SPEC 26371
HVTECK AL 3/C 175TRXLPE TS PVC AIA PVC 15kV 100% CSA
3 Conductor, 175 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
- Insulation:175 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Filler:Interstices filled with non-hydroscoping/non-wicking fillers
- Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
- Binder:Polypropylene tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL) and 105°C for use in harsh Canadian environments. For installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CPT AL 175 TRXLPE AIA 15kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground Size | Dia. Over Inner Jacket | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | inch | inch | mil | inch | AWG | inch | inch | mil | inch | lb/1000ft | |
TBA | 2 | 7 | 0.268 | 0.655 | 175 | 0.715 | 8 | 1.760 | 2.090 | 60 | 2.210 | 1917 |
TBA | 1 | 19 | 0.299 | 0.686 | 175 | 0.746 | 6 | 1.887 | 2.217 | 60 | 2.337 | 2201 |
TBA | 1/0 | 19 | 0.336 | 0.723 | 175 | 0.783 | 6 | 1.966 | 2.296 | 60 | 2.416 | 2364 |
TBA | 2/0 | 19 | 0.376 | 0.763 | 175 | 0.823 | 6 | 2.053 | 2.383 | 60 | 2.503 | 2551 |
TBA | 3/0 | 19 | 0.423 | 0.810 | 175 | 0.870 | 6 | 2.154 | 2.484 | 75 | 2.634 | 2854 |
TBA | 4/0 | 19 | 0.475 | 0.862 | 175 | 0.922 | 6 | 2.267 | 2.597 | 75 | 2.747 | 3126 |
TBA | 250 | 37 | 0.520 | 0.916 | 175 | 0.976 | 4 | 2.383 | 2.713 | 75 | 2.863 | 3449 |
TBA | 350 | 37 | 0.616 | 1.012 | 175 | 1.072 | 4 | 2.591 | 2.921 | 75 | 3.071 | 4016 |
TBA | 500 | 37 | 0.736 | 1.132 | 175 | 1.192 | 3 | 2.850 | 3.180 | 75 | 3.330 | 4839 |
TBA | 750 | 61 | 0.908 | 1.335 | 175 | 1.395 | 2 | 3.338 | 3.668 | 85 | 3.838 | 6505 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 2 – Electrical and Engineering Data
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity in Vented Cable Tray 90°C‡ | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
2 | 15.5 | 1194 | 0.266 | 0.334 | 0.061 | 0.045 | 0.709+j0.465 | 0.334+j0.045 | 3.1 | 135 | 157 |
1 | 16.4 | 1506 | 0.211 | 0.265 | 0.057 | 0.043 | 0.641+j0.448 | 0.265+j0.043 | 3.9 | 154 | 178 |
1/0 | 16.9 | 1901 | 0.168 | 0.211 | 0.052 | 0.042 | 0.587+j0.430 | 0.211+j0.042 | 5.0 | 176 | 202 |
2/0 | 17.5 | 2396 | 0.133 | 0.167 | 0.048 | 0.040 | 0.542+j0.411 | 0.167+j0.040 | 6.3 | 204 | 229 |
3/0 | 18.4 | 3020 | 0.105 | 0.132 | 0.044 | 0.039 | 0.505+j0.390 | 0.132+j0.039 | 7.9 | 234 | 260 |
4/0 | 19.2 | 3809 | 0.0836 | 0.105 | 0.041 | 0.037 | 0.475+j0.369 | 0.105+j0.037 | 9.9 | 268 | 294 |
250 | 20.0 | 4500 | 0.0707 | 0.089 | 0.039 | 0.037 | 0.456+j0.349 | 0.089+j0.037 | 11.8 | 296 | 323 |
350 | 21.5 | 6300 | 0.0505 | 0.064 | 0.034 | 0.035 | 0.424+j0.316 | 0.064+j0.035 | 16.4 | 363 | 386 |
500 | 23.3 | 9000 | 0.0354 | 0.045 | 0.029 | 0.033 | 0.394+j0.280 | 0.045+j0.033 | 23.5 | 447 | 465 |
750 | 26.9 | 13500 | 0.0236 | 0.030 | 0.026 | 0.032 | 0.358+j0.233 | 0.031+j0.032 | 35.3 | 566 | 563 |
* Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
Table 3 – Weights and Measurements (Metric)
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground Size | Dia. Over Inner Jacket | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | mm | mm | mm | mm | AWG | mm | mm | mm | mm | kg/km | |
TBA | 2 | 7 | 6.81 | 16.64 | 4.44 | 18.16 | 8 | 44.70 | 53.09 | 1.52 | 56.13 | 2853 |
TBA | 1 | 19 | 7.59 | 17.42 | 4.44 | 18.95 | 6 | 47.93 | 56.31 | 1.52 | 59.36 | 3275 |
TBA | 1/0 | 19 | 8.53 | 18.36 | 4.44 | 19.89 | 6 | 49.94 | 58.32 | 1.52 | 61.37 | 3518 |
TBA | 2/0 | 19 | 9.55 | 19.38 | 4.44 | 20.90 | 6 | 52.15 | 60.53 | 1.52 | 63.58 | 3796 |
TBA | 3/0 | 19 | 10.74 | 20.57 | 4.44 | 22.10 | 6 | 54.71 | 63.09 | 1.91 | 66.90 | 4247 |
TBA | 4/0 | 19 | 12.07 | 21.89 | 4.44 | 23.42 | 6 | 57.58 | 65.96 | 1.91 | 69.77 | 4652 |
TBA | 250 | 37 | 13.21 | 23.27 | 4.44 | 24.79 | 4 | 60.53 | 68.91 | 1.91 | 72.72 | 5133 |
TBA | 350 | 37 | 15.65 | 25.70 | 4.44 | 27.23 | 4 | 65.81 | 74.19 | 1.91 | 78.00 | 5976 |
TBA | 500 | 37 | 18.69 | 28.75 | 4.44 | 30.28 | 3 | 72.39 | 80.77 | 1.91 | 84.58 | 7201 |
TBA | 750 | 61 | 23.06 | 33.91 | 4.44 | 35.43 | 2 | 84.79 | 93.17 | 2.16 | 97.49 | 9681 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 4 – Electrical and Engineering Data (Metric)
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity in Vented Cable Tray 90°C‡ | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
2 | 393.70 | 5313 | 0.8727 | 1.10 | 0.0186 | 0.1476 | 0.709+j0.465 | 0.334+j0.045 | 3.1 | 135 | 157 |
1 | 416.56 | 6702 | 0.6923 | 0.87 | 0.0174 | 0.1411 | 0.641+j0.448 | 0.265+j0.043 | 3.9 | 154 | 178 |
1/0 | 429.26 | 8459 | 0.5512 | 0.69 | 0.0158 | 0.1378 | 0.587+j0.430 | 0.211+j0.042 | 5.0 | 176 | 202 |
2/0 | 444.50 | 10662 | 0.4364 | 0.55 | 0.0146 | 0.1312 | 0.542+j0.411 | 0.167+j0.040 | 6.3 | 204 | 229 |
3/0 | 467.36 | 13439 | 0.3445 | 0.43 | 0.0134 | 0.1280 | 0.505+j0.390 | 0.132+j0.039 | 7.9 | 234 | 260 |
4/0 | 487.68 | 16950 | 0.2743 | 0.34 | 0.0125 | 0.1214 | 0.475+j0.369 | 0.105+j0.037 | 9.9 | 268 | 294 |
250 | 508.00 | 20025 | 0.2320 | 0.29 | 0.0119 | 0.1214 | 0.456+j0.349 | 0.089+j0.037 | 11.8 | 296 | 323 |
350 | 546.10 | 28035 | 0.1657 | 0.21 | 0.0104 | 0.1148 | 0.424+j0.316 | 0.064+j0.035 | 16.4 | 363 | 386 |
500 | 591.82 | 40050 | 0.1161 | 0.15 | 0.0088 | 0.1083 | 0.394+j0.280 | 0.045+j0.033 | 23.5 | 447 | 465 |
750 | 683.26 | 60075 | 0.0774 | 0.10 | 0.0079 | 0.1050 | 0.358+j0.233 | 0.031+j0.032 | 35.3 | 566 | 563 |
* Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
Revision: 3.0.00C