SPEC 25010

CSA TECK 90 CU 1000V NON-SHIELDED XLPE POWER CABLE

1000V, Non-Shielded, XLPE Insulation, FT4, -40°C, HL (Hazardous Locations), 90°C

...

Construction:

  1. Conductor:Class B stranded compressed copper in accordance with ASTM B3 and ASTM B8
  2. Insulation:XLPE (Cross Linked Polyethylene), Minimum Average Thickness: 4/0 = 0.08 inches (2.03 mm), 250 kcmil to 1000 kcmil = 0.090 inches (2.3 mm), 90°C
  3. Concentric Bonding Conductors:Class B, concentric bare copper wire serve
  4. Binder:Polypropylene Separator
  5. Inner Jacket:Black PVC, Minumum average thickness - 4/0 = 0.050" (1.27mm), 250 kcmil to 1000 kcmil = 0.060" (1.5 mm)
  6. Armor:Aluminum Interlocked Armour (AIA)
  7. Overall Jacket:Black PVC (optional colours available), Minimum Thickness: 4/0 to 400 kcmil = 0.050 inches (1.3 mm), 500 kcmil to 1000 kcmil = 0.060 inches (1.5 mm)

Applications and Features:

Southwire's Single Conductor 1kV Teck 90 is a CSA approved armoured cable for Industrial and Commercial applications. FT4, -40C, HL, AG14 and 90°C rated for use in harsh Canadian environments. Rated for installation in cable trays, duct banks, direct burial, troughs, hazardous locations, continuous rigid cable supports, and concrete encaseable. CSA AG14 Acid Gas compliance.
  • -40°C - CSA Cold Bend and Impact Temperature
  • -25°C - Min. Installation Temperature
  • 90°C - Max. Continuous Operating Temperature
  • 140°C for Emergency Overload Temperature

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 131 Type TECK 90 Cable
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • CSA AG14 - Acid Gas Compliance
  • ICEA S-96-659 (NEMA WC 71) 2001-5000 V Nonshielded Cables
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • Sample Print Legend:

    {SQMTR} SOUTHWIRE {CSA} LL90458 1/C XX KCMIL CU TECK 90 XLPE -40{D}C FT4 AG14 SUN RES 90{D}C 1000V HL USA
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessConcentric NeutralDia. Over ArmourApprox. ODApprox. Weight
    AWG/KcmilNo.inchinchmilNo. x AWGinchinchlb/1000ft
    5978244/0370.510.6669013x14(3)1.221.311271
    606912250370.560.749017x14(2)1.321.421497
    TBA300370.610.799017x14(2)1.351.441677
    586405350370.660.849021x14(1)1.421.521905
    TBA400370.710.899021x14(1)1.481.572146
    581915500370.790.979017x12(1/0)1.591.712558
    TBA600610.871.059017x12(1/0)1.641.752908
    576233750610.971.159021x12(2/0)1.761.883551
    5842581000611.121.39021x12(2/0)1.922.044462
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Other conductor sizes and outer jacket colours are available upon request. (#s in brackets represent # of strands / conductor. Number of strands may vary as per CSA standard.)
    ** Non-Standard sizes are available upon request. Reel sizes are not guaranteed. The factory reserves the right to make changes as necessary to optimize manufacturing requirements.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CAllowable Ampacity In Air 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftAmpAmp
    4/015.7216930.0510.064405385
    2501720000.04310.0435455499
    30017.324000.0360.0367500550
    35018.328000.03080.0317570597
    40018.932000.02690.028615642
    50020.540000.02160.0413700721
    6002148000.0180.0194780790
    75022.660000.01440.0163885885
    100024.580000.01080.013210551020
    † Ampacities are based on Table 1 of the 2015 Canadian Electrical Code Part I
    ‡ Ampacities are based on Table D8A and Detail 1 of Diagram D8 of the 2015 Canadian Electrical Code Part I
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessConcentric NeutralDia. Over ArmourApprox. ODApprox. Weight
    AWG/KcmilNo.mmmmmmNo. x AWGmmmmkg/km
    5978244/03712.9516.922.2913x14(3)30.9933.271891
    6069122503714.2218.802.2917x14(2)33.5336.072228
    TBA3003715.4920.072.2917x14(2)34.2936.582496
    5864053503716.7621.342.2921x14(1)36.0738.612835
    TBA4003718.0322.612.2921x14(1)37.5939.883194
    5819155003720.0724.642.2917x12(1/0)40.3943.433807
    TBA6006122.1026.672.2917x12(1/0)41.6644.454328
    5762337506124.6429.212.2921x12(2/0)44.7047.755284
    58425810006128.4533.022.2921x12(2/0)48.7751.826640
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Other conductor sizes and outer jacket colours are available upon request. (#s in brackets represent # of strands / conductor. Number of strands may vary as per CSA standard.)
    ** Non-Standard sizes are available upon request. Reel sizes are not guaranteed. The factory reserves the right to make changes as necessary to optimize manufacturing requirements.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CAllowable Ampacity In Air 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilmmnewtonΩ/kmΩ/kmAmpAmp
    4/0399.2975340.16730.21405385
    250431.8089000.14140.14455499
    300439.42106800.11810.12500550
    350464.82124600.10100.10570597
    400480.06142400.08830.09615642
    500520.70178000.07090.14700721
    600533.40213600.05910.06780790
    750574.04267000.04720.05885885
    1000622.30356000.03540.0410551020
    † Ampacities are based on Table 1 of the 2015 Canadian Electrical Code Part I
    ‡ Ampacities are based on Table D8A and Detail 1 of Diagram D8 of the 2015 Canadian Electrical Code Part I

    Revision: 3.0.00C