SPEC 26306
HVTECK CU 1/C 220NLEPR CB PVC AIA PVC 15kV 133% CSA
Single Conductor, 220 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Conductor Shield:Semi-conducting cross-linked copolymer
- Insulation:220 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
- Neutral Separator:Mylar tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL) and 105°C for use in harsh Canadian environments. For installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable. When used in a 3 phase system, the combination of each bond conductor from each single conductor cable provide a 100% bonded system to ground.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 220 NLEPR AIA 15kV 133% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Dia. Over Inner Jacket | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | inch | inch | mil | inch | No. x AWG | inch | inch | mil | inch | lb/1000ft | |
TBA | 2 | 7 | 0.283 | 0.760 | 220 | 0.840 | 11x16 | 1.102 | 1.422 | 50 | 1.522 | 1068 |
TBA | 1 | 19 | 0.322 | 0.799 | 220 | 0.879 | 17x16 | 1.141 | 1.461 | 50 | 1.561 | 1201 |
TBA | 1/0 | 19 | 0.362 | 0.839 | 220 | 0.919 | 17x16 | 1.181 | 1.501 | 50 | 1.601 | 1304 |
646911 | 2/0 | 19 | 0.406 | 0.884 | 220 | 0.944 | 17x16 | 1.221 | 1.532 | 60 | 1.652 | 1440 |
TBA | 3/0 | 19 | 0.456 | 0.933 | 220 | 1.013 | 21x16 | 1.275 | 1.595 | 50 | 1.695 | 1610 |
TBA | 4/0 | 19 | 0.512 | 0.989 | 220 | 1.069 | 21x16 | 1.331 | 1.651 | 50 | 1.751 | 1795 |
TBA | 250 | 37 | 0.558 | 1.044 | 220 | 1.144 | 27x16 | 1.406 | 1.726 | 50 | 1.826 | 2035 |
TBA | 350 | 37 | 0.661 | 1.147 | 220 | 1.247 | 21x14 | 1.535 | 1.855 | 60 | 1.975 | 2535 |
646932 | 500 | 37 | 0.789 | 1.275 | 220 | 1.375 | 27x14 | 1.663 | 1.983 | 60 | 2.103 | 3189 |
TBA | 750 | 61 | 0.968 | 1.463 | 220 | 1.563 | 33x14 | 1.911 | 2.241 | 60 | 2.361 | 4403 |
587685 | 750 | 61 | 0.968 | 1.464 | 220 | 1.524 | 21x12 | 1.932 | 2.262 | 75 | 2.412 | 4607 |
TBA | 1000 | 61 | 1.117 | 1.612 | 220 | 1.742 | 33x14 | 2.090 | 2.420 | 60 | 2.540 | 5382 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 2 – Electrical and Engineering Data
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity in Vented Cable Tray 90°C‡ | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
2 | 10.7 | 531 | 0.162 | 0.203 | 0.053 | 0.060 | 0.498+j0.198 | 0.205+j0.060 | 4.5 | 215 | 221 |
1 | 10.9 | 670 | 0.129 | 0.161 | 0.049 | 0.058 | 0.384+j0.115 | 0.164+j0.058 | 5.7 | 245 | 247 |
1/0 | 11.2 | 845 | 0.102 | 0.128 | 0.045 | 0.056 | 0.350+j0.113 | 0.131+j0.055 | 7.2 | 278 | 275 |
2/0 | 11.5 | 1065 | 0.081 | 0.101 | 0.042 | 0.054 | 0.323+j0.112 | 0.104+j0.054 | 9.0 | 317 | 306 |
3/0 | 11.9 | 1342 | 0.0642 | 0.080 | 0.039 | 0.052 | 0.268+j0.085 | 0.083+j0.051 | 11.4 | 357 | 335 |
4/0 | 12.3 | 1693 | 0.051 | 0.064 | 0.036 | 0.050 | 0.252+j0.084 | 0.067+j0.049 | 14.3 | 404 | 369 |
250 | 12.8 | 2000 | 0.0431 | 0.054 | 0.034 | 0.049 | 0.206+j0.062 | 0.058+j0.048 | 16.9 | 456 | 412 |
350 | 13.8 | 2800 | 0.0308 | 0.039 | 0.030 | 0.047 | 0.164+j0.050 | 0.044+j0.046 | 23.7 | 537 | 456 |
500 | 14.7 | 4000 | 0.0216 | 0.028 | 0.026 | 0.044 | 0.127+j0.039 | 0.034+j0.043 | 33.9 | 616 | 497 |
750 | 16.5 | 6000 | 0.0144 | 0.019 | 0.022 | 0.042 | 0.101+j0.031 | 0.026+j0.040 | 50.8 | 706 | 551 |
750 | 16.5 | 6000 | 0.0144 | 0.019 | 0.022 | 0.042 | 0.101+j0.031 | 0.026+j0.040 | 50.8 | 706 | 551 |
1000 | 17.8 | 8000 | 0.0108 | 0.015 | 0.020 | 0.041 | 0.097+j0.031 | 0.021+j0.038 | 67.8 | 813 | 596 |
* Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
Table 3 – Weights and Measurements (Metric)
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Dia. Over Inner Jacket | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | mm | mm | mm | mm | No. x AWG | mm | mm | mm | mm | kg/km | |
TBA | 2 | 7 | 7.19 | 19.30 | 5.59 | 21.34 | 11x16 | 27.99 | 36.12 | 1.27 | 38.66 | 1589 |
TBA | 1 | 19 | 8.18 | 20.29 | 5.59 | 22.33 | 17x16 | 28.98 | 37.11 | 1.27 | 39.65 | 1787 |
TBA | 1/0 | 19 | 9.19 | 21.31 | 5.59 | 23.34 | 17x16 | 30.00 | 38.13 | 1.27 | 40.67 | 1941 |
646911 | 2/0 | 19 | 10.31 | 22.45 | 5.59 | 23.98 | 17x16 | 31.01 | 38.91 | 1.52 | 41.96 | 2143 |
TBA | 3/0 | 19 | 11.58 | 23.70 | 5.59 | 25.73 | 21x16 | 32.39 | 40.51 | 1.27 | 43.05 | 2396 |
TBA | 4/0 | 19 | 13.00 | 25.12 | 5.59 | 27.15 | 21x16 | 33.81 | 41.94 | 1.27 | 44.48 | 2671 |
TBA | 250 | 37 | 14.17 | 26.52 | 5.59 | 29.06 | 27x16 | 35.71 | 43.84 | 1.27 | 46.38 | 3028 |
TBA | 350 | 37 | 16.79 | 29.13 | 5.59 | 31.67 | 21x14 | 38.99 | 47.12 | 1.52 | 50.17 | 3772 |
646932 | 500 | 37 | 20.04 | 32.39 | 5.59 | 34.93 | 27x14 | 42.24 | 50.37 | 1.52 | 53.42 | 4746 |
TBA | 750 | 61 | 24.59 | 37.16 | 5.59 | 39.70 | 33x14 | 48.54 | 56.92 | 1.52 | 59.97 | 6552 |
587685 | 750 | 61 | 24.59 | 37.19 | 5.59 | 38.71 | 21x12 | 49.07 | 57.45 | 1.91 | 61.26 | 6856 |
TBA | 1000 | 61 | 28.37 | 40.94 | 5.59 | 44.25 | 33x14 | 53.09 | 61.47 | 1.52 | 64.52 | 8009 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 4 – Electrical and Engineering Data (Metric)
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity in Vented Cable Tray 90°C‡ | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
2 | 271.78 | 2363 | 0.5315 | 0.67 | 0.0162 | 0.1969 | 0.498+j0.198 | 0.205+j0.060 | 4.5 | 215 | 221 |
1 | 276.86 | 2982 | 0.4232 | 0.53 | 0.0149 | 0.1903 | 0.384+j0.115 | 0.164+j0.058 | 5.7 | 245 | 247 |
1/0 | 284.48 | 3760 | 0.3346 | 0.42 | 0.0137 | 0.1837 | 0.350+j0.113 | 0.131+j0.055 | 7.2 | 278 | 275 |
2/0 | 292.10 | 4739 | 0.2657 | 0.33 | 0.0128 | 0.1772 | 0.323+j0.112 | 0.104+j0.054 | 9.0 | 317 | 306 |
3/0 | 302.26 | 5972 | 0.2106 | 0.26 | 0.0119 | 0.1706 | 0.268+j0.085 | 0.083+j0.051 | 11.4 | 357 | 335 |
4/0 | 312.42 | 7534 | 0.1673 | 0.21 | 0.0110 | 0.1640 | 0.252+j0.084 | 0.067+j0.049 | 14.3 | 404 | 369 |
250 | 325.12 | 8900 | 0.1414 | 0.18 | 0.0104 | 0.1608 | 0.206+j0.062 | 0.058+j0.048 | 16.9 | 456 | 412 |
350 | 350.52 | 12460 | 0.1010 | 0.13 | 0.0091 | 0.1542 | 0.164+j0.050 | 0.044+j0.046 | 23.7 | 537 | 456 |
500 | 373.38 | 17800 | 0.0709 | 0.09 | 0.0079 | 0.1444 | 0.127+j0.039 | 0.034+j0.043 | 33.9 | 616 | 497 |
750 | 419.10 | 26700 | 0.0472 | 0.06 | 0.0067 | 0.1378 | 0.101+j0.031 | 0.026+j0.040 | 50.8 | 706 | 551 |
750 | 419.10 | 26700 | 0.0472 | 0.06 | 0.0067 | 0.1378 | 0.101+j0.031 | 0.026+j0.040 | 50.8 | 706 | 551 |
1000 | 452.12 | 35600 | 0.0354 | 0.05 | 0.0061 | 0.1345 | 0.097+j0.031 | 0.021+j0.038 | 67.8 | 813 | 596 |
* Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
Revision: 3.0.00C