SPEC 26272
HVTECK AL 3/C 140TRXLPE TS PVC AIA PVC 8kV 133% CSA
3 Conductor, 140 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
- Insulation:140 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Filler:Interstices filled with non-hydroscoping/non-wicking fillers
- Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
- Binder:Polypropylene tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 8kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL) and 105°C for use in harsh Canadian environments. For installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CPT AL 140 TRXLPE AIA 8kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground Size | Dia. Over Inner Jacket | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | inch | inch | mil | inch | AWG | inch | inch | mil | inch | lb/1000ft | |
673689 | 2 | 7 | 0.268 | 0.585 | 140 | 0.645 | 8 | 1.608 | 1.928 | 60 | 2.048 | 1648 |
652778 | 1 | 19 | 0.299 | 0.616 | 140 | 0.676 | 6 | 1.675 | 2.005 | 60 | 2.125 | 1864 |
672079 | 1/0 | 19 | 0.336 | 0.653 | 140 | 0.713 | 6 | 1.755 | 2.085 | 60 | 2.205 | 2016 |
674249 | 2/0 | 19 | 0.376 | 0.693 | 140 | 0.753 | 6 | 1.902 | 2.232 | 60 | 2.352 | 2316 |
TBA | 3/0 | 19 | 0.423 | 0.740 | 140 | 0.800 | 6 | 2.003 | 2.333 | 60 | 2.453 | 2537 |
672070 | 4/0 | 19 | 0.475 | 0.792 | 140 | 0.852 | 6 | 2.116 | 2.446 | 60 | 2.566 | 2797 |
TBA | 250 | 37 | 0.520 | 0.846 | 140 | 0.906 | 4 | 2.232 | 2.562 | 75 | 2.712 | 3184 |
652787 | 350 | 37 | 0.616 | 0.942 | 140 | 1.002 | 4 | 2.440 | 2.770 | 75 | 2.920 | 3734 |
674257 | 500 | 37 | 0.736 | 1.062 | 140 | 1.122 | 3 | 2.699 | 3.029 | 75 | 3.179 | 4537 |
TBA | 750 | 61 | 0.908 | 1.265 | 140 | 1.325 | 2 | 3.187 | 3.517 | 85 | 3.687 | 6159 |
TBA | 1000 | 61 | 1.060 | 1.417 | 140 | 1.477 | 2 | 3.516 | 3.846 | 85 | 4.016 | 7355 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 2 – Electrical and Engineering Data
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity in Vented Cable Tray 90°C‡ | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
2 | 14.3 | 1194 | 0.266 | 0.334 | 0.053 | 0.043 | 0.707+j0.498 | 0.334+j0.043 | 3.1 | 126 | 157 |
1 | 14.9 | 1506 | 0.211 | 0.265 | 0.049 | 0.041 | 0.639+j0.480 | 0.265+j0.041 | 3.9 | 144 | 178 |
1/0 | 15.4 | 1901 | 0.168 | 0.211 | 0.045 | 0.040 | 0.586+j0.460 | 0.211+j0.040 | 5.0 | 162 | 202 |
2/0 | 16.5 | 2396 | 0.133 | 0.167 | 0.042 | 0.038 | 0.543+j0.440 | 0.167+j0.038 | 6.3 | 188 | 229 |
3/0 | 17.2 | 3020 | 0.105 | 0.132 | 0.038 | 0.037 | 0.507+j0.418 | 0.132+j0.037 | 7.9 | 213 | 260 |
4/0 | 18.0 | 3809 | 0.0836 | 0.105 | 0.035 | 0.036 | 0.479+j0.394 | 0.105+j0.036 | 9.9 | 240 | 294 |
250 | 19.0 | 4500 | 0.0707 | 0.089 | 0.033 | 0.035 | 0.460+j0.372 | 0.089+j0.035 | 11.8 | 264 | 323 |
350 | 20.4 | 6300 | 0.0505 | 0.064 | 0.029 | 0.033 | 0.429+j0.337 | 0.064+j0.033 | 16.4 | 317 | 386 |
500 | 22.3 | 9000 | 0.0354 | 0.045 | 0.025 | 0.032 | 0.400+j0.298 | 0.045+j0.032 | 23.5 | 389 | 465 |
750 | 25.8 | 13500 | 0.0236 | 0.030 | 0.023 | 0.031 | 0.366+j0.246 | 0.030+j0.031 | 35.3 | 472 | 563 |
1000 | 28.1 | 18000 | 0.0177 | 0.023 | 0.020 | 0.030 | 0.343+j0.215 | 0.024+j0.030 | 47.0 | 544 | 638 |
* Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E or D17G of the 2021 Canadian Electrical Code Part I
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E or D17G of the 2021 Canadian Electrical Code Part I
Table 3 – Weights and Measurements (Metric)
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground Size | Dia. Over Inner Jacket | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | mm | mm | mm | mm | AWG | mm | mm | mm | mm | kg/km | |
673689 | 2 | 7 | 6.81 | 14.86 | 3.56 | 16.38 | 8 | 40.84 | 48.97 | 1.52 | 52.02 | 2452 |
652778 | 1 | 19 | 7.59 | 15.65 | 3.56 | 17.17 | 6 | 42.55 | 50.93 | 1.52 | 53.97 | 2774 |
672079 | 1/0 | 19 | 8.53 | 16.59 | 3.56 | 18.11 | 6 | 44.58 | 52.96 | 1.52 | 56.01 | 3000 |
674249 | 2/0 | 19 | 9.55 | 17.60 | 3.56 | 19.13 | 6 | 48.31 | 56.69 | 1.52 | 59.74 | 3447 |
TBA | 3/0 | 19 | 10.74 | 18.80 | 3.56 | 20.32 | 6 | 50.88 | 59.26 | 1.52 | 62.31 | 3775 |
672070 | 4/0 | 19 | 12.07 | 20.12 | 3.56 | 21.64 | 6 | 53.75 | 62.13 | 1.52 | 65.18 | 4162 |
TBA | 250 | 37 | 13.21 | 21.49 | 3.56 | 23.01 | 4 | 56.69 | 65.07 | 1.91 | 68.88 | 4738 |
652787 | 350 | 37 | 15.65 | 23.93 | 3.56 | 25.45 | 4 | 61.98 | 70.36 | 1.91 | 74.17 | 5557 |
674257 | 500 | 37 | 18.69 | 26.97 | 3.56 | 28.50 | 3 | 68.55 | 76.94 | 1.91 | 80.75 | 6752 |
TBA | 750 | 61 | 23.06 | 32.13 | 3.56 | 33.65 | 2 | 80.95 | 89.33 | 2.16 | 93.65 | 9166 |
TBA | 1000 | 61 | 26.92 | 35.99 | 3.56 | 37.52 | 2 | 89.31 | 97.69 | 2.16 | 102.01 | 10945 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 4 – Electrical and Engineering Data (Metric)
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity in Vented Cable Tray 90°C‡ | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
2 | 363.22 | 5313 | 0.8727 | 1.10 | 0.0162 | 0.1411 | 0.707+j0.498 | 0.334+j0.043 | 3.1 | 126 | 157 |
1 | 378.46 | 6702 | 0.6923 | 0.87 | 0.0149 | 0.1345 | 0.639+j0.480 | 0.265+j0.041 | 3.9 | 144 | 178 |
1/0 | 391.16 | 8459 | 0.5512 | 0.69 | 0.0137 | 0.1312 | 0.586+j0.460 | 0.211+j0.040 | 5.0 | 162 | 202 |
2/0 | 419.10 | 10662 | 0.4364 | 0.55 | 0.0128 | 0.1247 | 0.543+j0.440 | 0.167+j0.038 | 6.3 | 188 | 229 |
3/0 | 436.88 | 13439 | 0.3445 | 0.43 | 0.0116 | 0.1214 | 0.507+j0.418 | 0.132+j0.037 | 7.9 | 213 | 260 |
4/0 | 457.20 | 16950 | 0.2743 | 0.34 | 0.0107 | 0.1181 | 0.479+j0.394 | 0.105+j0.036 | 9.9 | 240 | 294 |
250 | 482.60 | 20025 | 0.2320 | 0.29 | 0.0101 | 0.1148 | 0.460+j0.372 | 0.089+j0.035 | 11.8 | 264 | 323 |
350 | 518.16 | 28035 | 0.1657 | 0.21 | 0.0088 | 0.1083 | 0.429+j0.337 | 0.064+j0.033 | 16.4 | 317 | 386 |
500 | 566.42 | 40050 | 0.1161 | 0.15 | 0.0076 | 0.1050 | 0.400+j0.298 | 0.045+j0.032 | 23.5 | 389 | 465 |
750 | 655.32 | 60075 | 0.0774 | 0.10 | 0.0070 | 0.1017 | 0.366+j0.246 | 0.030+j0.031 | 35.3 | 472 | 563 |
1000 | 713.74 | 80100 | 0.0581 | 0.08 | 0.0061 | 0.0984 | 0.343+j0.215 | 0.024+j0.030 | 47.0 | 544 | 638 |
* Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E or D17G of the 2021 Canadian Electrical Code Part I
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E or D17G of the 2021 Canadian Electrical Code Part I
Revision: 3.0.00C