SPEC 26651
HVTECK CU 3/C 345TRXLPE TS PVC AIA PVC 35kV 100% CSA
3 Conductor, 345 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Conductor Shield:Semi-conducting cross-linked copolymer
- Insulation:345 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Filler:Interstices filled with non-hydroscoping/non-wicking fillers
- Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
- Binder:Polypropylene tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 35kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL) and 105°C for use in harsh Canadian environments. For installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CU 345 TRXLPE AIA 35kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground Size | Dia. Over Inner Jacket | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | inch | inch | mil | inch | AWG | inch | inch | mil | inch | lb/1000ft | |
TBA | 1/0 | 19 | 0.362 | 1.089 | 345 | 1.149 | 6 | 2.757 | 3.087 | 75 | 3.237 | 4520 |
TBA | 2/0 | 19 | 0.405 | 1.132 | 345 | 1.192 | 6 | 2.850 | 3.180 | 75 | 3.330 | 4936 |
TBA | 3/0 | 19 | 0.456 | 1.183 | 345 | 1.243 | 4 | 3.010 | 3.340 | 85 | 3.510 | 5723 |
TBA | 4/0 | 19 | 0.512 | 1.239 | 345 | 1.299 | 4 | 3.131 | 3.461 | 85 | 3.631 | 6351 |
TBA | 250 | 37 | 0.558 | 1.294 | 345 | 1.354 | 4 | 3.250 | 3.580 | 85 | 3.750 | 6923 |
671385^ | 350 | 37 | 0.661 | 1.397 | 345 | 1.457 | 3 | 3.472 | 3.802 | 85 | 3.972 | 8302 |
TBA | 350 | 37 | 0.661 | 1.397 | 345 | 1.457 | 3 | 3.472 | 3.802 | 85 | 3.972 | 8302 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
^ Orange Jacket
^ Orange Jacket
Table 2 – Electrical and Engineering Data
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity in Vented Cable Tray 90°C‡ | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
1/0 | 22.7 | 2534 | 0.102 | 0.128 | 0.075 | 0.049 | 0.481+j0.307 | 0.128+j0.049 | 7.6 | 231 | 256 |
2/0 | 23.3 | 3194 | 0.081 | 0.101 | 0.070 | 0.047 | 0.450+j0.294 | 0.101+j0.047 | 9.6 | 265 | 290 |
3/0 | 24.6 | 4027 | 0.0642 | 0.080 | 0.065 | 0.045 | 0.424+j0.279 | 0.080+j0.045 | 12.1 | 303 | 327 |
4/0 | 25.4 | 5078 | 0.051 | 0.064 | 0.060 | 0.043 | 0.402+j0.265 | 0.064+j0.043 | 15.2 | 348 | 369 |
250 | 26.3 | 6000 | 0.0431 | 0.054 | 0.057 | 0.042 | 0.387+j0.251 | 0.055+j0.042 | 18.0 | 384 | 408 |
350 | 27.8 | 8400 | 0.0308 | 0.039 | 0.051 | 0.040 | 0.361+j0.229 | 0.040+j0.040 | 25.2 | 468 | 485 |
350 | 27.8 | 8400 | 0.0308 | 0.039 | 0.051 | 0.040 | 0.361+j0.229 | 0.040+j0.040 | 25.2 | 468 | 485 |
* Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
Table 3 – Weights and Measurements (Metric)
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground Size | Dia. Over Inner Jacket | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | mm | mm | mm | mm | AWG | mm | mm | mm | mm | kg/km | |
TBA | 1/0 | 19 | 9.19 | 27.66 | 8.76 | 29.18 | 6 | 70.03 | 78.41 | 1.91 | 82.22 | 6727 |
TBA | 2/0 | 19 | 10.29 | 28.75 | 8.76 | 30.28 | 6 | 72.39 | 80.77 | 1.91 | 84.58 | 7346 |
TBA | 3/0 | 19 | 11.58 | 30.05 | 8.76 | 31.57 | 4 | 76.45 | 84.84 | 2.16 | 89.15 | 8517 |
TBA | 4/0 | 19 | 13.00 | 31.47 | 8.76 | 32.99 | 4 | 79.53 | 87.91 | 2.16 | 92.23 | 9451 |
TBA | 250 | 37 | 14.17 | 32.87 | 8.76 | 34.39 | 4 | 82.55 | 90.93 | 2.16 | 95.25 | 10303 |
671385^ | 350 | 37 | 16.79 | 35.48 | 8.76 | 37.01 | 3 | 88.19 | 96.57 | 2.16 | 100.89 | 12355 |
TBA | 350 | 37 | 16.79 | 35.48 | 8.76 | 37.01 | 3 | 88.19 | 96.57 | 2.16 | 100.89 | 12355 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
^ Orange Jacket
^ Orange Jacket
Table 4 – Electrical and Engineering Data (Metric)
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity in Vented Cable Tray 90°C‡ | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
1/0 | 576.58 | 11276 | 0.3346 | 0.42 | 0.0229 | 0.1608 | 0.481+j0.307 | 0.128+j0.049 | 7.6 | 231 | 256 |
2/0 | 591.82 | 14213 | 0.2657 | 0.33 | 0.0213 | 0.1542 | 0.450+j0.294 | 0.101+j0.047 | 9.6 | 265 | 290 |
3/0 | 624.84 | 17920 | 0.2106 | 0.26 | 0.0198 | 0.1476 | 0.424+j0.279 | 0.080+j0.045 | 12.1 | 303 | 327 |
4/0 | 645.16 | 22597 | 0.1673 | 0.21 | 0.0183 | 0.1411 | 0.402+j0.265 | 0.064+j0.043 | 15.2 | 348 | 369 |
250 | 668.02 | 26700 | 0.1414 | 0.18 | 0.0174 | 0.1378 | 0.387+j0.251 | 0.055+j0.042 | 18.0 | 384 | 408 |
350 | 706.12 | 37380 | 0.1010 | 0.13 | 0.0155 | 0.1312 | 0.361+j0.229 | 0.040+j0.040 | 25.2 | 468 | 485 |
350 | 706.12 | 37380 | 0.1010 | 0.13 | 0.0155 | 0.1312 | 0.361+j0.229 | 0.040+j0.040 | 25.2 | 468 | 485 |
* Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
Revision: 3.0.00C