SPEC 26236

HVTECK AL 1/C 140TRXLPE CB PVC AIA PVC 8kV 133% CSA

Single Conductor, 140 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:140 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
  6. Neutral Separator:Mylar tape
  7. Inner Jacket:PVC inner jacket
  8. Armour:Aluminum Interlocked Armour (AIA)
  9. Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 8kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL) and 105°C for use in harsh Canadian environments. For installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable. When used in a 3 phase system, the combination of each bond conductor from each single conductor cable provide a 100% bonded system to ground.

Specifications:

  • ASTM B800 8000 Series Aluminum Alloy Wire
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 140 TRXLPE AIA 8kV 133% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralDia. Over Inner JacketDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchNo. x AWGinchinchmilinchlb/1000ft
    TBA270.2680.5851400.66511x160.8971.107501.207619
    TBA1190.2990.6161400.69611x160.9281.248501.348731
    TBA1/0190.3360.6531400.73311x160.9651.285501.385776
    TBA2/0190.3760.6931400.77317x161.0351.355501.455912
    TBA3/0190.4230.7401400.82017x161.0821.402501.502978
    TBA4/0190.4750.7921400.87217x161.1341.454501.5541055
    TBA250370.5200.8461400.92621x161.1881.508501.6081164
    TBA350370.6160.9421401.02227x161.2841.604501.7041372
    TBA500370.7361.0621401.16221x141.4501.770501.8701686
    TBA750610.9081.2651401.36527x141.6531.973602.0932195
    TBA1000611.0601.4171401.51727x141.8052.135602.2552612
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity in Vented Cable Tray 90°C‡Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    28.43980.2660.3340.0530.0560.632+j0.1920.336+j0.0563.1169176
    19.45020.2110.2650.0490.0560.562+j0.1910.267+j0.0563.9194198
    1/09.76340.1680.2110.0450.0540.508+j0.1900.213+j0.0545.0222223
    2/010.27990.1330.1670.0420.0530.390+j0.1080.170+j0.0526.3255250
    3/010.510070.1050.1320.0380.0510.355+j0.1060.135+j0.0507.9290278
    4/010.912700.08360.1050.0350.0490.328+j0.1050.108+j0.0499.9329309
    25011.315000.07070.0890.0330.0480.278+j0.0800.093+j0.04711.8370347
    35011.921000.05050.0640.0290.0450.216+j0.0570.068+j0.04416.4446402
    50013.130000.03540.0450.0250.0430.170+j0.0460.050+j0.04223.5533451
    75014.745000.02360.0300.0230.0410.129+j0.0350.036+j0.03935.3631500
    100015.860000.01770.0230.0200.0390.122+j0.0340.028+j0.03747.0707539
    * Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralDia. Over Inner JacketDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmkg/km
    TBA276.8114.863.5616.8911x1622.7828.121.2730.66921
    TBA1197.5915.653.5617.6811x1623.5731.701.2734.241088
    TBA1/0198.5316.593.5618.6211x1624.5132.641.2735.181155
    TBA2/0199.5517.603.5619.6317x1626.2934.421.2736.961357
    TBA3/01910.7418.803.5620.8317x1627.4835.611.2738.151455
    TBA4/01912.0720.123.5622.1517x1628.8036.931.2739.471570
    TBA2503713.2121.493.5623.5221x1630.1838.301.2740.841732
    TBA3503715.6523.933.5625.9627x1632.6140.741.2743.282042
    TBA5003718.6926.973.5629.5121x1436.8344.961.2747.502509
    TBA7506123.0632.133.5634.6727x1441.9950.111.5253.163267
    TBA10006126.9235.993.5638.5327x1445.8554.231.5257.283887
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity in Vented Cable Tray 90°C‡Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftkAmpAmpAmp
    2213.3617710.87271.100.01620.18370.632+j0.1920.336+j0.0563.1169176
    1238.7622340.69230.870.01490.18370.562+j0.1910.267+j0.0563.9194198
    1/0246.3828210.55120.690.01370.17720.508+j0.1900.213+j0.0545.0222223
    2/0259.0835560.43640.550.01280.17390.390+j0.1080.170+j0.0526.3255250
    3/0266.7044810.34450.430.01160.16730.355+j0.1060.135+j0.0507.9290278
    4/0276.8656520.27430.340.01070.16080.328+j0.1050.108+j0.0499.9329309
    250287.0266750.23200.290.01010.15750.278+j0.0800.093+j0.04711.8370347
    350302.2693450.16570.210.00880.14760.216+j0.0570.068+j0.04416.4446402
    500332.74133500.11610.150.00760.14110.170+j0.0460.050+j0.04223.5533451
    750373.38200250.07740.100.00700.13450.129+j0.0350.036+j0.03935.3631500
    1000401.32267000.05810.080.00610.12800.122+j0.0340.028+j0.03747.0707539
    * Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I

    Revision: 3.0.00C