SPEC 25051

CSA TECK 90 1000V PVC POWER CABLE

1000V Multi Conductor, 8AWG -1000 Kcmil Copper, FT4 - Flame Retardancy Rating, XLPE Insulation, Aluminum Interlocked Armour, Sunlight Resistant, Direct Buried, -40°C - 90°C, Rated HL, AG14

...

Construction:

  1. Conductor:Class B stranded copper, compressed or compact, in accordance with ASTM B3 and B8.
  2. Insulation:Cross-Linked Polyethylene (XLPE), Colour Code: 2/C black, white; 3/C red, black, blue; 4/C red, black, blue, white; For cables larger than No. 2 AWG or more than 4/C, the insulation is black and numbered
  3. Grounding Conductors:Uninsulated Class B stranded grounding conductor
  4. Inner Jacket:Black Polyvinyl Chloride (PVC)
  5. Armor:Aluminum Interlocked Armour (AIA)
  6. Overall Jacket:Black PVC (optional colours available)

Applications and Features:

For exposed or concealed wiring in wet or dry locations. For use in ventilated, non-ventilated and ladder type cable troughs and ventilated flexible cableway in wet, dry, hazardous locations or direct buried. Sunlight Resistant. Typical applications are for control. lighting and power circuits in: pulp and paper mills, steel mills, food processing plants, commercial centers, mines, generating stations, refineries, industrial plants and chemical plants. Rated for 1000 lbs./FT maximum sidewall pressure.
  • -40°C - CSA Cold Bend and Impact Temperature
  • -40°C - Min. Installation Temperature
  • 90°C - Max. Continuous Operating Temperature
  • Listed for direct burial, CSA File Listing: LL90458.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 131 Type TECK 90 Cable
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • CSA AG14 - Acid Gas Compliance
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Sample Print Legend:

    {SQMTR} SOUTHWIRE {CSA} LL90458 X/C XX AWG CU TECK 90 XLPE -40{D}C FT4 AG14 SUN RES 90{D}C 1000V HL USA
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberGroundDia. Over Inner JacketDiameter Over ArmorJacket ThicknessApprox. ODCopper WeightApprox. WeightDC ResistanceAC Resistance @ 90°CMin Bending RadiusAllowable Ampacity 75°C *Allowable Ampacity 90°C *
    AWGNo.No. x AWGinchinchmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    568605^821 x 100.590.8400.91353970.6520.8156.35050
    671448821 x 100.590.8400.91353970.6520.8156.35050
    561963831 x 100.6270.837400.9171864660.6520.8156.415050
    561964841 x 100.6810.891400.9912385530.6520.8156.935050
    573821^621 x 80.720.93401.032155360.4110.5147.216565
    671452621 x 80.720.93401.032155360.4110.5147.216565
    561965631 x 80.7681.088401.1872977100.4110.5148.306565
    561966641 x 80.8831.203401.2833788880.4110.5148.986565
    582005421 x 80.8071.129401.2293117300.2580.3238.608585
    561967431 x 80.9071.228401.3284419580.2580.3239.298585
    561968441 x 80.9941.318401.39457211440.2580.3239.758585
    571184^221 x 60.9631.283401.38349510160.1620.2039.68115115
    671456221 x 60.9631.283401.38349510160.1620.2039.68115115
    561972231 x 61.031.35401.4570212810.1620.20310.15115115
    561973241 x 61.1311.451401.55190915590.1620.20310.85115115
    561974131 x 61.2111.531501.65186415950.1290.16211.55130130
    561975141 x 61.3331.653501.773112519700.1290.16112.41130130
    5619761/031 x 61.2951.615501.735106918670.1020.12812.14150150
    5619781/041 x 61.4271.747501.868139923030.1020.12813.07150150
    5619482/031 x 61.391.71501.83132622820.0810.10212.81175175
    5619492/041 x 61.5331.864501.984174227740.0810.10113.88175175
    5864003/021 x 41.41.72501.84117619960.0810.10212.88200200
    5619503/031 x 41.4981.818501.938169926230.0640.08113.56200200
    5619523/041 x 41.6541.984502.104222333380.0640.08014.72200200
    5619534/031 x 41.6191.949502.047210931680.0510.06414.32230230
    5619544/041 x 41.8492.179502.299276941030.0510.06416.09230230
    56195525031 x 41.8262.156502.275246937600.0430.05515.92255255
    56195625041 x 42.0132.343602.464324848780.0430.05417.24255255
    56195730031 x 41.942.276602.42293643780.0310.04017.0285285
    56195830041 x 42.1412.471602.622387255120.0310.03918.35285285
    56195935031 x 32.0482.378602.529343849620.0220.02917.70310310
    56196035041 x 32.2622.592602.742453062660.0220.02719.19310310
    56196150031 x 32.3272.657602.807484165740.0180.02419.64380380
    56196250041 x 32.5732.903603.054640183820.0180.02321.37380380
    59231460031 x 22.4912.764602.971582076600.0140.02020.79420420
    56847875031 x 22.7113.041803.211722392860.0140.01922.47475475
    56847975041 x 23.0633.273803.4439562121200.0140.01924.10475475
    641155100031 x 13.1213.451803.6199616122310.0110.01525.33545615
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Ampacities based on not more than 3 conductors (4 with neutral) in raceway or cable as per Table 2 of 2015 Canadian Electrical Code Part 1.
    ^ Colour Code: 2/C black, Red

    Revision: 3.0.00C