SPEC 26405

HVTECK CU 1/C 260NLEPR CB PVC AIA PVC 25kV 100% CSA

Single Conductor, 260 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:260 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
  6. Neutral Separator:Mylar tape
  7. Inner Jacket:PVC inner jacket
  8. Armour:Aluminum Interlocked Armour (AIA)
  9. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 25kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL) and 105°C for use in harsh Canadian environments. For installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable. When used in a 3 phase system, the combination of each bond conductor from each single conductor cable provide a 100% bonded system to ground.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 260 NLEPR AIA 25kV 100% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralDia. Over Inner JacketDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchNo. x AWGinchinchmilinchlb/1000ft
    TBA1190.3220.8792600.95917x161.2211.541501.6411292
    TBA1/0190.3620.9192600.99917x161.2611.581501.6811398
    TBA2/0190.4050.9622601.04217x161.3041.624501.7241523
    TBA3/0190.4561.0132601.09321x161.3551.675501.7751710
    TBA4/0190.5121.0692601.16921x161.4311.751501.8511926
    TBA250370.5581.1242601.22427x161.4861.806601.9262179
    TBA350370.6611.2272601.32721x141.6151.935602.0552651
    TBA500370.7891.3552601.45527x141.7432.073602.1933379
    TBA750610.9681.5432601.64333x141.9912.321602.4414546
    TBA1000611.1171.6922601.82233x142.1702.500602.6205536
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity in Vented Cable Tray 90°C‡Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    111.56700.1290.1610.0540.0590.383+j0.1170.164+j0.0595.7245244
    1/011.88450.1020.1280.0500.0570.350+j0.1150.131+j0.0577.2278272
    2/012.110650.0810.1010.0470.0550.323+j0.1140.104+j0.0559.0316303
    3/012.413420.06420.0800.0430.0530.268+j0.0870.083+j0.05211.4356333
    4/013.016930.0510.0640.0400.0510.252+j0.0860.067+j0.05114.3403367
    25013.520000.04310.0540.0380.0500.206+j0.0640.058+j0.04916.9455411
    35014.428000.03080.0390.0330.0480.164+j0.0520.044+j0.04723.7537459
    50015.440000.02160.0280.0290.0450.127+j0.0400.034+j0.04433.9616499
    75017.160000.01440.0190.0250.0430.101+j0.0330.025+j0.04150.8716557
    100018.380000.01080.0150.0220.0410.097+j0.0320.021+j0.03967.8825608
    * Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralDia. Over Inner JacketDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmkg/km
    TBA1198.1822.336.6024.3617x1631.0139.141.2741.681923
    TBA1/0199.1923.346.6025.3717x1632.0340.161.2742.702080
    TBA2/01910.2924.436.6026.4717x1633.1241.251.2743.792266
    TBA3/01911.5825.736.6027.7621x1634.4242.551.2745.082545
    TBA4/01913.0027.156.6029.6921x1636.3544.481.2747.022866
    TBA2503714.1728.556.6031.0927x1637.7445.871.5248.923243
    TBA3503716.7931.176.6033.7121x1441.0249.151.5252.203945
    TBA5003720.0434.426.6036.9627x1444.2752.651.5255.705029
    TBA7506124.5939.196.6041.7333x1450.5758.951.5262.006765
    TBA10006128.3742.986.6046.2833x1455.1263.501.5266.558238
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity in Vented Cable Tray 90°C‡Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftkAmpAmpAmp
    1292.1029820.42320.530.01650.19360.383+j0.1170.164+j0.0595.7245244
    1/0299.7237600.33460.420.01520.18700.350+j0.1150.131+j0.0577.2278272
    2/0307.3447390.26570.330.01430.18040.323+j0.1140.104+j0.0559.0316303
    3/0314.9659720.21060.260.01310.17390.268+j0.0870.083+j0.05211.4356333
    4/0330.2075340.16730.210.01220.16730.252+j0.0860.067+j0.05114.3403367
    250342.9089000.14140.180.01160.16400.206+j0.0640.058+j0.04916.9455411
    350365.76124600.10100.130.01010.15750.164+j0.0520.044+j0.04723.7537459
    500391.16178000.07090.090.00880.14760.127+j0.0400.034+j0.04433.9616499
    750434.34267000.04720.060.00760.14110.101+j0.0330.025+j0.04150.8716557
    1000464.82356000.03540.050.00670.13450.097+j0.0320.021+j0.03967.8825608
    * Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I

    Revision: 3.0.00C