SPEC 26461
HVTECK AL 3/C 260NLEPR TS PVC AIA PVC 25kV 100% CSA
3 Conductor, 260 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
- Insulation:260 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Filler:Interstices filled with non-hydroscoping/non-wicking fillers
- Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
- Binder:Polypropylene tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 25kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL) and 105°C for use in harsh Canadian environments. For installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CPT AL 260 NLEPR AIA 25kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground Size | Dia. Over Inner Jacket | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | inch | inch | mil | inch | AWG | inch | inch | mil | inch | lb/1000ft | |
TBA | 1 | 19 | 0.299 | 0.856 | 260 | 0.916 | 6 | 2.254 | 2.584 | 75 | 2.734 | 3009 |
585951 | 1/0 | 19 | 0.336 | 0.893 | 260 | 0.953 | 6 | 2.334 | 2.664 | 75 | 2.814 | 3198 |
TBA | 2/0 | 19 | 0.376 | 0.933 | 260 | 0.993 | 6 | 2.420 | 2.750 | 75 | 2.900 | 3413 |
TBA | 3/0 | 19 | 0.423 | 0.980 | 260 | 1.040 | 6 | 2.522 | 2.852 | 75 | 3.002 | 3676 |
TBA | 4/0 | 19 | 0.475 | 1.032 | 260 | 1.092 | 6 | 2.634 | 2.964 | 75 | 3.114 | 3982 |
TBA | 250 | 37 | 0.520 | 1.086 | 260 | 1.146 | 4 | 2.751 | 3.081 | 75 | 3.231 | 4341 |
TBA | 350 | 37 | 0.616 | 1.182 | 260 | 1.242 | 4 | 3.008 | 3.338 | 85 | 3.508 | 5193 |
TBA | 500 | 37 | 0.736 | 1.302 | 260 | 1.362 | 3 | 3.267 | 3.597 | 85 | 3.767 | 6111 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 2 – Electrical and Engineering Data
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity in Vented Cable Tray 90°C‡ | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
1 | 19.1 | 1506 | 0.211 | 0.265 | 0.057 | 0.048 | 0.636+j0.382 | 0.265+j0.048 | 3.7 | 158 | 177 |
1/0 | 19.7 | 1901 | 0.168 | 0.211 | 0.053 | 0.046 | 0.580+j0.366 | 0.211+j0.046 | 4.7 | 181 | 200 |
2/0 | 20.3 | 2396 | 0.133 | 0.167 | 0.049 | 0.044 | 0.533+j0.351 | 0.167+j0.044 | 5.9 | 208 | 228 |
3/0 | 21.0 | 3020 | 0.105 | 0.132 | 0.045 | 0.043 | 0.494+j0.334 | 0.132+j0.043 | 7.4 | 239 | 258 |
4/0 | 21.8 | 3809 | 0.0836 | 0.105 | 0.042 | 0.041 | 0.463+j0.316 | 0.105+j0.041 | 9.4 | 273 | 292 |
250 | 22.6 | 4500 | 0.0707 | 0.089 | 0.040 | 0.040 | 0.442+j0.300 | 0.089+j0.040 | 11.1 | 302 | 321 |
350 | 24.6 | 6300 | 0.0505 | 0.064 | 0.035 | 0.038 | 0.408+j0.273 | 0.064+j0.038 | 15.5 | 368 | 385 |
500 | 26.4 | 9000 | 0.0354 | 0.045 | 0.031 | 0.036 | 0.377+j0.244 | 0.046+j0.036 | 22.1 | 454 | 462 |
* Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
Table 3 – Weights and Measurements (Metric)
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground Size | Dia. Over Inner Jacket | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | mm | mm | mm | mm | AWG | mm | mm | mm | mm | kg/km | |
TBA | 1 | 19 | 7.59 | 21.74 | 6.60 | 23.27 | 6 | 57.25 | 65.63 | 1.91 | 69.44 | 4478 |
585951 | 1/0 | 19 | 8.53 | 22.68 | 6.60 | 24.21 | 6 | 59.28 | 67.67 | 1.91 | 71.48 | 4759 |
TBA | 2/0 | 19 | 9.55 | 23.70 | 6.60 | 25.22 | 6 | 61.47 | 69.85 | 1.91 | 73.66 | 5079 |
TBA | 3/0 | 19 | 10.74 | 24.89 | 6.60 | 26.42 | 6 | 64.06 | 72.44 | 1.91 | 76.25 | 5470 |
TBA | 4/0 | 19 | 12.07 | 26.21 | 6.60 | 27.74 | 6 | 66.90 | 75.29 | 1.91 | 79.10 | 5926 |
TBA | 250 | 37 | 13.21 | 27.58 | 6.60 | 29.11 | 4 | 69.88 | 78.26 | 1.91 | 82.07 | 6460 |
TBA | 350 | 37 | 15.65 | 30.02 | 6.60 | 31.55 | 4 | 76.40 | 84.79 | 2.16 | 89.10 | 7728 |
TBA | 500 | 37 | 18.69 | 33.07 | 6.60 | 34.59 | 3 | 82.98 | 91.36 | 2.16 | 95.68 | 9094 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 4 – Electrical and Engineering Data (Metric)
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity in Vented Cable Tray 90°C‡ | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
1 | 485.14 | 6702 | 0.6923 | 0.87 | 0.0174 | 0.1575 | 0.636+j0.382 | 0.265+j0.048 | 3.7 | 158 | 177 |
1/0 | 500.38 | 8459 | 0.5512 | 0.69 | 0.0162 | 0.1509 | 0.580+j0.366 | 0.211+j0.046 | 4.7 | 181 | 200 |
2/0 | 515.62 | 10662 | 0.4364 | 0.55 | 0.0149 | 0.1444 | 0.533+j0.351 | 0.167+j0.044 | 5.9 | 208 | 228 |
3/0 | 533.40 | 13439 | 0.3445 | 0.43 | 0.0137 | 0.1411 | 0.494+j0.334 | 0.132+j0.043 | 7.4 | 239 | 258 |
4/0 | 553.72 | 16950 | 0.2743 | 0.34 | 0.0128 | 0.1345 | 0.463+j0.316 | 0.105+j0.041 | 9.4 | 273 | 292 |
250 | 574.04 | 20025 | 0.2320 | 0.29 | 0.0122 | 0.1312 | 0.442+j0.300 | 0.089+j0.040 | 11.1 | 302 | 321 |
350 | 624.84 | 28035 | 0.1657 | 0.21 | 0.0107 | 0.1247 | 0.408+j0.273 | 0.064+j0.038 | 15.5 | 368 | 385 |
500 | 670.56 | 40050 | 0.1161 | 0.15 | 0.0094 | 0.1181 | 0.377+j0.244 | 0.046+j0.036 | 22.1 | 454 | 462 |
* Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
Revision: 3.0.00C