SPEC 26205

HVTECK CU 1/C 115NLEPR CB PVC AIA PVC 8kV 100% CSA

Single Conductor, 115 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:115 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
  6. Neutral Separator:Mylar tape
  7. Inner Jacket:PVC inner jacket
  8. Armour:Aluminum Interlocked Armour (AIA)
  9. Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 8kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL) and 105°C for use in harsh Canadian environments. For installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable. When used in a 3 phase system, the combination of each bond conductor from each single conductor cable provide a 100% bonded system to ground.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 115 NLEPR AIA 8kV 100% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralDia. Over Inner JacketDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchNo. x AWGinchinchmilinchlb/1000ft
    TBA270.2830.5501150.63011x160.8621.072501.172752
    TBA1190.3220.5891150.66917x160.9011.111501.211875
    TBA1/0190.3620.6291150.70917x160.9411.261501.3611045
    TBA2/0190.4050.6721150.75217x161.0141.334501.4341196
    TBA3/0190.4560.7231150.80321x161.0651.385501.4851371
    TBA4/0190.5120.7791150.85921x161.1211.441501.5411547
    TBA250370.5580.8341150.91427x161.1761.496501.5961751
    TBA350370.6610.9371151.01721x141.3051.625501.7252196
    TBA500370.7891.0651151.16527x141.4531.773501.8732852
    TBA750610.9681.2531151.35333x141.6411.961602.0813876
    TBA1000611.1171.4021151.50233x141.7902.120602.2404826
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity in Vented Cable Tray 90°C‡Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    28.25310.1620.2030.0360.0540.502+j0.1890.205+j0.0544.5215221
    18.56700.1290.1610.0330.0520.385+j0.1070.164+j0.0525.7245247
    1/09.58450.1020.1280.0300.0520.352+j0.1060.131+j0.0527.2278275
    2/010.010650.0810.1010.0270.0510.324+j0.1050.104+j0.0509.0317306
    3/010.413420.06420.0800.0250.0490.269+j0.0790.084+j0.04811.4357335
    4/010.816930.0510.0640.0230.0470.253+j0.0780.068+j0.04614.3404369
    25011.220000.04310.0540.0220.0460.206+j0.0570.059+j0.04516.9456412
    35012.128000.03080.0390.0190.0440.164+j0.0450.044+j0.04223.7537456
    50013.140000.02160.0280.0160.0420.127+j0.0340.034+j0.04033.9616497
    75014.660000.01440.0190.0140.0390.101+j0.0280.026+j0.03750.8706551
    100015.780000.01080.0150.0120.0380.097+j0.0270.022+j0.03567.8813596
    * Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralDia. Over Inner JacketDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmkg/km
    TBA277.1913.972.9216.0011x1621.8927.231.2729.771119
    TBA1198.1814.962.9216.9917x1622.8928.221.2730.761302
    TBA1/0199.1915.982.9218.0117x1623.9032.031.2734.571555
    TBA2/01910.2917.072.9219.1017x1625.7633.881.2736.421780
    TBA3/01911.5818.362.9220.4021x1627.0535.181.2737.722040
    TBA4/01913.0019.792.9221.8221x1628.4736.601.2739.142302
    TBA2503714.1721.182.9223.2227x1629.8738.001.2740.542606
    TBA3503716.7923.802.9225.8321x1433.1541.281.2743.823268
    TBA5003720.0427.052.9229.5927x1436.9145.031.2747.574244
    TBA7506124.5931.832.9234.3733x1441.6849.811.5252.865768
    TBA10006128.3735.612.9238.1533x1445.4753.851.5256.907182
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity in Vented Cable Tray 90°C‡Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftkAmpAmpAmp
    2208.2823630.53150.670.01100.17720.502+j0.1890.205+j0.0544.5215221
    1215.9029820.42320.530.01010.17060.385+j0.1070.164+j0.0525.7245247
    1/0241.3037600.33460.420.00910.17060.352+j0.1060.131+j0.0527.2278275
    2/0254.0047390.26570.330.00820.16730.324+j0.1050.104+j0.0509.0317306
    3/0264.1659720.21060.260.00760.16080.269+j0.0790.084+j0.04811.4357335
    4/0274.3275340.16730.210.00700.15420.253+j0.0780.068+j0.04614.3404369
    250284.4889000.14140.180.00670.15090.206+j0.0570.059+j0.04516.9456412
    350307.34124600.10100.130.00580.14440.164+j0.0450.044+j0.04223.7537456
    500332.74178000.07090.090.00490.13780.127+j0.0340.034+j0.04033.9616497
    750370.84267000.04720.060.00430.12800.101+j0.0280.026+j0.03750.8706551
    1000398.78356000.03540.050.00370.12470.097+j0.0270.022+j0.03567.8813596
    * Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I

    Revision: 3.0.00C