SPEC 26142
HVTECK CU 3/C 115NLEPR TS PVC AIA PVC 5kV 133% CSA
3 Conductor, 115 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Conductor Shield:Semi-conducting cross-linked copolymer
- Insulation:115 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Filler:Interstices filled with non-hydroscoping/non-wicking fillers
- Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
- Binder:Polypropylene tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 5kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL) and 105°C for use in harsh Canadian environments. For installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CU 115 NLEPR AIA 5kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground Size | Dia. Over Inner Jacket | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | inch | inch | mil | inch | AWG | inch | inch | mil | inch | lb/1000ft | |
582464^ | 2 | 7 | 0.283 | 0.550 | 115 | 0.610 | 6 | 1.533 | 1.853 | 60 | 1.973 | 2065 |
646923 | 2 | 7 | 0.283 | 0.550 | 115 | 0.610 | 6 | 1.533 | 1.853 | 60 | 1.973 | 2065 |
TBA | 1 | 19 | 0.322 | 0.589 | 115 | 0.649 | 6 | 1.617 | 1.937 | 60 | 2.057 | 2313 |
644322^ | 1/0 | 19 | 0.362 | 0.629 | 115 | 0.689 | 6 | 1.703 | 2.033 | 60 | 2.153 | 2678 |
582463^ | 2/0 | 19 | 0.405 | 0.672 | 115 | 0.732 | 6 | 1.856 | 2.186 | 60 | 2.306 | 3164 |
599626 | 2/0 | 19 | 0.405 | 0.672 | 115 | 0.732 | 6 | 1.856 | 2.186 | 60 | 2.306 | 3164 |
TBA | 3/0 | 19 | 0.456 | 0.723 | 115 | 0.783 | 4 | 1.966 | 2.296 | 60 | 2.416 | 3674 |
TBA | 4/0 | 19 | 0.512 | 0.779 | 115 | 0.839 | 4 | 2.087 | 2.417 | 60 | 2.537 | 4234 |
646655^ | 250 | 37 | 0.558 | 0.834 | 115 | 0.894 | 4 | 2.206 | 2.536 | 75 | 2.686 | 4814 |
646924 | 250 | 37 | 0.558 | 0.834 | 115 | 0.894 | 4 | 2.206 | 2.536 | 75 | 2.686 | 4814 |
646645^ | 350 | 37 | 0.661 | 0.937 | 115 | 0.997 | 3 | 2.429 | 2.759 | 75 | 2.909 | 6075 |
588713^ | 500 | 37 | 0.789 | 1.065 | 115 | 1.125 | 3 | 2.705 | 3.035 | 75 | 3.185 | 7844 |
TBA | 750 | 61 | 0.968 | 1.253 | 115 | 1.313 | 2 | 3.161 | 3.491 | 85 | 3.661 | 11013 |
TBA | 1000 | 61 | 1.117 | 1.402 | 115 | 1.462 | 1 | 3.483 | 3.813 | 85 | 3.983 | 13877 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
^Yellow outer jacket
^Yellow outer jacket
Table 2 – Electrical and Engineering Data
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity in Vented Cable Tray 90°C‡ | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
2 | 13.8 | 1593 | 0.162 | 0.203 | 0.036 | 0.040 | 0.573+j0.514 | 0.203+j0.040 | 4.5 | 172 | 201 |
2 | 13.8 | 1593 | 0.162 | 0.203 | 0.036 | 0.040 | 0.573+j0.514 | 0.203+j0.040 | 4.5 | 172 | 201 |
1 | 14.4 | 2009 | 0.129 | 0.161 | 0.033 | 0.039 | 0.534+j0.492 | 0.161+j0.038 | 5.7 | 197 | 228 |
1/0 | 15.1 | 2534 | 0.102 | 0.128 | 0.030 | 0.037 | 0.503+j0.470 | 0.128+j0.037 | 7.2 | 225 | 257 |
2/0 | 16.1 | 3194 | 0.081 | 0.102 | 0.027 | 0.036 | 0.478+j0.448 | 0.102+j0.036 | 9.0 | 260 | 292 |
2/0 | 16.1 | 3194 | 0.081 | 0.102 | 0.027 | 0.036 | 0.478+j0.448 | 0.102+j0.036 | 9.0 | 260 | 292 |
3/0 | 16.9 | 4027 | 0.0642 | 0.081 | 0.025 | 0.035 | 0.457+j0.423 | 0.081+j0.035 | 11.4 | 297 | 330 |
4/0 | 17.8 | 5078 | 0.051 | 0.064 | 0.023 | 0.034 | 0.438+j0.398 | 0.064+j0.034 | 14.3 | 342 | 372 |
250 | 18.8 | 6000 | 0.0431 | 0.054 | 0.022 | 0.033 | 0.426+j0.375 | 0.054+j0.033 | 16.9 | 376 | 410 |
250 | 18.8 | 6000 | 0.0431 | 0.054 | 0.022 | 0.033 | 0.426+j0.375 | 0.054+j0.033 | 16.9 | 376 | 410 |
350 | 20.4 | 8400 | 0.0308 | 0.039 | 0.019 | 0.032 | 0.404+j0.337 | 0.039+j0.032 | 23.7 | 460 | 487 |
500 | 22.3 | 12000 | 0.0216 | 0.028 | 0.016 | 0.030 | 0.383+j0.296 | 0.028+j0.030 | 33.9 | 556 | 573 |
750 | 25.6 | 18000 | 0.0144 | 0.020 | 0.014 | 0.029 | 0.357+j0.247 | 0.020+j0.029 | 50.8 | 678 | 668 |
1000 | 27.9 | 24000 | 0.0108 | 0.016 | 0.012 | 0.028 | 0.338+j0.216 | 0.017+j0.028 | 67.8 | 798 | 772 |
* Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
Table 3 – Weights and Measurements (Metric)
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground Size | Dia. Over Inner Jacket | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | mm | mm | mm | mm | AWG | mm | mm | mm | mm | kg/km | |
582464^ | 2 | 7 | 7.19 | 13.97 | 2.92 | 15.49 | 6 | 38.94 | 47.07 | 1.52 | 50.11 | 3073 |
646923 | 2 | 7 | 7.19 | 13.97 | 2.92 | 15.49 | 6 | 38.94 | 47.07 | 1.52 | 50.11 | 3073 |
TBA | 1 | 19 | 8.18 | 14.96 | 2.92 | 16.48 | 6 | 41.07 | 49.20 | 1.52 | 52.25 | 3442 |
644322^ | 1/0 | 19 | 9.19 | 15.98 | 2.92 | 17.50 | 6 | 43.26 | 51.64 | 1.52 | 54.69 | 3985 |
582463^ | 2/0 | 19 | 10.29 | 17.07 | 2.92 | 18.59 | 6 | 47.14 | 55.52 | 1.52 | 58.57 | 4709 |
599626 | 2/0 | 19 | 10.29 | 17.07 | 2.92 | 18.59 | 6 | 47.14 | 55.52 | 1.52 | 58.57 | 4709 |
TBA | 3/0 | 19 | 11.58 | 18.36 | 2.92 | 19.89 | 4 | 49.94 | 58.32 | 1.52 | 61.37 | 5468 |
TBA | 4/0 | 19 | 13.00 | 19.79 | 2.92 | 21.31 | 4 | 53.01 | 61.39 | 1.52 | 64.44 | 6301 |
646655^ | 250 | 37 | 14.17 | 21.18 | 2.92 | 22.71 | 4 | 56.03 | 64.41 | 1.91 | 68.22 | 7164 |
646924 | 250 | 37 | 14.17 | 21.18 | 2.92 | 22.71 | 4 | 56.03 | 64.41 | 1.91 | 68.22 | 7164 |
646645^ | 350 | 37 | 16.79 | 23.80 | 2.92 | 25.32 | 3 | 61.70 | 70.08 | 1.91 | 73.89 | 9041 |
588713^ | 500 | 37 | 20.04 | 27.05 | 2.92 | 28.58 | 3 | 68.71 | 77.09 | 1.91 | 80.90 | 11673 |
TBA | 750 | 61 | 24.59 | 31.83 | 2.92 | 33.35 | 2 | 80.29 | 88.67 | 2.16 | 92.99 | 16389 |
TBA | 1000 | 61 | 28.37 | 35.61 | 2.92 | 37.13 | 1 | 88.47 | 96.85 | 2.16 | 101.17 | 20651 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
^Yellow outer jacket
^Yellow outer jacket
Table 4 – Electrical and Engineering Data (Metric)
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity in Vented Cable Tray 90°C‡ | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
2 | 350.52 | 7089 | 0.5315 | 0.67 | 0.0110 | 0.1312 | 0.573+j0.514 | 0.203+j0.040 | 4.5 | 172 | 201 |
2 | 350.52 | 7089 | 0.5315 | 0.67 | 0.0110 | 0.1312 | 0.573+j0.514 | 0.203+j0.040 | 4.5 | 172 | 201 |
1 | 365.76 | 8940 | 0.4232 | 0.53 | 0.0101 | 0.1280 | 0.534+j0.492 | 0.161+j0.038 | 5.7 | 197 | 228 |
1/0 | 383.54 | 11276 | 0.3346 | 0.42 | 0.0091 | 0.1214 | 0.503+j0.470 | 0.128+j0.037 | 7.2 | 225 | 257 |
2/0 | 408.94 | 14213 | 0.2657 | 0.33 | 0.0082 | 0.1181 | 0.478+j0.448 | 0.102+j0.036 | 9.0 | 260 | 292 |
2/0 | 408.94 | 14213 | 0.2657 | 0.33 | 0.0082 | 0.1181 | 0.478+j0.448 | 0.102+j0.036 | 9.0 | 260 | 292 |
3/0 | 429.26 | 17920 | 0.2106 | 0.27 | 0.0076 | 0.1148 | 0.457+j0.423 | 0.081+j0.035 | 11.4 | 297 | 330 |
4/0 | 452.12 | 22597 | 0.1673 | 0.21 | 0.0070 | 0.1115 | 0.438+j0.398 | 0.064+j0.034 | 14.3 | 342 | 372 |
250 | 477.52 | 26700 | 0.1414 | 0.18 | 0.0067 | 0.1083 | 0.426+j0.375 | 0.054+j0.033 | 16.9 | 376 | 410 |
250 | 477.52 | 26700 | 0.1414 | 0.18 | 0.0067 | 0.1083 | 0.426+j0.375 | 0.054+j0.033 | 16.9 | 376 | 410 |
350 | 518.16 | 37380 | 0.1010 | 0.13 | 0.0058 | 0.1050 | 0.404+j0.337 | 0.039+j0.032 | 23.7 | 460 | 487 |
500 | 566.42 | 53400 | 0.0709 | 0.09 | 0.0049 | 0.0984 | 0.383+j0.296 | 0.028+j0.030 | 33.9 | 556 | 573 |
750 | 650.24 | 80100 | 0.0472 | 0.07 | 0.0043 | 0.0951 | 0.357+j0.247 | 0.020+j0.029 | 50.8 | 678 | 668 |
1000 | 708.66 | 106800 | 0.0354 | 0.05 | 0.0037 | 0.0919 | 0.338+j0.216 | 0.017+j0.028 | 67.8 | 798 | 772 |
* Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
Revision: 3.0.00C