SPEC 85085

CU 600 V FR-XLPE Shielded CPE Jacket Power Cable Color Method 1 Table 2

Power Cable 600 or 1000 Volt Three Conductor Copper, Fire Retardant Cross-Linked Polyethylene (FR-XLPE) insulation Shielded Chlorinated Polyethylene (CPE) Jacket Conductor Identification Method 1 Table 2

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Fire Retardant Cross Linked Polyethylene (FR-XLPE)
  3. Filler:Paper or Polypropylene filler
  4. Binder:Polyester flat thread binder tape
  5. Shield:5 mils tape shield
  6. Rip Cord:Rip cord for ease of jacket removal
  7. Overall Jacket:Chlorinated Polyethylene (CPE) Jacket

Applications and Features:

Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Sample Print Legend:

    SOUTHWIRE MASTER-DESIGN XX AWG XX/C FR-XLPE CDRS 90C COPPER SHIELDED CPE JKT 600V SUN. RES. DIRECT BURIAL YEAR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessDiameter Over InsulationJacket ThicknessApprox. ODApprox. WeightDC Resistance @ 25°CAC Resistance @ 90°CMin Bending RadiusAllowable Ampacity At 60°C *Allowable Ampacity 75°C *Allowable Ampacity 90°C *
    AWGNo.strandsinchmilinchmilinchlb/1000ftΩ/1000ftΩ/1000ftinchAmpAmpAmp
    TBA8270.139450.229600.592060.6520.8157.1405055
    TBA8370.139450.229600.6152750.6520.8157.4405055
    TBA8470.139450.229600.6733470.6520.8158.1324044
    603609812190.143450.233801.15710690.6520.81513.9202527
    TBA6270.174450.264600.6612850.4110.5147.9556575
    TBA6370.174450.264600.6913940.4110.5148.3556575
    TBA6470.174450.264600.7955700.4110.5149.5445260
    TBA6470.174450.264800.8395820.4110.51410.1445260
    TBA4270.221450.311600.7534090.2580.3239708595
    TBA4370.221450.311600.7915570.2580.3239.5708595
    TBA4470.221450.311800.9388260.2580.32311.3566876
    TBA2270.277450.367800.9076300.1620.20310.995115130
    TBA2370.277450.367800.9538610.1620.20311.495115130
    TBA2470.277450.367801.04711090.1620.20312.67692104
    TBA12190.321550.431801.0367890.1290.16112.4110130145
    TBA13190.321550.431801.09110790.1290.16213.1110130145
    TBA14190.321550.431801.20013920.1290.16114.488104116
    TBA1/02190.36550.47801.1169560.1020.12813.4125150150
    TBA1/03190.360550.470801.17513170.1020.12814.1125150170
    TBA1/04190.360550.470801.29517040.1020.12815.5100120136
    TBA2/02190.404550.515801.20211620.0810.10114.4145175195
    TBA2/03190.404550.514801.27016130.0810.10215.2145175195
    TBA2/04190.404550.514801.40120930.0810.10116.8116140156
    TBA3/02190.454550.564801.30414220.0640.0815.7165200225
    TBA3/03190.454550.564801.37819860.0640.08116.5165200225
    TBA3/04190.454550.564801.52125820.0640.08018.3132160180
    TBA4/02190.51550.62801.41617440.0510.06417195230260
    TBA4/03190.510550.620801.49924490.0510.06418195230260
    TBA4/04190.510550.620801.65731910.0510.06420156184208
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item

    Revision: