SPEC 26341
HVTECK CU 3/C 175NLEPR TS PVC AIA PVC 15kV 100% CSA
3 Conductor, 175 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Conductor Shield:Semi-conducting cross-linked copolymer
- Insulation:175 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Filler:Interstices filled with non-hydroscoping/non-wicking fillers
- Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
- Binder:Polypropylene tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL) and 105°C for use in harsh Canadian environments. For installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CU 175 NLEPR AIA 15kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground Size | Dia. Over Inner Jacket | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | inch | inch | mil | inch | AWG | inch | inch | mil | inch | lb/1000ft | |
TBA | 2 | 7 | 0.283 | 0.670 | 175 | 0.730 | 6 | 1.852 | 2.182 | 60 | 2.302 | 2633 |
TBA | 1 | 19 | 0.322 | 0.709 | 175 | 0.769 | 6 | 1.936 | 2.266 | 60 | 2.386 | 2902 |
TBA | 1/0 | 19 | 0.362 | 0.749 | 175 | 0.809 | 6 | 2.023 | 2.353 | 60 | 2.473 | 3224 |
583752 | 2/0 | 19 | 0.405 | 0.792 | 175 | 0.852 | 6 | 2.116 | 2.446 | 60 | 2.566 | 3609 |
TBA | 3/0 | 19 | 0.456 | 0.843 | 175 | 0.903 | 4 | 2.226 | 2.556 | 75 | 2.706 | 4211 |
TBA | 4/0 | 19 | 0.512 | 0.899 | 175 | 0.959 | 4 | 2.347 | 2.677 | 75 | 2.827 | 4794 |
TBA | 250 | 37 | 0.558 | 0.954 | 175 | 1.014 | 4 | 2.465 | 2.795 | 75 | 2.945 | 5322 |
TBA | 350 | 37 | 0.661 | 1.057 | 175 | 1.117 | 3 | 2.688 | 3.018 | 75 | 3.168 | 6618 |
TBA | 500 | 37 | 0.789 | 1.185 | 175 | 1.245 | 3 | 3.014 | 3.344 | 85 | 3.514 | 8654 |
TBA | 750 | 61 | 0.968 | 1.373 | 175 | 1.433 | 2 | 3.420 | 3.750 | 85 | 3.920 | 11683 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 2 – Electrical and Engineering Data
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity in Vented Cable Tray 90°C‡ | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
2 | 16.1 | 1593 | 0.162 | 0.203 | 0.047 | 0.044 | 0.579+j0.457 | 0.203+j0.044 | 4.5 | 172 | 201 |
1 | 16.7 | 2009 | 0.129 | 0.161 | 0.043 | 0.042 | 0.537+j0.437 | 0.161+j0.042 | 5.7 | 197 | 228 |
1/0 | 17.3 | 2534 | 0.102 | 0.128 | 0.039 | 0.041 | 0.503+j0.418 | 0.128+j0.041 | 7.2 | 225 | 257 |
2/0 | 18.0 | 3194 | 0.081 | 0.101 | 0.036 | 0.039 | 0.475+j0.398 | 0.101+j0.039 | 9.0 | 260 | 292 |
3/0 | 18.9 | 4027 | 0.0642 | 0.081 | 0.033 | 0.038 | 0.452+j0.377 | 0.081+j0.038 | 11.4 | 297 | 330 |
4/0 | 19.8 | 5078 | 0.051 | 0.064 | 0.030 | 0.037 | 0.432+j0.355 | 0.064+j0.037 | 14.3 | 342 | 372 |
250 | 20.6 | 6000 | 0.0431 | 0.054 | 0.029 | 0.036 | 0.418+j0.335 | 0.054+j0.036 | 16.9 | 376 | 410 |
350 | 22.2 | 8400 | 0.0308 | 0.039 | 0.025 | 0.034 | 0.395+j0.302 | 0.039+j0.034 | 23.7 | 460 | 487 |
500 | 24.6 | 12000 | 0.0216 | 0.028 | 0.022 | 0.033 | 0.371+j0.266 | 0.028+j0.032 | 33.9 | 556 | 573 |
750 | 27.4 | 18000 | 0.0144 | 0.020 | 0.019 | 0.031 | 0.345+j0.224 | 0.021+j0.031 | 50.8 | 678 | 668 |
* Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
Table 3 – Weights and Measurements (Metric)
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground Size | Dia. Over Inner Jacket | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | mm | mm | mm | mm | AWG | mm | mm | mm | mm | kg/km | |
TBA | 2 | 7 | 7.19 | 17.02 | 4.44 | 18.54 | 6 | 47.04 | 55.42 | 1.52 | 58.47 | 3918 |
TBA | 1 | 19 | 8.18 | 18.01 | 4.44 | 19.53 | 6 | 49.17 | 57.56 | 1.52 | 60.60 | 4319 |
TBA | 1/0 | 19 | 9.19 | 19.02 | 4.44 | 20.55 | 6 | 51.38 | 59.77 | 1.52 | 62.81 | 4798 |
583752 | 2/0 | 19 | 10.29 | 20.12 | 4.44 | 21.64 | 6 | 53.75 | 62.13 | 1.52 | 65.18 | 5371 |
TBA | 3/0 | 19 | 11.58 | 21.41 | 4.44 | 22.94 | 4 | 56.54 | 64.92 | 1.91 | 68.73 | 6267 |
TBA | 4/0 | 19 | 13.00 | 22.83 | 4.44 | 24.36 | 4 | 59.61 | 68.00 | 1.91 | 71.81 | 7134 |
TBA | 250 | 37 | 14.17 | 24.23 | 4.44 | 25.76 | 4 | 62.61 | 70.99 | 1.91 | 74.80 | 7920 |
TBA | 350 | 37 | 16.79 | 26.85 | 4.44 | 28.37 | 3 | 68.28 | 76.66 | 1.91 | 80.47 | 9849 |
TBA | 500 | 37 | 20.04 | 30.10 | 4.44 | 31.62 | 3 | 76.56 | 84.94 | 2.16 | 89.26 | 12879 |
TBA | 750 | 61 | 24.59 | 34.87 | 4.44 | 36.40 | 2 | 86.87 | 95.25 | 2.16 | 99.57 | 17386 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 4 – Electrical and Engineering Data (Metric)
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity in Vented Cable Tray 90°C‡ | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
2 | 408.94 | 7089 | 0.5315 | 0.67 | 0.0143 | 0.1444 | 0.579+j0.457 | 0.203+j0.044 | 4.5 | 172 | 201 |
1 | 424.18 | 8940 | 0.4232 | 0.53 | 0.0131 | 0.1378 | 0.537+j0.437 | 0.161+j0.042 | 5.7 | 197 | 228 |
1/0 | 439.42 | 11276 | 0.3346 | 0.42 | 0.0119 | 0.1345 | 0.503+j0.418 | 0.128+j0.041 | 7.2 | 225 | 257 |
2/0 | 457.20 | 14213 | 0.2657 | 0.33 | 0.0110 | 0.1280 | 0.475+j0.398 | 0.101+j0.039 | 9.0 | 260 | 292 |
3/0 | 480.06 | 17920 | 0.2106 | 0.27 | 0.0101 | 0.1247 | 0.452+j0.377 | 0.081+j0.038 | 11.4 | 297 | 330 |
4/0 | 502.92 | 22597 | 0.1673 | 0.21 | 0.0091 | 0.1214 | 0.432+j0.355 | 0.064+j0.037 | 14.3 | 342 | 372 |
250 | 523.24 | 26700 | 0.1414 | 0.18 | 0.0088 | 0.1181 | 0.418+j0.335 | 0.054+j0.036 | 16.9 | 376 | 410 |
350 | 563.88 | 37380 | 0.1010 | 0.13 | 0.0076 | 0.1115 | 0.395+j0.302 | 0.039+j0.034 | 23.7 | 460 | 487 |
500 | 624.84 | 53400 | 0.0709 | 0.09 | 0.0067 | 0.1083 | 0.371+j0.266 | 0.028+j0.032 | 33.9 | 556 | 573 |
750 | 695.96 | 80100 | 0.0472 | 0.07 | 0.0058 | 0.1017 | 0.345+j0.224 | 0.021+j0.031 | 50.8 | 678 | 668 |
* Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
Revision: 3.0.00C