SPEC 26312

HVTECK CU 1/C 220TRXLPE TS PVC AIA PVC 15kV 133% CSA

Single Conductor, 220 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:220 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Inner Jacket:PVC inner jacket
  7. Armour:Aluminum Interlocked Armour (AIA)
  8. Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL) and 105°C for use in harsh Canadian environments. For installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 220 TRXLPE AIA 15kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldDia. Over Inner JacketDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchinchinchmilinchlb/1000ft
    TBA270.2830.7602200.8201.0001.320501.420952
    TBA1190.3220.7992200.8591.0391.359501.4591037
    TBA1/0190.3620.8392200.8991.0791.399501.4991140
    6709652/0190.4060.8842200.9441.1241.454501.5541317
    TBA3/0190.4560.9332200.9931.1731.493501.5931414
    672441^4/0190.5120.9892201.0491.2291.549501.6491599
    TBA250370.5581.0442201.1041.2841.604501.7041765
    671319350370.6611.1472201.2071.3871.717601.8372198
    672047500370.7891.2752201.3351.5151.835601.9552776
    641194750610.9681.4632201.5231.7032.033602.1533780
    6720461000611.1171.6122201.6721.9122.242602.3624815
    672445^1000611.1171.6122201.6721.9122.242602.3624815
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    ^Black outer jacket
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity in Vented Cable Tray 90°C‡Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    29.95310.1620.2030.0670.0590.565+j0.4160.204+j0.0594.8215221
    110.26700.1290.1610.0620.0560.523+j0.3990.162+j0.0566.0245247
    1/010.58450.1020.1280.0570.0540.489+j0.3820.129+j0.0547.6278275
    2/010.810650.0810.1010.0530.0520.460+j0.3650.102+j0.0529.6317306
    3/011.213420.06420.0800.0490.0500.436+j0.3460.081+j0.05012.1357335
    4/011.516930.0510.0640.0450.0490.417+j0.3270.065+j0.04815.2404369
    25011.920000.04310.0540.0430.0470.403+j0.3100.055+j0.04718.0456412
    35012.828000.03080.0390.0380.0450.380+j0.2800.040+j0.04525.2537456
    50013.740000.02160.0280.0330.0430.357+j0.2480.029+j0.04236.0616497
    75015.160000.01440.0190.0280.0400.330+j0.2110.020+j0.04053.9706551
    100016.580000.01080.0150.0250.0390.312+j0.1860.016+j0.03971.9813596
    100016.580000.01080.0150.0250.0390.312+j0.1860.016+j0.03971.9813596
    * Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldDia. Over Inner JacketDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmmmmmmmmmkg/km
    TBA277.1919.305.5920.8325.4033.531.2736.071417
    TBA1198.1820.295.5921.8226.3934.521.2737.061543
    TBA1/0199.1921.315.5922.8327.4135.531.2738.071697
    6709652/01910.3122.455.5923.9828.5536.931.2739.471960
    TBA3/01911.5823.705.5925.2229.7937.921.2740.462104
    672441^4/01913.0025.125.5926.6431.2239.341.2741.882380
    TBA2503714.1726.525.5928.0432.6140.741.2743.282627
    6713193503716.7929.135.5930.6635.2343.611.5246.663271
    6720475003720.0432.395.5933.9138.4846.611.5249.664131
    6411947506124.5937.165.5938.6843.2651.641.5254.695625
    67204610006128.3740.945.5942.4748.5656.951.5259.997166
    672445^10006128.3740.945.5942.4748.5656.951.5259.997166
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    ^Black outer jacket
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity in Vented Cable Tray 90°C‡Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftkAmpAmpAmp
    2251.4623630.53150.670.02040.19360.565+j0.4160.204+j0.0594.8215221
    1259.0829820.42320.530.01890.18370.523+j0.3990.162+j0.0566.0245247
    1/0266.7037600.33460.420.01740.17720.489+j0.3820.129+j0.0547.6278275
    2/0274.3247390.26570.330.01620.17060.460+j0.3650.102+j0.0529.6317306
    3/0284.4859720.21060.260.01490.16400.436+j0.3460.081+j0.05012.1357335
    4/0292.1075340.16730.210.01370.16080.417+j0.3270.065+j0.04815.2404369
    250302.2689000.14140.180.01310.15420.403+j0.3100.055+j0.04718.0456412
    350325.12124600.10100.130.01160.14760.380+j0.2800.040+j0.04525.2537456
    500347.98178000.07090.090.01010.14110.357+j0.2480.029+j0.04236.0616497
    750383.54267000.04720.060.00850.13120.330+j0.2110.020+j0.04053.9706551
    1000419.10356000.03540.050.00760.12800.312+j0.1860.016+j0.03971.9813596
    1000419.10356000.03540.050.00760.12800.312+j0.1860.016+j0.03971.9813596
    * Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I

    Revision: 3.0.00C