SPEC 25055

3/C CSA TECK 90 1000V ALUMINUM POWER CABLE

Three Conductor 1000V Multi Conductor, FT4 - Flame Retardancy Rating, Direct Burial, XLPE Insulation, Aluminum Interlocked Armour, Sunlight Resistant, -40ºC Min, 90ºC Max, Rated HL (Hazardous Locations)

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series Aluminum ACM in accordance with ASTM B801.
  2. Insulation:Cross-Linked Polyethylene (XLPE), Color Code: Black and numbered
  3. Grounding Conductors:Uninsulated Aluminum Class B stranded grounding conductor
  4. Assembly:Oil Impregnated Kraft Paper Binder
  5. Inner Jacket:Black Polyvinyl Chloride (PVC)
  6. Armor:Aluminum Interlocked Armour (AIA)
  7. Overall Jacket:Black PVC (optional colours available)

Applications and Features:

For exposed or concealed wiring in wet or dry locations. For use in ventilated, non-ventilated and ladder type cable troughs and ventilated flexible cableway in wet, dry, hazardous locations or direct buried. Sunlight Resistant. Typical applications are for control. lighting and power circuits in: pulp and paper mills, steel mills, food processing plants, commercial centers, mines, generating stations, refineries, industrial plants and chemical plants. AG14 - Acid Gas Compliance. Voltage 1000V CSA / 600V UL.

Specifications:

  • ASTM B800 8000 Series Aluminum Alloy Wire
  • CSA C22.2 No. 131 Type TECK 90 Cable
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • CSA AG14 - Acid Gas Compliance
  • CSA AWM IB 105°C 600V. FT4-ST1
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Sample Print Legend:

    SOUTHWIRE {CSA} LL90458 X/C XX AWG 8000 TECK 90 XLPE -40{D}C FT4 SUN RES 90{D}C 1000V HL {YYYY} USA {UL} E96627 TYPE MC XLPE 600V SUN. RES. DIRECT BURIAL 90{D}C {SEQUENTIAL METER MARKS} SEQ METERS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessGround SizeDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.inchinchmilAWGinchmilinchlb/1000ft
    584846^670.1690.2956061.09551.20535
    584848^260.2680.3946061.35551.46818
    5848521190.2990.4598041.49551.6351029
    5848731/0190.3360.4968041.57551.7151146
    5848762/0190.3760.5368041.66551.8021292
    5848833/0190.4230.5838041.76551.9031456
    5848914/0190.4750.6358021.89552.0251714
    583957250370.5200.79022.14552.2312203
    TBA350370.6160.7969022.29752.442453
    583961500370.7360.9169012.54752.7323463
    TBA750610.9081.088901/02.91803.074181
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Ampacity based on Canadian Electrical Code Table 4 for not more than 3 current-carrying conductors, ambient 30°C. The ampacity shall be derated as per CE Code Table 5C. All measurements are subject to nominal manufacturing tolerances.
    ‡ Ampacity based on Canadian Electric Code Table D10B (Detail 1): Allowable insulated aluminum conductor ampacities for cables rated not more than 5000 V and unshielded for the installation configurations
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzPhase Short Circuit Current @ 60HzAllowable Ampacity In Raceway 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    68.44720.6750.8480.029601655-
    210.211940.2660.3340.02815213100-
    111.215060.2110.2650.02919186115-
    1/011.819010.1680.2110.02824209135203
    2/012.423960.1330.1670.02830513150230
    3/01330200.1050.1320.02738468175261
    4/01438090.0840.1050.02648509205298
    25015.345000.0710.0890.02757313230324
    3501763000.0510.0640.02680238280390
    50018.890000.0350.0450.025114625350473
    75021.5135000.0240.0310.025171938435586
    * Ampacity based on Canadian Electrical Code Table 4 for not more than 3 current-carrying conductors, ambient 30°C. The ampacity shall be derated as per CE Code Table 5C. All measurements are subject to nominal manufacturing tolerances.
    ‡ Ampacity based on Canadian Electric Code Table D10B (Detail 1): Allowable insulated aluminum conductor ampacities for cables rated not more than 5000 V and unshielded for the installation configurations
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessGround SizeDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.mmmmmmAWGmmmmmmkg/km
    584846^674.297.491.52627.691.4030.48796
    584848^266.8110.011.52634.291.4037.081217
    5848521197.5911.662.03437.851.4041.531531
    5848731/0198.5312.602.03439.881.4043.561705
    5848762/0199.5513.612.03442.161.4045.771923
    5848833/01910.7414.812.03444.701.4048.342167
    5848914/01912.0716.132.03248.011.4051.432551
    5839572503713.2117.782.29254.361.4056.673278
    TBA3503715.6520.222.29258.171.9161.983650
    5839615003718.6923.272.29164.521.9169.395154
    TBA7506123.0627.642.291/073.912.0377.986222
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Ampacity based on Canadian Electrical Code Table 4 for not more than 3 current-carrying conductors, ambient 30°C. The ampacity shall be derated as per CE Code Table 5C. All measurements are subject to nominal manufacturing tolerances.
    ‡ Ampacity based on Canadian Electric Code Table D10B (Detail 1): Allowable insulated aluminum conductor ampacities for cables rated not more than 5000 V and unshielded for the installation configurations
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzPhase Short Circuit Current @ 60HzAllowable Ampacity In Raceway 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilmmnewtonΩ/kmΩ/kmΩ/kmkAmpAmpAmp
    6213.3621002.21462.780.0951601655-
    2259.0853130.87271.100.091915213100-
    1284.4867020.69230.870.095119186115-
    1/0299.7284590.55120.690.091924209135203
    2/0314.96106620.43640.550.091930513150230
    3/0330.20134390.34450.430.088638468175261
    4/0355.60169500.27560.340.085348509205298
    250388.62200250.23290.290.088657313230324
    350431.80280350.16730.210.085380238280390
    500477.52400500.11480.150.0820114625350473
    750546.10600750.07870.100.0820171938435586
    * Ampacity based on Canadian Electrical Code Table 4 for not more than 3 current-carrying conductors, ambient 30°C. The ampacity shall be derated as per CE Code Table 5C. All measurements are subject to nominal manufacturing tolerances.
    ‡ Ampacity based on Canadian Electric Code Table D10B (Detail 1): Allowable insulated aluminum conductor ampacities for cables rated not more than 5000 V and unshielded for the installation configurations

    Phase Colors

    ^ Phase Colors: Black, Red, Blue

    Revision: 3.0.00C