SPEC 26425
HVTECK AL 1/C 260NLEPR CB PVC AIA PVC 25kV 100% CSA
Single Conductor, 260 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
- Insulation:260 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
- Neutral Separator:Mylar tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 25kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL) and 105°C for use in harsh Canadian environments. For installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable. When used in a 3 phase system, the combination of each bond conductor from each single conductor cable provide a 100% bonded system to ground.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 260 NLEPR AIA 25kV 100% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Dia. Over Inner Jacket | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | inch | inch | mil | inch | No. x AWG | inch | inch | mil | inch | lb/1000ft | |
TBA | 1 | 19 | 0.299 | 0.856 | 260 | 0.936 | 11x16 | 1.198 | 1.518 | 50 | 1.618 | 1042 |
TBA | 1/0 | 19 | 0.336 | 0.893 | 260 | 0.973 | 11x16 | 1.235 | 1.555 | 50 | 1.655 | 1097 |
TBA | 2/0 | 19 | 0.376 | 0.933 | 260 | 1.013 | 17x16 | 1.275 | 1.595 | 50 | 1.695 | 1206 |
TBA | 3/0 | 19 | 0.423 | 0.980 | 260 | 1.060 | 17x16 | 1.322 | 1.642 | 50 | 1.742 | 1283 |
TBA | 4/0 | 19 | 0.475 | 1.032 | 260 | 1.112 | 17x16 | 1.374 | 1.694 | 50 | 1.794 | 1372 |
TBA | 250 | 37 | 0.520 | 1.086 | 260 | 1.186 | 21x16 | 1.448 | 1.768 | 50 | 1.868 | 1521 |
TBA | 350 | 37 | 0.616 | 1.182 | 260 | 1.282 | 27x16 | 1.544 | 1.864 | 60 | 1.984 | 1790 |
TBA | 500 | 37 | 0.736 | 1.302 | 260 | 1.402 | 21x14 | 1.690 | 2.010 | 60 | 2.130 | 2109 |
TBA | 750 | 61 | 0.908 | 1.505 | 260 | 1.605 | 27x14 | 1.953 | 2.283 | 60 | 2.403 | 2827 |
TBA | 1000 | 61 | 1.060 | 1.657 | 260 | 1.787 | 27x14 | 2.135 | 2.465 | 60 | 2.585 | 3284 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 2 – Electrical and Engineering Data
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity in Vented Cable Tray 90°C‡ | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
1 | 11.3 | 502 | 0.211 | 0.265 | 0.057 | 0.061 | 0.559+j0.199 | 0.267+j0.060 | 3.7 | 193 | 194 |
1/0 | 11.6 | 634 | 0.168 | 0.211 | 0.053 | 0.058 | 0.504+j0.198 | 0.213+j0.058 | 4.7 | 221 | 219 |
2/0 | 11.9 | 799 | 0.133 | 0.167 | 0.049 | 0.056 | 0.389+j0.115 | 0.170+j0.056 | 5.9 | 253 | 246 |
3/0 | 12.2 | 1007 | 0.105 | 0.132 | 0.045 | 0.054 | 0.354+j0.113 | 0.135+j0.054 | 7.4 | 288 | 275 |
4/0 | 12.6 | 1270 | 0.0836 | 0.105 | 0.042 | 0.052 | 0.326+j0.112 | 0.108+j0.052 | 9.4 | 327 | 305 |
250 | 13.1 | 1500 | 0.0707 | 0.089 | 0.040 | 0.051 | 0.277+j0.086 | 0.092+j0.051 | 11.1 | 367 | 343 |
350 | 13.9 | 2100 | 0.0505 | 0.064 | 0.035 | 0.049 | 0.216+j0.063 | 0.068+j0.048 | 15.5 | 443 | 399 |
500 | 14.9 | 3000 | 0.0354 | 0.045 | 0.031 | 0.046 | 0.170+j0.051 | 0.050+j0.045 | 22.1 | 529 | 451 |
750 | 16.8 | 4500 | 0.0236 | 0.030 | 0.027 | 0.044 | 0.129+j0.039 | 0.036+j0.042 | 33.2 | 633 | 505 |
1000 | 18.1 | 6000 | 0.0177 | 0.023 | 0.024 | 0.042 | 0.122+j0.038 | 0.028+j0.041 | 44.3 | 711 | 544 |
* Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
Table 3 – Weights and Measurements (Metric)
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Dia. Over Inner Jacket | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | mm | mm | mm | mm | No. x AWG | mm | mm | mm | mm | kg/km | |
TBA | 1 | 19 | 7.59 | 21.74 | 6.60 | 23.77 | 11x16 | 30.43 | 38.56 | 1.27 | 41.10 | 1551 |
TBA | 1/0 | 19 | 8.53 | 22.68 | 6.60 | 24.71 | 11x16 | 31.37 | 39.50 | 1.27 | 42.04 | 1633 |
TBA | 2/0 | 19 | 9.55 | 23.70 | 6.60 | 25.73 | 17x16 | 32.39 | 40.51 | 1.27 | 43.05 | 1795 |
TBA | 3/0 | 19 | 10.74 | 24.89 | 6.60 | 26.92 | 17x16 | 33.58 | 41.71 | 1.27 | 44.25 | 1909 |
TBA | 4/0 | 19 | 12.07 | 26.21 | 6.60 | 28.24 | 17x16 | 34.90 | 43.03 | 1.27 | 45.57 | 2042 |
TBA | 250 | 37 | 13.21 | 27.58 | 6.60 | 30.12 | 21x16 | 36.78 | 44.91 | 1.27 | 47.45 | 2263 |
TBA | 350 | 37 | 15.65 | 30.02 | 6.60 | 32.56 | 27x16 | 39.22 | 47.35 | 1.52 | 50.39 | 2664 |
TBA | 500 | 37 | 18.69 | 33.07 | 6.60 | 35.61 | 21x14 | 42.93 | 51.05 | 1.52 | 54.10 | 3139 |
TBA | 750 | 61 | 23.06 | 38.23 | 6.60 | 40.77 | 27x14 | 49.61 | 57.99 | 1.52 | 61.04 | 4207 |
TBA | 1000 | 61 | 26.92 | 42.09 | 6.60 | 45.39 | 27x14 | 54.23 | 62.61 | 1.52 | 65.66 | 4887 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 4 – Electrical and Engineering Data (Metric)
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity in Vented Cable Tray 90°C‡ | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
1 | 287.02 | 2234 | 0.6923 | 0.87 | 0.0174 | 0.2001 | 0.559+j0.199 | 0.267+j0.060 | 3.7 | 193 | 194 |
1/0 | 294.64 | 2821 | 0.5512 | 0.69 | 0.0162 | 0.1903 | 0.504+j0.198 | 0.213+j0.058 | 4.7 | 221 | 219 |
2/0 | 302.26 | 3556 | 0.4364 | 0.55 | 0.0149 | 0.1837 | 0.389+j0.115 | 0.170+j0.056 | 5.9 | 253 | 246 |
3/0 | 309.88 | 4481 | 0.3445 | 0.43 | 0.0137 | 0.1772 | 0.354+j0.113 | 0.135+j0.054 | 7.4 | 288 | 275 |
4/0 | 320.04 | 5652 | 0.2743 | 0.34 | 0.0128 | 0.1706 | 0.326+j0.112 | 0.108+j0.052 | 9.4 | 327 | 305 |
250 | 332.74 | 6675 | 0.2320 | 0.29 | 0.0122 | 0.1673 | 0.277+j0.086 | 0.092+j0.051 | 11.1 | 367 | 343 |
350 | 353.06 | 9345 | 0.1657 | 0.21 | 0.0107 | 0.1608 | 0.216+j0.063 | 0.068+j0.048 | 15.5 | 443 | 399 |
500 | 378.46 | 13350 | 0.1161 | 0.15 | 0.0094 | 0.1509 | 0.170+j0.051 | 0.050+j0.045 | 22.1 | 529 | 451 |
750 | 426.72 | 20025 | 0.0774 | 0.10 | 0.0082 | 0.1444 | 0.129+j0.039 | 0.036+j0.042 | 33.2 | 633 | 505 |
1000 | 459.74 | 26700 | 0.0581 | 0.08 | 0.0073 | 0.1378 | 0.122+j0.038 | 0.028+j0.041 | 44.3 | 711 | 544 |
* Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
Revision: 3.0.00C