SPEC 81112

15kV AL 133% TRXLPE One-Third Neutral LLDPE Primary UD

Single Conductor, 220 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, One-third Concentric Neutral, Linear Low Density Polyethylene (LLDPE) Jacket. Silicone Free

...

Construction:

  1. Conductor:Class B compressed Aluminum ASTM 1350 ¾ hard H16/H26; Conductor moisture block (optional)
  2. Conductor Shield:Conventional Semi-conducting cross-linked copolymer; Supersmooth conductor shield optional; A conductor tape is used for cable size larger than or equal to 1500 Kcmil
  3. Insulation:220 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Neutral:Helically applied soft drawn bare copper one-third concentric neutral
  6. Overall Jacket:Linear Low Density Polyethylene (LLDPE) Jacket, Black (red extruded stripes optional); PowerGlide® LLDPE jacket optional

Applications and Features:

Southwire's 15kV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, sunlight, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation. 130°C for emergency overload, and 250°C for short circuit conditions. Jacket types available that can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.

Specifications:

  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B609 Standard Specification for Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
  • ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5 - 46kV
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • UL 1072 Listed as MV 90 When Specified
  • Optional CSA: CSA 68.5 and -40C optional marking available upon request
  • Sample Print Legend:

    SOUTHWIRE HI-DRI(R) [CONDUCTOR SIZE] [AWG or KCMIL] AL 15000 VOLTS TRXLPE INSULATION 220 MILS -- (NESC) -- SOUTHWIRE {MMM} {YYYY} NON-CONDUCTING JACKET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension*
    AWG/KcmilinchinchmilinchNo. x AWGΩ/1000ftmilinchlb/1000ftinchlb
    5114032 (1)0.2580.7352200.8156x140.438501.04346112.5398
    6117002 (7)0.2830.7602200.8406x140.438501.06848512.8398
    TBA1 (1)0.2890.7662200.8466x140.438501.07449312.9502
    TBA1 (19)0.3220.7992200.8796x140.438501.10752213.3502
    TBA1/0 (1)0.3250.8022200.8826x140.438501.11053113.3634
    6117821/0 (19)0.3520.8292200.9096x140.438501.13755513.6634
    6202912/0 (19)0.3950.8722200.95210x140.376501.18065214.2799
    6278602/0 (19)0.3950.8722200.9527x140.376501.18061614.2799
    TBA3/0 (19)0.4430.9202201.0009x140.292501.22869914.71007
    6133654/0 (19)0.4980.9752201.05511x140.239501.28379415.41270
    613449#4/0 (19)0.4980.9752201.05511x140.239501.28379415.41270
    TBA250 (37)0.5581.0442201.14413x140.202501.37292416.51500
    613615350 (37)0.6611.1472201.24718x140.146501.475114017.72100
    683847500 (37)0.7891.2752201.37516x120.104501.635148419.63000
    604102750 (61)0.9681.4632201.56324x120.069801.883206422.64500
    6124941000 (61)1.1171.6122201.74220x100.052802.106265525.36000
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftA/1000ftW/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    2 (1)0.2660.3340.0620.0510.1390.3620.652+j0.2330.335+j0.0512196.1120150
    2 (7)0.2660.3340.0590.0490.1470.3820.651+j0.2320.335+j0.0492196.1120150
    1 (1)0.2110.2650.0580.0490.1490.3870.582+j0.2320.266+j0.0492196.1140175
    1 (19)0.2110.2650.0540.0480.1590.4130.581+j0.2300.266+j0.0482196.1140175
    1/0 (1)0.1680.2110.0540.0470.1600.4160.527+j0.2300.212+j0.0472196.1155195
    1/0 (19)0.1680.2110.0510.0460.1680.4370.527+j0.2300.212+j0.0462196.1155195
    2/0 (19)0.1330.1670.0480.0450.1810.4710.459+j0.1900.168+j0.0454182180225
    2/0 (19)0.1330.1670.0480.0450.1810.4710.459+j0.1900.168+j0.0452562.1180225
    3/0 (19)0.1050.1320.0440.0430.1960.5080.383+j0.1370.133+j0.0433294.2200255
    4/0 (19)0.08360.1050.0410.0420.2120.5510.322+j0.1050.107+j0.0424026.2235285
    4/0 (19)0.08360.1050.0410.0420.2120.5510.322+j0.1050.107+j0.0424026.2235285
    250 (37)0.07070.0890.0370.0410.2330.6040.279+j0.0850.091+j0.0404758.3
    350 (37)0.05050.0640.0330.0390.2630.6830.208+j0.0570.066+j0.0386588.4310375
    500 (37)0.03540.0450.0290.0370.3010.7810.151+j0.0420.048+j0.0369304.6370450
    750 (61)0.02360.0300.0240.0360.3560.9240.102+j0.0290.035+j0.03413956.9460545
    1000 (61)0.01770.0230.0220.0350.3991.0370.077+j0.0260.029+j0.03218488.1520620
    * Calculations are based on three cables triplexed / concentric shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Figure 7 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
    ‡ Ampacities are based on Figure 1 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension*
    AWG/KcmilmmmmmmmmNo. x AWGΩ/kmmmmmkg/kmmmnewton
    5114032 (1)6.5518.675.5920.706x141.441.2726.49686317.501771
    6117002 (7)7.1919.305.5921.346x141.441.2727.13722325.121771
    TBA1 (1)7.3419.465.5921.496x141.441.2727.28734327.662234
    TBA1 (19)8.1820.295.5922.336x141.441.2728.12777337.822234
    TBA1/0 (1)8.2520.375.5922.406x141.441.2728.19790337.822821
    6117821/0 (19)8.9421.065.5923.096x141.441.2728.88826345.442821
    6202912/0 (19)10.0322.155.5924.1810x141.231.2729.97970360.683556
    6278602/0 (19)10.0322.155.5924.187x141.231.2729.97917360.683556
    TBA3/0 (19)11.2523.375.5925.409x140.961.2731.191040373.384481
    6133654/0 (19)12.6524.765.5926.8011x140.781.2732.591182391.165652
    613449#4/0 (19)12.6524.765.5926.8011x140.781.2732.591182391.165652
    TBA250 (37)14.1726.525.5929.0613x140.661.2734.851375419.106675
    613615350 (37)16.7929.135.5931.6718x140.481.2737.471697449.589345
    683847500 (37)20.0432.395.5934.9316x120.341.2741.532208497.8413350
    604102750 (61)24.5937.165.5939.7024x120.232.0347.833072574.0420025
    6124941000 (61)28.3740.945.5944.2520x100.172.0353.493951642.6226700
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilΩ/kmΩ/kmMΩ*kmΩ/kmA/kmW/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2 (1)0.87271.100.01890.16730.4561.18770.652+j0.2330.335+j0.0512196.1120150
    2 (7)0.87271.100.01800.16080.4821.25330.651+j0.2320.335+j0.0492196.1120150
    1 (1)0.69230.870.01770.16080.4891.26970.582+j0.2320.266+j0.0492196.1140175
    1 (19)0.69230.870.01650.15750.5221.35500.581+j0.2300.266+j0.0482196.1140175
    1/0 (1)0.55120.690.01650.15420.5251.36480.527+j0.2300.212+j0.0472196.1155195
    1/0 (19)0.55120.690.01550.15090.5511.43370.527+j0.2300.212+j0.0462196.1155195
    2/0 (19)0.43640.550.01460.14760.5941.54530.459+j0.1900.168+j0.0454182180225
    2/0 (19)0.43640.550.01460.14760.5941.54530.459+j0.1900.168+j0.0452562.1180225
    3/0 (19)0.34450.430.01340.14110.6431.66670.383+j0.1370.133+j0.0433294.2200255
    4/0 (19)0.27430.340.01250.13780.6961.80770.322+j0.1050.107+j0.0424026.2235285
    4/0 (19)0.27430.340.01250.13780.6961.80770.322+j0.1050.107+j0.0424026.2235285
    250 (37)0.23200.290.01130.13450.7641.98160.279+j0.0850.091+j0.0404758.3
    350 (37)0.16570.210.01010.12800.8632.24080.208+j0.0570.066+j0.0386588.4310375
    500 (37)0.11610.150.00880.12140.9882.56230.151+j0.0420.048+j0.0369304.6370450
    750 (61)0.07740.100.00730.11811.1683.03150.102+j0.0290.035+j0.03413956.9460545
    1000 (61)0.05810.080.00670.11481.3093.40220.077+j0.0260.029+j0.03218488.1520620
    * Calculations are based on three cables triplexed / concentric shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Figure 7 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
    ‡ Ampacities are based on Figure 1 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)

    Revision: 3.0.00C