SPEC 26451
HVTECK CU 3/C 260TRXLPE TS PVC AIA PVC 25kV 100% CSA
3 Conductor, 260 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Conductor Shield:Semi-conducting cross-linked copolymer
- Insulation:260 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Filler:Interstices filled with non-hydroscoping/non-wicking fillers
- Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
- Binder:Polypropylene tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 25kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL) and 105°C for use in harsh Canadian environments. For installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CU 260 TRXLPE AIA 25kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground Size | Dia. Over Inner Jacket | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | inch | inch | mil | inch | AWG | inch | inch | mil | inch | lb/1000ft | |
TBA | 1 | 19 | 0.322 | 0.879 | 260 | 0.939 | 6 | 2.303 | 2.633 | 75 | 2.783 | 3491 |
TBA | 1/0 | 19 | 0.362 | 0.919 | 260 | 0.979 | 6 | 2.390 | 2.720 | 75 | 2.870 | 3825 |
TBA | 2/0 | 19 | 0.405 | 0.962 | 260 | 1.022 | 6 | 2.483 | 2.813 | 75 | 2.963 | 4223 |
TBA | 3/0 | 19 | 0.456 | 1.013 | 260 | 1.073 | 4 | 2.593 | 2.923 | 75 | 3.073 | 4766 |
TBA | 4/0 | 19 | 0.512 | 1.069 | 260 | 1.129 | 4 | 2.714 | 3.044 | 75 | 3.194 | 5363 |
TBA | 250 | 37 | 0.558 | 1.124 | 260 | 1.184 | 4 | 2.833 | 3.163 | 75 | 3.313 | 5905 |
TBA | 350 | 37 | 0.661 | 1.227 | 260 | 1.287 | 3 | 3.105 | 3.435 | 85 | 3.605 | 7456 |
TBA | 500 | 37 | 0.789 | 1.355 | 260 | 1.415 | 3 | 3.382 | 3.712 | 85 | 3.882 | 9320 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 2 – Electrical and Engineering Data
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity in Vented Cable Tray 90°C‡ | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
1 | 19.5 | 2009 | 0.129 | 0.161 | 0.068 | 0.047 | 0.530+j0.372 | 0.161+j0.047 | 6.0 | 202 | 226 |
1/0 | 20.1 | 2534 | 0.102 | 0.128 | 0.063 | 0.045 | 0.495+j0.356 | 0.128+j0.045 | 7.6 | 231 | 256 |
2/0 | 20.7 | 3194 | 0.081 | 0.101 | 0.059 | 0.043 | 0.465+j0.340 | 0.101+j0.043 | 9.6 | 265 | 290 |
3/0 | 21.5 | 4027 | 0.0642 | 0.081 | 0.054 | 0.042 | 0.440+j0.322 | 0.081+j0.042 | 12.1 | 303 | 327 |
4/0 | 22.4 | 5078 | 0.051 | 0.064 | 0.050 | 0.040 | 0.419+j0.304 | 0.064+j0.040 | 15.2 | 348 | 369 |
250 | 23.2 | 6000 | 0.0431 | 0.054 | 0.048 | 0.039 | 0.403+j0.289 | 0.054+j0.039 | 18.0 | 384 | 408 |
350 | 25.2 | 8400 | 0.0308 | 0.039 | 0.042 | 0.037 | 0.378+j0.261 | 0.039+j0.037 | 25.2 | 468 | 485 |
500 | 27.2 | 12000 | 0.0216 | 0.028 | 0.037 | 0.035 | 0.354+j0.232 | 0.029+j0.035 | 36.0 | 565 | 571 |
* Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
Table 3 – Weights and Measurements (Metric)
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground Size | Dia. Over Inner Jacket | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | mm | mm | mm | mm | AWG | mm | mm | mm | mm | kg/km | |
TBA | 1 | 19 | 8.18 | 22.33 | 6.60 | 23.85 | 6 | 58.50 | 66.88 | 1.91 | 70.69 | 5195 |
TBA | 1/0 | 19 | 9.19 | 23.34 | 6.60 | 24.87 | 6 | 60.71 | 69.09 | 1.91 | 72.90 | 5692 |
TBA | 2/0 | 19 | 10.29 | 24.43 | 6.60 | 25.96 | 6 | 63.07 | 71.45 | 1.91 | 75.26 | 6285 |
TBA | 3/0 | 19 | 11.58 | 25.73 | 6.60 | 27.25 | 4 | 65.86 | 74.24 | 1.91 | 78.05 | 7093 |
TBA | 4/0 | 19 | 13.00 | 27.15 | 6.60 | 28.68 | 4 | 68.94 | 77.32 | 1.91 | 81.13 | 7981 |
TBA | 250 | 37 | 14.17 | 28.55 | 6.60 | 30.07 | 4 | 71.96 | 80.34 | 1.91 | 84.15 | 8788 |
TBA | 350 | 37 | 16.79 | 31.17 | 6.60 | 32.69 | 3 | 78.87 | 87.25 | 2.16 | 91.57 | 11096 |
TBA | 500 | 37 | 20.04 | 34.42 | 6.60 | 35.94 | 3 | 85.90 | 94.28 | 2.16 | 98.60 | 13870 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 4 – Electrical and Engineering Data (Metric)
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity in Vented Cable Tray 90°C‡ | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
1 | 495.30 | 8940 | 0.4232 | 0.53 | 0.0207 | 0.1542 | 0.530+j0.372 | 0.161+j0.047 | 6.0 | 202 | 226 |
1/0 | 510.54 | 11276 | 0.3346 | 0.42 | 0.0192 | 0.1476 | 0.495+j0.356 | 0.128+j0.045 | 7.6 | 231 | 256 |
2/0 | 525.78 | 14213 | 0.2657 | 0.33 | 0.0180 | 0.1411 | 0.465+j0.340 | 0.101+j0.043 | 9.6 | 265 | 290 |
3/0 | 546.10 | 17920 | 0.2106 | 0.27 | 0.0165 | 0.1378 | 0.440+j0.322 | 0.081+j0.042 | 12.1 | 303 | 327 |
4/0 | 568.96 | 22597 | 0.1673 | 0.21 | 0.0152 | 0.1312 | 0.419+j0.304 | 0.064+j0.040 | 15.2 | 348 | 369 |
250 | 589.28 | 26700 | 0.1414 | 0.18 | 0.0146 | 0.1280 | 0.403+j0.289 | 0.054+j0.039 | 18.0 | 384 | 408 |
350 | 640.08 | 37380 | 0.1010 | 0.13 | 0.0128 | 0.1214 | 0.378+j0.261 | 0.039+j0.037 | 25.2 | 468 | 485 |
500 | 690.88 | 53400 | 0.0709 | 0.09 | 0.0113 | 0.1148 | 0.354+j0.232 | 0.029+j0.035 | 36.0 | 565 | 571 |
* Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
Revision: 3.0.00C