SPEC 26316

HVTECK CU 1/C 220TRXLPE CB PVC AIA PVC 15kV 133% CSA

Single Conductor, 220 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:220 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
  6. Neutral Separator:Mylar tape
  7. Inner Jacket:PVC inner jacket
  8. Armour:Aluminum Interlocked Armour (AIA)
  9. Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL) and 105°C for use in harsh Canadian environments. For installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable. When used in a 3 phase system, the combination of each bond conductor from each single conductor cable provide a 100% bonded system to ground.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 220 TRXLPE AIA 15kV 133% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralDia. Over Inner JacketDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchNo. x AWGinchinchmilinchlb/1000ft
    TBA270.2830.7602200.84011x161.1021.422501.5221032
    TBA1190.3220.7992200.87917x161.1411.461501.5611162
    TBA1/0190.3620.8392200.91917x161.1811.501501.6011262
    TBA2/0190.4050.8822200.96217x161.2241.544501.6441382
    TBA3/0190.4560.9332201.01321x161.2751.595501.6951562
    TBA4/0190.5120.9892201.06921x161.3311.651501.7511743
    TBA250370.5581.0442201.14427x161.4061.726501.8261979
    TBA350370.6611.1472201.24721x141.5351.855601.9752472
    672982500370.7891.2752201.37527x141.6631.983602.1033118
    668996750610.9681.4642201.52430x141.8792.209602.3294250
    TBA750610.9681.4632201.56333x141.9112.241602.3614319
    6729861000611.1171.6122201.74233x142.0902.420602.5405287
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity in Vented Cable Tray 90°C‡Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    210.75310.1620.2030.0670.0600.498+j0.1980.205+j0.0604.8215221
    110.96700.1290.1610.0620.0580.384+j0.1150.164+j0.0586.0245247
    1/011.28450.1020.1280.0570.0560.350+j0.1130.131+j0.0557.6278275
    2/011.510650.0810.1010.0530.0540.323+j0.1120.104+j0.0549.6317306
    3/011.913420.06420.0800.0490.0520.268+j0.0850.083+j0.05112.1357335
    4/012.316930.0510.0640.0450.0500.252+j0.0840.067+j0.04915.2404369
    25012.820000.04310.0540.0430.0490.206+j0.0620.058+j0.04818.0456412
    35013.828000.03080.0390.0380.0470.164+j0.0500.044+j0.04625.2537456
    50014.740000.02160.0280.0330.0440.127+j0.0390.034+j0.04336.0616497
    75016.560000.01440.0190.0280.0420.101+j0.0310.026+j0.04053.9706551
    75016.560000.01440.0190.0280.0420.101+j0.0310.026+j0.04053.9706551
    100017.880000.01080.0150.0250.0410.097+j0.0310.021+j0.03871.9813596
    * Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralDia. Over Inner JacketDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmkg/km
    TBA277.1919.305.5921.3411x1627.9936.121.2738.661536
    TBA1198.1820.295.5922.3317x1628.9837.111.2739.651729
    TBA1/0199.1921.315.5923.3417x1630.0038.131.2740.671878
    TBA2/01910.2922.405.5924.4317x1631.0939.221.2741.762057
    TBA3/01911.5823.705.5925.7321x1632.3940.511.2743.052325
    TBA4/01913.0025.125.5927.1521x1633.8141.941.2744.482594
    TBA2503714.1726.525.5929.0627x1635.7143.841.2746.382945
    TBA3503716.7929.135.5931.6721x1438.9947.121.5250.173679
    6729825003720.0432.395.5934.9327x1442.2450.371.5253.424640
    6689967506124.5937.195.5938.7130x1447.7356.111.5259.166325
    TBA7506124.5937.165.5939.7033x1448.5456.921.5259.976427
    67298610006128.3740.945.5944.2533x1453.0961.471.5264.527868
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity in Vented Cable Tray 90°C‡Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftkAmpAmpAmp
    2271.7823630.53150.670.02040.19690.498+j0.1980.205+j0.0604.8215221
    1276.8629820.42320.530.01890.19030.384+j0.1150.164+j0.0586.0245247
    1/0284.4837600.33460.420.01740.18370.350+j0.1130.131+j0.0557.6278275
    2/0292.1047390.26570.330.01620.17720.323+j0.1120.104+j0.0549.6317306
    3/0302.2659720.21060.260.01490.17060.268+j0.0850.083+j0.05112.1357335
    4/0312.4275340.16730.210.01370.16400.252+j0.0840.067+j0.04915.2404369
    250325.1289000.14140.180.01310.16080.206+j0.0620.058+j0.04818.0456412
    350350.52124600.10100.130.01160.15420.164+j0.0500.044+j0.04625.2537456
    500373.38178000.07090.090.01010.14440.127+j0.0390.034+j0.04336.0616497
    750419.10267000.04720.060.00850.13780.101+j0.0310.026+j0.04053.9706551
    750419.10267000.04720.060.00850.13780.101+j0.0310.026+j0.04053.9706551
    1000452.12356000.03540.050.00760.13450.097+j0.0310.021+j0.03871.9813596
    * Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I

    Revision: 3.0.00C