SPEC 26525

HVTECK AL 1/C 280NLEPR CB PVC AIA PVC 28kV 100% CSA

Single Conductor, 280 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:280 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
  6. Neutral Separator:Mylar tape
  7. Inner Jacket:PVC inner jacket
  8. Armour:Aluminum Interlocked Armour (AIA)
  9. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 28kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL) and 105°C for use in harsh Canadian environments. For installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable. When used in a 3 phase system, the combination of each bond conductor from each single conductor cable provide a 100% bonded system to ground.

Specifications:

  • ASTM B800 8000 Series Aluminum Alloy Wire
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 280 NLEPR AIA 28kV 100% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralDia. Over Inner JacketDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchNo. x AWGinchinchmilinchlb/1000ft
    TBA1190.2990.8962800.97611x161.2381.558501.6581089
    TBA1/0190.3360.9332801.01311x161.2751.595501.6951145
    TBA2/0190.3760.9732801.05317x161.3151.635501.7351256
    TBA3/0190.4231.0202801.10017x161.3621.682501.7821334
    TBA4/0190.4751.0722801.17217x161.4341.754501.8541452
    TBA250370.5201.1262801.22621x161.4881.808601.9281611
    TBA350370.6161.2222801.32227x161.5841.904602.0241848
    TBA500370.7361.3422801.44221x141.7302.060602.1802236
    TBA750610.9081.5452801.64527x141.9932.323602.4432900
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity in Vented Cable Tray 90°C‡Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    111.65020.2110.2650.0590.0610.558+j0.2010.267+j0.0613.7193194
    1/011.96340.1680.2110.0550.0590.504+j0.1990.213+j0.0594.7221219
    2/012.17990.1330.1670.0510.0570.389+j0.1160.170+j0.0565.9253246
    3/012.510070.1050.1320.0480.0550.354+j0.1140.135+j0.0547.4288275
    4/013.012700.08360.1050.0440.0530.326+j0.1130.108+j0.0539.4327305
    25013.515000.07070.0890.0420.0520.277+j0.0870.092+j0.05111.1367343
    35014.221000.05050.0640.0370.0490.216+j0.0640.068+j0.04815.5443399
    50015.330000.03540.0450.0320.0470.170+j0.0510.050+j0.04622.1529451
    75017.145000.02360.0300.0290.0440.129+j0.0400.035+j0.04333.2633505
    * Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralDia. Over Inner JacketDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmkg/km
    TBA1197.5922.767.1124.7911x1631.4539.571.2742.111621
    TBA1/0198.5323.707.1125.7311x1632.3940.511.2743.051704
    TBA2/0199.5524.717.1126.7517x1633.4041.531.2744.071869
    TBA3/01910.7425.917.1127.9417x1634.5942.721.2745.261985
    TBA4/01912.0727.237.1129.7717x1636.4244.551.2747.092161
    TBA2503713.2128.607.1131.1421x1637.8045.921.5248.972397
    TBA3503715.6531.047.1133.5827x1640.2348.361.5251.412750
    TBA5003718.6934.097.1136.6321x1443.9452.321.5255.373328
    TBA7506123.0639.247.1141.7827x1450.6259.001.5262.054316
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity in Vented Cable Tray 90°C‡Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftkAmpAmpAmp
    1294.6422340.69230.870.01800.20010.558+j0.2010.267+j0.0613.7193194
    1/0302.2628210.55120.690.01680.19360.504+j0.1990.213+j0.0594.7221219
    2/0307.3435560.43640.550.01550.18700.389+j0.1160.170+j0.0565.9253246
    3/0317.5044810.34450.430.01460.18040.354+j0.1140.135+j0.0547.4288275
    4/0330.2056520.27430.340.01340.17390.326+j0.1130.108+j0.0539.4327305
    250342.9066750.23200.290.01280.17060.277+j0.0870.092+j0.05111.1367343
    350360.6893450.16570.210.01130.16080.216+j0.0640.068+j0.04815.5443399
    500388.62133500.11610.150.00980.15420.170+j0.0510.050+j0.04622.1529451
    750434.34200250.07740.100.00880.14440.129+j0.0400.035+j0.04333.2633505
    * Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I

    Revision: 3.0.00C