SPEC 26261
HVTECK AL 3/C 115NLEPR TS PVC AIA PVC 8kV 100% CSA
3 Conductor, 115 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
- Insulation:115 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Filler:Interstices filled with non-hydroscoping/non-wicking fillers
- Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
- Binder:Polypropylene tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 8kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL) and 105°C for use in harsh Canadian environments. For installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CPT AL 115 NLEPR AIA 8kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground Size | Dia. Over Inner Jacket | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | inch | inch | mil | inch | AWG | inch | inch | mil | inch | lb/1000ft | |
TBA | 2 | 7 | 0.268 | 0.535 | 115 | 0.595 | 8 | 1.500 | 1.820 | 60 | 1.940 | 1556 |
TBA | 1 | 19 | 0.299 | 0.566 | 115 | 0.626 | 6 | 1.567 | 1.887 | 60 | 2.007 | 1708 |
TBA | 1/0 | 19 | 0.336 | 0.603 | 115 | 0.663 | 6 | 1.647 | 1.977 | 60 | 2.097 | 1919 |
TBA | 2/0 | 19 | 0.376 | 0.643 | 115 | 0.703 | 6 | 1.734 | 2.064 | 60 | 2.184 | 2093 |
TBA | 3/0 | 19 | 0.423 | 0.690 | 115 | 0.750 | 6 | 1.895 | 2.225 | 60 | 2.345 | 2433 |
TBA | 4/0 | 19 | 0.475 | 0.742 | 115 | 0.802 | 6 | 2.008 | 2.338 | 60 | 2.458 | 2692 |
TBA | 250 | 37 | 0.520 | 0.796 | 115 | 0.856 | 4 | 2.124 | 2.454 | 60 | 2.574 | 3003 |
TBA | 350 | 37 | 0.616 | 0.892 | 115 | 0.952 | 4 | 2.332 | 2.662 | 75 | 2.812 | 3624 |
TBA | 500 | 37 | 0.736 | 1.012 | 115 | 1.072 | 3 | 2.591 | 2.921 | 75 | 3.071 | 4424 |
TBA | 750 | 61 | 0.908 | 1.215 | 115 | 1.275 | 2 | 3.079 | 3.409 | 85 | 3.579 | 6036 |
TBA | 1000 | 61 | 1.060 | 1.367 | 115 | 1.427 | 2 | 3.408 | 3.738 | 85 | 3.908 | 7231 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 2 – Electrical and Engineering Data
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity in Vented Cable Tray 90°C‡ | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
2 | 13.6 | 1194 | 0.266 | 0.334 | 0.037 | 0.041 | 0.703+j0.523 | 0.334+j0.041 | 2.9 | 135 | 157 |
1 | 14.0 | 1506 | 0.211 | 0.265 | 0.034 | 0.039 | 0.637+j0.505 | 0.265+j0.039 | 3.7 | 154 | 178 |
1/0 | 14.7 | 1901 | 0.168 | 0.211 | 0.032 | 0.038 | 0.585+j0.484 | 0.211+j0.038 | 4.7 | 176 | 202 |
2/0 | 15.3 | 2396 | 0.133 | 0.167 | 0.029 | 0.037 | 0.542+j0.462 | 0.167+j0.037 | 5.9 | 204 | 229 |
3/0 | 16.4 | 3020 | 0.105 | 0.132 | 0.026 | 0.035 | 0.508+j0.439 | 0.132+j0.035 | 7.4 | 234 | 260 |
4/0 | 17.2 | 3809 | 0.0836 | 0.105 | 0.024 | 0.034 | 0.480+j0.414 | 0.105+j0.034 | 9.4 | 268 | 294 |
250 | 18.0 | 4500 | 0.0707 | 0.089 | 0.023 | 0.034 | 0.463+j0.391 | 0.089+j0.034 | 11.1 | 296 | 323 |
350 | 19.7 | 6300 | 0.0505 | 0.064 | 0.020 | 0.032 | 0.433+j0.353 | 0.064+j0.032 | 15.5 | 363 | 386 |
500 | 21.5 | 9000 | 0.0354 | 0.045 | 0.017 | 0.031 | 0.405+j0.312 | 0.045+j0.031 | 22.1 | 447 | 465 |
750 | 25.1 | 13500 | 0.0236 | 0.031 | 0.016 | 0.030 | 0.372+j0.256 | 0.031+j0.030 | 33.2 | 566 | 563 |
1000 | 27.4 | 18000 | 0.0177 | 0.023 | 0.014 | 0.029 | 0.348+j0.223 | 0.024+j0.029 | 44.3 | 661 | 638 |
* Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
Table 3 – Weights and Measurements (Metric)
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground Size | Dia. Over Inner Jacket | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | mm | mm | mm | mm | AWG | mm | mm | mm | mm | kg/km | |
TBA | 2 | 7 | 6.81 | 13.59 | 2.92 | 15.11 | 8 | 38.10 | 46.23 | 1.52 | 49.28 | 2316 |
TBA | 1 | 19 | 7.59 | 14.38 | 2.92 | 15.90 | 6 | 39.80 | 47.93 | 1.52 | 50.98 | 2542 |
TBA | 1/0 | 19 | 8.53 | 15.32 | 2.92 | 16.84 | 6 | 41.83 | 50.22 | 1.52 | 53.26 | 2856 |
TBA | 2/0 | 19 | 9.55 | 16.33 | 2.92 | 17.86 | 6 | 44.04 | 52.43 | 1.52 | 55.47 | 3115 |
TBA | 3/0 | 19 | 10.74 | 17.53 | 2.92 | 19.05 | 6 | 48.13 | 56.52 | 1.52 | 59.56 | 3621 |
TBA | 4/0 | 19 | 12.07 | 18.85 | 2.92 | 20.37 | 6 | 51.00 | 59.39 | 1.52 | 62.43 | 4006 |
TBA | 250 | 37 | 13.21 | 20.22 | 2.92 | 21.74 | 4 | 53.95 | 62.33 | 1.52 | 65.38 | 4469 |
TBA | 350 | 37 | 15.65 | 22.66 | 2.92 | 24.18 | 4 | 59.23 | 67.61 | 1.91 | 71.42 | 5393 |
TBA | 500 | 37 | 18.69 | 25.70 | 2.92 | 27.23 | 3 | 65.81 | 74.19 | 1.91 | 78.00 | 6584 |
TBA | 750 | 61 | 23.06 | 30.86 | 2.92 | 32.39 | 2 | 78.21 | 86.59 | 2.16 | 90.91 | 8983 |
TBA | 1000 | 61 | 26.92 | 34.72 | 2.92 | 36.25 | 2 | 86.56 | 94.95 | 2.16 | 99.26 | 10761 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 4 – Electrical and Engineering Data (Metric)
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity in Vented Cable Tray 90°C‡ | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
2 | 345.44 | 5313 | 0.8727 | 1.10 | 0.0113 | 0.1345 | 0.703+j0.523 | 0.334+j0.041 | 2.9 | 135 | 157 |
1 | 355.60 | 6702 | 0.6923 | 0.87 | 0.0104 | 0.1280 | 0.637+j0.505 | 0.265+j0.039 | 3.7 | 154 | 178 |
1/0 | 373.38 | 8459 | 0.5512 | 0.69 | 0.0098 | 0.1247 | 0.585+j0.484 | 0.211+j0.038 | 4.7 | 176 | 202 |
2/0 | 388.62 | 10662 | 0.4364 | 0.55 | 0.0088 | 0.1214 | 0.542+j0.462 | 0.167+j0.037 | 5.9 | 204 | 229 |
3/0 | 416.56 | 13439 | 0.3445 | 0.43 | 0.0079 | 0.1148 | 0.508+j0.439 | 0.132+j0.035 | 7.4 | 234 | 260 |
4/0 | 436.88 | 16950 | 0.2743 | 0.34 | 0.0073 | 0.1115 | 0.480+j0.414 | 0.105+j0.034 | 9.4 | 268 | 294 |
250 | 457.20 | 20025 | 0.2320 | 0.29 | 0.0070 | 0.1115 | 0.463+j0.391 | 0.089+j0.034 | 11.1 | 296 | 323 |
350 | 500.38 | 28035 | 0.1657 | 0.21 | 0.0061 | 0.1050 | 0.433+j0.353 | 0.064+j0.032 | 15.5 | 363 | 386 |
500 | 546.10 | 40050 | 0.1161 | 0.15 | 0.0052 | 0.1017 | 0.405+j0.312 | 0.045+j0.031 | 22.1 | 447 | 465 |
750 | 637.54 | 60075 | 0.0774 | 0.10 | 0.0049 | 0.0984 | 0.372+j0.256 | 0.031+j0.030 | 33.2 | 566 | 563 |
1000 | 695.96 | 80100 | 0.0581 | 0.08 | 0.0043 | 0.0951 | 0.348+j0.223 | 0.024+j0.029 | 44.3 | 661 | 638 |
* Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
Revision: 3.0.00C