SPEC 81115

15kV AL 133% TRXLPE LCT LLDPE Primary UD

Single Conductor, 220 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Longitudinally Corrugated Tape Shield, Linear Low Density Polyethylene (LLDPE) Jacket. Silicone Free

...

Construction:

  1. Conductor:Moisture blocked class B compressed Aluminum ASTM B231 1350 ¾ hard H16/H26 ( Non Moisture Blocked Optional )
  2. Conductor Shield:Conventional Semi-conducting cross-linked copolymer; Supersmooth conductor shield optional; A conductor tape is used for cable size larger than or equal to 1500 Kcmil
  3. Insulation:220 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Tape Shield:10 mils Longitudinally Corrugated Tape Shield
  6. Overall Jacket:Linear Low Density Polyethylene (LLDPE) Jacket, black with red extruded stripes; PowerGlide® LLDPE jacket optional

Applications and Features:

Southwire's 15kV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, sunlight, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation. 130°C for emergency overload, and 250°C for short circuit conditions. Jacket types available that can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.

Specifications:

  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B609 Standard Specification for Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
  • ICEA S-97-682 Standard for Shielded Utility Cable Rated for 5 - 46kV
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • UL 1072 Listed as MV 90 When Specified
  • Optional CSA: CSA 68.5 and -40C optional marking available upon request
  • Sample Print Legend:

    SOUTHWIRE HI-DRI(R) [CONDUCTOR SIZE] [AWG or KCMIL] AL 15000 VOLTS TRXLPE INSULATION 220 MILS -- (NESC) -- SOUTHWIRE {MMM} {YYYY} NON-CONDUCTING JACKET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension*
    AWG/Kcmilinchinchmilinchmilinchlb/1000ftinchlb
    TBA2 (1)0.2580.7352200.795801.05550212.7398
    TBA2 (7)0.2830.7602200.820801.08052413.0398
    TBA1 (1)0.2890.7662200.826801.08653213.0502
    TBA1 (19)0.3220.7992200.859801.11960313.4502
    TBA1/0 (1)0.3250.8022200.862801.12261313.5634
    TBA1/0 (19)0.3520.8292200.889801.14963513.8634
    TBA2/0 (19)0.3950.8722200.932801.19268314.3799
    TBA3/0 (19)0.4430.9202200.980801.24074014.91007
    TBA4/0 (19)0.4980.9752201.035801.29580915.51270
    TBA250 (37)0.5581.0442201.104801.36489216.41500
    TBA350 (37)0.6611.1472201.207801.467104617.62100
    TBA500 (37)0.7891.2752201.335801.561130418.73000
    TBA750 (61)0.9681.4632201.5231101.809172121.74500
    TBA1000 (61)1.1171.6122201.6721101.958205623.56000
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftA/1000ftW/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    2 (1)0.2660.3340.0620.0510.1390.3620.648+j0.2050.335+j0.0513425.1120150
    2 (7)0.2660.3340.0590.0500.1470.3820.642+j0.1960.335+j0.0503513.8120150
    1 (1)0.2110.2650.0580.0490.1490.3870.572+j0.1940.266+j0.0493535.1140170
    1 (19)0.2110.2650.0540.0480.1590.4130.565+j0.1840.266+j0.0483652.3140170
    1/0 (1)0.1680.2110.0540.0480.1600.4160.511+j0.1830.212+j0.0483663.0155195
    1/0 (19)0.1680.2110.0510.0470.1680.4370.505+j0.1750.212+j0.0463758.9155195
    2/0 (19)0.1330.1670.0480.0450.1810.4710.453+j0.1640.168+j0.0453911.6180220
    3/0 (19)0.1050.1320.0440.0440.1960.5080.409+j0.1520.133+j0.0434082.1200250
    4/0 (19)0.08360.1050.0410.0420.2120.5510.372+j0.1410.106+j0.0424277.4235285
    250 (37)0.07070.0890.0370.0400.2330.6040.345+j0.1280.090+j0.0404522.4
    350 (37)0.05050.0640.0330.0380.2630.6830.304+j0.1120.065+j0.0384888.2310375
    500 (37)0.03540.0450.0290.0360.3010.7810.268+j0.0970.046+j0.0365342.8375455
    750 (61)0.02360.0300.0240.0350.3560.9240.231+j0.0790.032+j0.0356010.5470560
    1000 (61)0.01770.0230.0220.0330.3991.0370.209+j0.0690.025+j0.0336539.6540645
    * Calculations are based on three cables triplexed / tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Figure 7 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
    ‡ Ampacities are based on Figure 1 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension*
    AWG/Kcmilmmmmmmmmmmmmkg/kmmmnewton
    TBA2 (1)6.5518.675.5920.192.0326.80747322.581771
    TBA2 (7)7.1919.305.5920.832.0327.43780330.201771
    TBA1 (1)7.3419.465.5920.982.0327.58792330.202234
    TBA1 (19)8.1820.295.5921.822.0328.42897340.362234
    TBA1/0 (1)8.2520.375.5921.892.0328.50912342.902821
    TBA1/0 (19)8.9421.065.5922.582.0329.18945350.522821
    TBA2/0 (19)10.0322.155.5923.672.0330.281016363.223556
    TBA3/0 (19)11.2523.375.5924.892.0331.501101378.464481
    TBA4/0 (19)12.6524.765.5926.292.0332.891204393.705652
    TBA250 (37)14.1726.525.5928.042.0334.651327416.566675
    TBA350 (37)16.7929.135.5930.662.0337.261557447.049345
    TBA500 (37)20.0432.395.5933.912.0339.651941474.9813350
    TBA750 (61)24.5937.165.5938.682.7945.952561551.1820025
    TBA1000 (61)28.3740.945.5942.472.7949.733060596.9026700
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilΩ/kmΩ/kmMΩ*kmΩ/kmA/kmW/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2 (1)0.87271.100.01890.16730.4561.18770.648+j0.2050.335+j0.0513425.1120150
    2 (7)0.87271.100.01800.16400.4821.25330.642+j0.1960.335+j0.0503513.8120150
    1 (1)0.69230.870.01770.16080.4891.26970.572+j0.1940.266+j0.0493535.1140170
    1 (19)0.69230.870.01650.15750.5221.35500.565+j0.1840.266+j0.0483652.3140170
    1/0 (1)0.55120.690.01650.15750.5251.36480.511+j0.1830.212+j0.0483663.0155195
    1/0 (19)0.55120.690.01550.15420.5511.43370.505+j0.1750.212+j0.0463758.9155195
    2/0 (19)0.43640.550.01460.14760.5941.54530.453+j0.1640.168+j0.0453911.6180220
    3/0 (19)0.34450.430.01340.14440.6431.66670.409+j0.1520.133+j0.0434082.1200250
    4/0 (19)0.27430.340.01250.13780.6961.80770.372+j0.1410.106+j0.0424277.4235285
    250 (37)0.23200.290.01130.13120.7641.98160.345+j0.1280.090+j0.0404522.4
    350 (37)0.16570.210.01010.12470.8632.24080.304+j0.1120.065+j0.0384888.2310375
    500 (37)0.11610.150.00880.11810.9882.56230.268+j0.0970.046+j0.0365342.8375455
    750 (61)0.07740.100.00730.11481.1683.03150.231+j0.0790.032+j0.0356010.5470560
    1000 (61)0.05810.080.00670.10831.3093.40220.209+j0.0690.025+j0.0336539.6540645
    * Calculations are based on three cables triplexed / tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Figure 7 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
    ‡ Ampacities are based on Figure 1 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)

    Revision: 3.0.00C