm2) SEOOW E46194 (UL) 600V -40C TO 105C -- CSA LL90458 SEOOW 600V -50C TO 105C FT2 WATER RESISTANT

    Packaging:

    Standard lengths: 250', 500' and 1,000' reels. Other lengths available upon request.
    Table 1 – Weights and Measurements
    Stock NumberCCI Part #Cond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacityInsul. ColorJacket Color
    AWG/KcmilNo.No.milmilinchlb/1000ftAmp
    550560222251821630600.3425210BK/WEBlack
    550561223251831630650.365647BK/WE/GNBlack
    551469224251841630600.387745WE/BK/GN/RBlack
    569645305051851630850.4621065BK/WE/RD/GBlack
    598758306051861630800.4841165BK/WE/RD/GBlack
    598728307051871630800.4881244BK/WE/RD/GBlack
    598729308051881630800.5171384BK/WE/RD/GBlack
    5987303100518101630800.6001703BK/WE/RD/GBlack
    5987313120518121630800.6131903BK/WE/RD/GBlack
    5987323140518141630800.6402143BK/WE/RD/GBlack
    5954873160518161630950.6972553BK/WE/RD/GBlack
    598733NA182441301000.8103443BK/WE/RD/GBlack
    550634222261622630600.3686313BK/WEBlack
    550464224261642630600.416938BK/WE/GN/RBlack
    550555305061652630800.4921288BK/WE/RD/GBlack
    595375307061672630800.5251547BK/WE/RD/GBlack
    562791306061662630850.5331498BK/WE/RD/GBlack
    589888308061682630800.5601737BK/WE/RD/GBlack
    5987353100616102630800.6382115BK/WE/RD/GBlack
    5948893120616122630950.6982595BK/WE/RD/GBlack
    5987363140616142630950.7252865BK/WE/RD/GBlack
    5987373160616162630950.7573165BK/WE/RD/GBlack
    595667NA16246530950.8644424BK/WE/RD/GBlack
    550562222271424145800.49711318BK/WEBlack
    550398223271434145800.52213615BK/WE/GNBlack
    550399224271444145900.59218012BK/WE/RD/GBlack
    598739306071464145950.69024712BK/WE/RD/GBlack
    598740307071474145950.69026110BK/WE/RD/GBlack
    598741308071484145950.74329810BK/WE/RD/GBlack
    5899213100714104145950.8353527BK/WE/RD/GBlack
    5504322222812265451050.57015825BK/WEBlack
    550395223281236545950.60319320BK/WE/GNBlack
    550397224281246545950.64223116BK/WE/RD/GBlack
    5504973050812565451050.70728416BK/WE/RD/GBlack
    598745306081266545950.74531616BK/WE/RD/GBlack
    598746308081286545950.80437614BK/WE/RD/GBlack
    55043122229102104451000.61719630BK/WEBlack
    55039322329103104451050.65224625BK/WE/GNBlack
    55039422429104104451000.70330420BK/WE/RD/GBlack
    55087530509105104451050.76236320BK/WE/RD/GBlack
    59875230709107104451150.84546917BK/WE/RD/GBlack
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Ampacities are based on TABLE 400.5(A)(1) of the 2023 National Electrical Code and CEC Table 12.
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCCI Part #Cond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacity *Insul. ColorJacket Color
    AWG/KcmilNo.No.mmmmmmkg/kmAmp
    55056022225182160.761.528.697710BK/WEBlack
    55056122325183160.761.659.27957BK/WE/GNBlack
    55146922425184160.761.529.831105WE/BK/GN/RBlack
    56964530505185160.762.1611.731585BK/WE/RD/GBlack
    59875830605186160.762.0312.291735BK/WE/RD/GBlack
    59872830705187160.762.0312.401854BK/WE/RD/GBlack
    59872930805188160.762.0313.132054BK/WE/RD/GBlack
    598730310051810160.762.0315.242533BK/WE/RD/GBlack
    598731312051812160.762.0315.572833BK/WE/RD/GBlack
    598732314051814160.762.0316.263183BK/WE/RD/GBlack
    595487316051816160.762.4117.703793BK/WE/RD/GBlack
    598733NA1824410.762.5420.575123BK/WE/RD/GBlack
    55063422226162260.761.529.359413BK/WEBlack
    55046422426164260.761.5210.571388BK/WE/GN/RBlack
    55055530506165260.762.0312.501908BK/WE/RD/GBlack
    59537530706167260.762.0313.332297BK/WE/RD/GBlack
    56279130606166260.762.1613.542228BK/WE/RD/GBlack
    58988830806168260.762.0314.222577BK/WE/RD/GBlack
    598735310061610260.762.0316.213145BK/WE/RD/GBlack
    594889312061612260.762.4117.733855BK/WE/RD/GBlack
    598736314061614260.762.4118.424265BK/WE/RD/GBlack
    598737316061616260.762.4119.234705BK/WE/RD/GBlack
    595667NA1624650.762.4121.956584BK/WE/RD/GBlack
    55056222227142411.142.0312.6216818BK/WEBlack
    55039822327143411.142.0313.2620215BK/WE/GNBlack
    55039922427144411.142.2915.0426812BK/WE/RD/GBlack
    59873930607146411.142.4117.5336812BK/WE/RD/GBlack
    59874030707147411.142.4117.5338810BK/WE/RD/GBlack
    59874130807148411.142.4118.8744310BK/WE/RD/GBlack
    589921310071410411.142.4121.215247BK/WE/RD/GBlack
    55043222228122651.142.6714.4823525BK/WEBlack
    55039522328123651.142.4115.3228720BK/WE/GNBlack
    55039722428124651.142.4116.3134416BK/WE/RD/GBlack
    55049730508125651.142.6717.9642316BK/WE/RD/GBlack
    59874530608126651.142.4118.9247016BK/WE/RD/GBlack
    59874630808128651.142.4120.4256014BK/WE/RD/GBlack
    550431222291021041.142.5415.6729230BK/WEBlack
    550393223291031041.142.6716.5636625BK/WE/GNBlack
    550394224291041041.142.5417.8645220BK/WE/RD/GBlack
    550875305091051041.142.6719.3554020BK/WE/RD/GBlack
    598752307091071041.142.9221.4669817BK/WE/RD/GBlack
    * Ampacities are based on TABLE 400.5(A)(1) of the 2023 National Electrical Code and CEC Table 12.

    Color Code

    # of ConductorColor SequenceTracer# of ConductorColor SequenceTracer
    1Black21OrangeGreen
    2White22BlackWhite/Red
    3Red23WhiteBlack/Red
    4Green24RedBlack/White
    5Orange25GreenBlack/White
    6Blue26OrangeBlack/White
    7WhiteBlack27BlueBlack/White
    8RedBlack28BlackRed/Green
    9GreenBlack29WhiteRed/Green
    10OrangeBlack30RedBlack/Green
    11BlueBlack31GreenBlack/Orange
    12BlackWhite32OrangeBlack/Green
    13RedWhite33BlueWhite/Orange
    14GreenWhite34BlackWhite/Orange
    15BlueWhite35WhiteRed/Orange
    16BlackRed36OrangeWhite/Blue
    17WhiteRed37WhiteRed/Blue
    18OrangeRed38BlackWhite/Green
    19BlueRed39WhiteBlack/Green
    20RedGreen40RedWhite/Green

    Revision: 1.000.000

    Updated On: Dec. 16, 2023, 11:32 p.m. UTC