SPEC 26311
HVTECK CU 1/C 175TRXLPE TS PVC AIA PVC 15kV 100% CSA
Single Conductor, 175 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Conductor Shield:Semi-conducting cross-linked copolymer
- Insulation:175 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL) and 105°C for use in harsh Canadian environments. For installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 175 TRXLPE AIA 15kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Dia. Over Inner Jacket | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | inch | inch | mil | inch | inch | inch | mil | inch | lb/1000ft | |
TBA | 2 | 7 | 0.283 | 0.670 | 175 | 0.730 | 0.880 | 1.200 | 50 | 1.300 | 828 |
TBA | 1 | 19 | 0.322 | 0.709 | 175 | 0.769 | 0.949 | 1.269 | 50 | 1.369 | 945 |
TBA | 1/0 | 19 | 0.362 | 0.749 | 175 | 0.809 | 0.989 | 1.309 | 50 | 1.409 | 1045 |
TBA | 2/0 | 19 | 0.405 | 0.792 | 175 | 0.852 | 1.032 | 1.352 | 50 | 1.452 | 1165 |
672009 | 3/0 | 19 | 0.456 | 0.843 | 175 | 0.903 | 1.083 | 1.403 | 50 | 1.503 | 1314 |
TBA | 4/0 | 19 | 0.512 | 0.899 | 175 | 0.959 | 1.139 | 1.459 | 50 | 1.559 | 1496 |
TBA | 250 | 37 | 0.558 | 0.954 | 175 | 1.014 | 1.194 | 1.514 | 50 | 1.614 | 1659 |
TBA | 350 | 37 | 0.661 | 1.057 | 175 | 1.117 | 1.297 | 1.617 | 50 | 1.717 | 2052 |
TBA | 500 | 37 | 0.789 | 1.185 | 175 | 1.245 | 1.425 | 1.745 | 60 | 1.865 | 2655 |
TBA | 750 | 61 | 0.968 | 1.373 | 175 | 1.433 | 1.613 | 1.943 | 60 | 2.063 | 3645 |
TBA | 1000 | 61 | 1.117 | 1.522 | 175 | 1.582 | 1.822 | 2.152 | 60 | 2.272 | 4667 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 2 – Electrical and Engineering Data
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity in Vented Cable Tray 90°C‡ | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
2 | 9.1 | 531 | 0.162 | 0.203 | 0.059 | 0.057 | 0.565+j0.452 | 0.204+j0.057 | 4.8 | 215 | 221 |
1 | 9.6 | 670 | 0.129 | 0.161 | 0.054 | 0.055 | 0.523+j0.433 | 0.162+j0.055 | 6.0 | 245 | 247 |
1/0 | 9.9 | 845 | 0.102 | 0.128 | 0.049 | 0.053 | 0.490+j0.415 | 0.129+j0.053 | 7.6 | 278 | 275 |
2/0 | 10.2 | 1065 | 0.081 | 0.101 | 0.046 | 0.051 | 0.463+j0.396 | 0.102+j0.051 | 9.6 | 317 | 306 |
3/0 | 10.5 | 1342 | 0.0642 | 0.080 | 0.042 | 0.049 | 0.441+j0.375 | 0.081+j0.049 | 12.1 | 357 | 335 |
4/0 | 10.9 | 1693 | 0.051 | 0.064 | 0.038 | 0.047 | 0.422+j0.354 | 0.065+j0.047 | 15.2 | 404 | 369 |
250 | 11.3 | 2000 | 0.0431 | 0.054 | 0.036 | 0.046 | 0.409+j0.335 | 0.055+j0.046 | 18.0 | 456 | 412 |
350 | 12.0 | 2800 | 0.0308 | 0.039 | 0.032 | 0.044 | 0.387+j0.302 | 0.040+j0.044 | 25.2 | 537 | 456 |
500 | 13.1 | 4000 | 0.0216 | 0.028 | 0.028 | 0.041 | 0.365+j0.267 | 0.029+j0.041 | 36.0 | 616 | 497 |
750 | 14.4 | 6000 | 0.0144 | 0.019 | 0.024 | 0.039 | 0.339+j0.225 | 0.020+j0.039 | 53.9 | 706 | 551 |
1000 | 15.9 | 8000 | 0.0108 | 0.015 | 0.021 | 0.038 | 0.320+j0.199 | 0.016+j0.038 | 71.9 | 813 | 596 |
* Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
Table 3 – Weights and Measurements (Metric)
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Dia. Over Inner Jacket | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | mm | mm | mm | mm | mm | mm | mm | mm | kg/km | |
TBA | 2 | 7 | 7.19 | 17.02 | 4.44 | 18.54 | 22.35 | 30.48 | 1.27 | 33.02 | 1232 |
TBA | 1 | 19 | 8.18 | 18.01 | 4.44 | 19.53 | 24.10 | 32.23 | 1.27 | 34.77 | 1406 |
TBA | 1/0 | 19 | 9.19 | 19.02 | 4.44 | 20.55 | 25.12 | 33.25 | 1.27 | 35.79 | 1555 |
TBA | 2/0 | 19 | 10.29 | 20.12 | 4.44 | 21.64 | 26.21 | 34.34 | 1.27 | 36.88 | 1734 |
672009 | 3/0 | 19 | 11.58 | 21.41 | 4.44 | 22.94 | 27.51 | 35.64 | 1.27 | 38.18 | 1955 |
TBA | 4/0 | 19 | 13.00 | 22.83 | 4.44 | 24.36 | 28.93 | 37.06 | 1.27 | 39.60 | 2226 |
TBA | 250 | 37 | 14.17 | 24.23 | 4.44 | 25.76 | 30.33 | 38.46 | 1.27 | 41.00 | 2469 |
TBA | 350 | 37 | 16.79 | 26.85 | 4.44 | 28.37 | 32.94 | 41.07 | 1.27 | 43.61 | 3054 |
TBA | 500 | 37 | 20.04 | 30.10 | 4.44 | 31.62 | 36.20 | 44.32 | 1.52 | 47.37 | 3951 |
TBA | 750 | 61 | 24.59 | 34.87 | 4.44 | 36.40 | 40.97 | 49.35 | 1.52 | 52.40 | 5424 |
TBA | 1000 | 61 | 28.37 | 38.66 | 4.44 | 40.18 | 46.28 | 54.66 | 1.52 | 57.71 | 6945 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 4 – Electrical and Engineering Data (Metric)
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity in Vented Cable Tray 90°C‡ | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
2 | 231.14 | 2363 | 0.5315 | 0.67 | 0.0180 | 0.1870 | 0.565+j0.452 | 0.204+j0.057 | 4.8 | 215 | 221 |
1 | 243.84 | 2982 | 0.4232 | 0.53 | 0.0165 | 0.1804 | 0.523+j0.433 | 0.162+j0.055 | 6.0 | 245 | 247 |
1/0 | 251.46 | 3760 | 0.3346 | 0.42 | 0.0149 | 0.1739 | 0.490+j0.415 | 0.129+j0.053 | 7.6 | 278 | 275 |
2/0 | 259.08 | 4739 | 0.2657 | 0.33 | 0.0140 | 0.1673 | 0.463+j0.396 | 0.102+j0.051 | 9.6 | 317 | 306 |
3/0 | 266.70 | 5972 | 0.2106 | 0.26 | 0.0128 | 0.1608 | 0.441+j0.375 | 0.081+j0.049 | 12.1 | 357 | 335 |
4/0 | 276.86 | 7534 | 0.1673 | 0.21 | 0.0116 | 0.1542 | 0.422+j0.354 | 0.065+j0.047 | 15.2 | 404 | 369 |
250 | 287.02 | 8900 | 0.1414 | 0.18 | 0.0110 | 0.1509 | 0.409+j0.335 | 0.055+j0.046 | 18.0 | 456 | 412 |
350 | 304.80 | 12460 | 0.1010 | 0.13 | 0.0098 | 0.1444 | 0.387+j0.302 | 0.040+j0.044 | 25.2 | 537 | 456 |
500 | 332.74 | 17800 | 0.0709 | 0.09 | 0.0085 | 0.1345 | 0.365+j0.267 | 0.029+j0.041 | 36.0 | 616 | 497 |
750 | 365.76 | 26700 | 0.0472 | 0.06 | 0.0073 | 0.1280 | 0.339+j0.225 | 0.020+j0.039 | 53.9 | 706 | 551 |
1000 | 403.86 | 35600 | 0.0354 | 0.05 | 0.0064 | 0.1247 | 0.320+j0.199 | 0.016+j0.038 | 71.9 | 813 | 596 |
* Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
Revision: 3.0.00C