SPEC 81122

15kV AL 100% EPR (EAM) One-Third Neutral LLDPE Primary UD

Single Conductor, 175 Mils Ethylene Propylene Rubber (EPR) / Ethylene Alkene Copolymer (EAM), 100% Insulation Level, One-third Concentric Neutral, Linear Low Density Polyethylene (LLDPE) Jacket. Silicone Free

...

Construction:

  1. Conductor:Moisture blocked class B compressed Aluminum ASTM B231 1350 ¾ hard H16/H26 ( Non Moisture Blocked Optional )
  2. Conductor Shield:Conventional Semi-conducting cross-linked copolymer; Supersmooth conductor shield optional; A conductor tape is used for cable size larger than or equal to 1500 Kcmil
  3. Insulation:175 Mils Ethylene Propylene Rubber (EPR) / Ethylene Alkene Copolymer (EAM) 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Neutral:Helically applied soft drawn bare copper one-third concentric neutral
  6. Overall Jacket:Linear Low Density Polyethylene (LLDPE) Jacket, black with red extruded stripes; PowerGlide® LLDPE jacket optional

Applications and Features:

Southwire's 15kV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, sunlight, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation. 140°C for emergency overload, and 250°C for short circuit conditions. Jacket types available that can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.

Specifications:

  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B609 Standard Specification for Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
  • ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5 - 46kV
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • UL 1072 Listed as MV 90 When Specified
  • Optional CSA: CSA 68.5 and -40C optional marking available upon request
  • Sample Print Legend:

    SOUTHWIRE HI-DRI(R) [CONDUCTOR SIZE] [AWG or KCMIL] AL 15000 VOLTS EPR INSULATION 175 MILS -- (NESC) -- SOUTHWIRE {MMM} {YYYY} NON-CONDUCTING JACKET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension*
    AWG/KcmilinchinchmilinchNo. x AWGΩ/1000ftmilinchlb/1000ftinchlb
    TBA2 (1)0.2580.6451750.7256x140.438500.95343511.4398
    6294592 (7)0.2830.6701750.7506x140.438500.97845911.7398
    TBA1 (1)0.2890.6761750.7566x140.438500.98446811.8502
    TBA1 (19)0.3220.7091750.7896x140.438501.01749712.2502
    TBA1/0 (1)0.3250.7121750.7926x140.438501.02050712.2634
    TBA1/0 (19)0.3520.7391750.8196x140.438501.04753112.6634
    TBA2/0 (19)0.3950.7821750.8627x140.376501.09059313.1799
    TBA3/0 (19)0.4430.8301750.9109x140.292501.13867513.71007
    6294664/0 (19)0.4980.8851750.96511x140.239501.19377114.31270
    TBA250 (37)0.5580.9541751.03413x140.202501.26288115.11500
    TBA350 (37)0.6611.0571751.15718x140.146501.385111916.62100
    622454500 (37)0.7891.1851751.28516x120.104501.545146118.53000
    622583750 (61)0.9681.3731751.47324x120.069801.793204021.54500
    6218281000 (61)1.1171.5221751.62220x100.052801.986258323.86000
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftA/1000ftW/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    2 (1)0.2660.3340.0440.0490.19834.3040.654+j0.2300.335+j0.0492025.6120150
    2 (7)0.2660.3340.0410.0470.21036.3150.653+j0.2290.335+j0.0472025.6120150
    1 (1)0.2110.2650.0410.0470.21236.7960.584+j0.2280.266+j0.0472025.6140175
    1 (19)0.2110.2650.0380.0460.22839.4320.583+j0.2270.266+j0.0462025.6140175
    1/0 (1)0.1680.2110.0380.0460.22939.6710.529+j0.2270.212+j0.0452025.6155195
    1/0 (19)0.1680.2110.0360.0440.24141.8170.529+j0.2270.212+j0.0442025.6155195
    2/0 (19)0.1330.1670.0330.0430.26145.2200.461+j0.1870.168+j0.0432363.3180225
    3/0 (19)0.1050.1320.0310.0420.28349.0010.383+j0.1350.133+j0.0413038.5200255
    4/0 (19)0.08360.1050.0280.0400.30853.3160.322+j0.1030.107+j0.0403713.7235285
    250 (37)0.07070.0890.0260.0390.33958.7080.279+j0.0820.091+j0.0384388.9
    350 (37)0.05050.0640.0220.0370.38566.7270.208+j0.0550.066+j0.0376076.9310375
    500 (37)0.03540.0450.0200.0360.44376.6570.151+j0.0400.048+j0.0358582.3370450
    750 (61)0.02360.0300.0160.0350.52691.1950.102+j0.0280.035+j0.03312873.4460545
    1000 (61)0.01770.0230.0150.0340.593102.6920.077+j0.0240.029+j0.03117052.9520620
    * Calculations are based on three cables triplexed / concentric shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Figure 7 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
    ‡ Ampacities are based on Figure 1 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension*
    AWG/KcmilmmmmmmmmNo. x AWGΩ/kmmmmmkg/kmmmnewton
    TBA2 (1)6.5516.384.4418.426x141.441.2724.21647289.561771
    6294592 (7)7.1917.024.4419.056x141.441.2724.84683297.181771
    TBA1 (1)7.3417.174.4419.206x141.441.2724.99696299.722234
    TBA1 (19)8.1818.014.4420.046x141.441.2725.83740309.882234
    TBA1/0 (1)8.2518.084.4420.126x141.441.2725.91754309.882821
    TBA1/0 (19)8.9418.774.4420.806x141.441.2726.59790320.042821
    TBA2/0 (19)10.0319.864.4421.897x141.231.2727.69882332.743556
    TBA3/0 (19)11.2521.084.4423.119x140.961.2728.911005347.984481
    6294664/0 (19)12.6522.484.4424.5111x140.781.2730.301147363.225652
    TBA250 (37)14.1724.234.4426.2613x140.661.2732.051311383.546675
    TBA350 (37)16.7926.854.4429.3918x140.481.2735.181665421.649345
    622454500 (37)20.0430.104.4432.6416x120.341.2739.242174469.9013350
    622583750 (61)24.5934.874.4437.4124x120.232.0345.543036546.1020025
    6218281000 (61)28.3738.664.4441.2020x100.172.0350.443844604.5226700
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilΩ/kmΩ/kmMΩ*kmΩ/kmA/kmW/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2 (1)0.87271.100.01340.16080.650112.54590.654+j0.2300.335+j0.0492025.6120150
    2 (7)0.87271.100.01250.15420.689119.14370.653+j0.2290.335+j0.0472025.6120150
    1 (1)0.69230.870.01250.15420.696120.72180.584+j0.2280.266+j0.0472025.6140175
    1 (19)0.69230.870.01160.15090.748129.37010.583+j0.2270.266+j0.0462025.6140175
    1/0 (1)0.55120.690.01160.15090.751130.15420.529+j0.2270.212+j0.0452025.6155195
    1/0 (19)0.55120.690.01100.14440.791137.19490.529+j0.2270.212+j0.0442025.6155195
    2/0 (19)0.43640.550.01010.14110.856148.35960.461+j0.1870.168+j0.0432363.3180225
    3/0 (19)0.34450.430.00940.13780.928160.76440.383+j0.1350.133+j0.0413038.5200255
    4/0 (19)0.27430.340.00850.13121.010174.92130.322+j0.1030.107+j0.0403713.7235285
    250 (37)0.23200.290.00790.12801.112192.61150.279+j0.0820.091+j0.0384388.9
    350 (37)0.16570.210.00670.12141.263218.92060.208+j0.0550.066+j0.0376076.9310375
    500 (37)0.11610.150.00610.11811.453251.49930.151+j0.0400.048+j0.0358582.3370450
    750 (61)0.07740.100.00490.11481.726299.19620.102+j0.0280.035+j0.03312873.4460545
    1000 (61)0.05810.080.00460.11151.946336.91600.077+j0.0240.029+j0.03117052.9520620
    * Calculations are based on three cables triplexed / concentric shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Figure 7 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
    ‡ Ampacities are based on Figure 1 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)

    Revision: 3.0.00C