SPEC 81124

15kV CU 100% EPR One-Third Neutral LLDPE Primary UD

Single Conductor, 175 Mils Ethylene Propylene Rubber (EPR), 100% Insulation Level, One-third Concentric Neutral, Linear Low Density Polyethylene (LLDPE) Jacket. Silicone Free

...

Construction:

  1. Conductor:Class B compressed stranded soft drawn bare copper per ASTM B3 and ASTM B8; (Conductor moisture block optional and tinned copper per ASTM B33 optional)
  2. Conductor Shield:Conventional Semi-conducting cross-linked copolymer. A conductor tape is used for cable size larger than or equal to 1500 Kcmil
  3. Insulation:175 Mils Ethylene Propylene Rubber (EPR) 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Neutral:Helically applied soft drawn bare copper one-third concentric neutral
  6. Overall Jacket:Linear Low Density Polyethylene (LLDPE) Jacket, Black (red extruded stripes optional); PowerGlide® LLDPE jacket optional

Applications and Features:

Southwire's 15kV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, sunlight, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation. 140°C for emergency overload, and 250°C for short circuit conditions. Jacket types available that can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5 - 46kV
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • UL 1072 Listed as MV 90 When Specified
  • Optional CSA: CSA 68.5 and -40C optional marking available upon request
  • Sample Print Legend:

    SOUTHWIRE HI-DRI(R) [CONDUCTOR SIZE] [AWG or KCMIL] CU 15000 VOLTS EPR INSULATION 175 MILS -- (NESC) -- SOUTHWIRE {MMM} {YYYY} NON-CONDUCTING JACKET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension*
    AWG/KcmilinchinchmilinchNo. x AWGΩ/1000ftmilinchlb/1000ftinchlb
    TBA2 (1)0.2580.6451750.7256x140.438500.95357511.4531
    6280702 (7)0.2830.6701750.7506x140.438500.97860211.7531
    TBA2 (7)0.2830.6701750.7506x140.438500.97860211.7531
    TBA1 (1)0.2890.6761750.7567x140.376500.98465511.8670
    TBA1 (19)0.3220.7091750.7897x140.376501.01768812.2670
    TBA1/0 (1)0.3250.7121750.7929x140.292501.02076212.2845
    6280741/0 (19)0.3620.7491750.8299x140.292501.05780212.7845
    TBA1/0 (19)0.3620.7491750.8299x140.292501.05780212.7845
    6280772/0 (19)0.4050.7921750.87211x140.239501.10093413.21065
    TBA2/0 (19)0.4050.7921750.87211x140.239501.10093413.21065
    TBA3/0 (19)0.4560.8431750.92314x140.188501.151110713.81342
    6233524/0 (19)0.5120.8991750.97918x140.146501.207132114.51693
    TBA4/0 (19)0.5120.8991750.97918x140.146501.207132114.51693
    TBA250 (37)0.5580.9541751.03421x140.125501.262150715.12000
    628080350 (37)0.6611.0571751.15718x120.092501.417201817.02800
    619989500 (37)0.7891.1851751.28526x120.061501.551272119.14000
    621464^500 (37)0.7891.1851751.28517x100.061501.589277219.14000
    628083500 (37)0.7891.1851751.28517x100.061501.589277219.14000
    628084750 (61)0.9681.3731751.47325x100.041801.862401422.36000
    6235071000 (61)1.1171.5221751.62226x90.031802.039517524.58000
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    ^ Solid Black Jacket
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftA/1000ftW/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    2 (1)0.1620.2030.0440.0490.19834.3040.523+j0.2300.204+j0.0492025.6160195
    2 (7)0.1620.2030.0410.0470.21036.3150.522+j0.2290.204+j0.0472025.6160195
    2 (7)0.1620.2030.0410.0470.21036.3150.522+j0.2290.204+j0.0472025.6160195
    1 (1)0.1290.1610.0410.0470.21236.7960.456+j0.1890.162+j0.0472363.3180220
    1 (19)0.1290.1610.0380.0460.22839.4320.456+j0.1880.162+j0.0462363.3180220
    1/0 (1)0.1020.1280.0380.0460.22939.6710.381+j0.1370.129+j0.0453038.5200250
    1/0 (19)0.1020.1280.0350.0440.24642.6100.380+j0.1360.129+j0.0443038.5200250
    1/0 (19)0.1020.1280.0350.0440.24642.6100.380+j0.1360.129+j0.0443038.5200250
    2/0 (19)0.0810.1010.0330.0430.26646.0090.319+j0.1040.103+j0.0423713.7230285
    2/0 (19)0.0810.1010.0330.0430.26646.0090.319+j0.1040.103+j0.0423713.7230285
    3/0 (19)0.06420.0810.0300.0410.28950.0220.260+j0.0770.083+j0.0414726.5260325
    4/0 (19)0.0510.0640.0280.0400.31454.4110.208+j0.0560.067+j0.0396076.9300365
    4/0 (19)0.0510.0640.0280.0400.31454.4110.208+j0.0560.067+j0.0396076.9300365
    250 (37)0.04310.0540.0260.0390.33958.7080.180+j0.0470.057+j0.0387089.8
    350 (37)0.03080.0390.0220.0380.38566.7270.134+j0.0370.043+j0.0379655.1390475
    500 (37)0.02160.0280.0200.0360.44376.6570.091+j0.0290.034+j0.03414494.9455555
    500 (37)0.02160.0280.0200.0360.44376.6570.091+j0.0290.034+j0.03414494.9455555
    500 (37)0.02160.0280.0200.0360.44376.6570.091+j0.0290.034+j0.03414494.9455555
    750 (61)0.01440.0190.0160.0350.52691.1950.062+j0.0230.026+j0.03121505.0545650
    1000 (61)0.01080.0150.0150.0340.593102.6920.047+j0.0210.023+j0.02828479.8
    * Calculations are based on three cables triplexed / concentric shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Figure 7 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
    ‡ Ampacities are based on Figure 1 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension*
    AWG/KcmilmmmmmmmmNo. x AWGΩ/kmmmmmkg/kmmmnewton
    TBA2 (1)6.5516.384.4418.426x141.441.2724.21856289.562363
    6280702 (7)7.1917.024.4419.056x141.441.2724.84896297.182363
    TBA2 (7)7.1917.024.4419.056x141.441.2724.84896297.182363
    TBA1 (1)7.3417.174.4419.207x141.231.2724.99975299.722982
    TBA1 (19)8.1818.014.4420.047x141.231.2725.831024309.882982
    TBA1/0 (1)8.2518.084.4420.129x140.961.2725.911134309.883760
    6280741/0 (19)9.1919.024.4421.069x140.961.2726.851194322.583760
    TBA1/0 (19)9.1919.024.4421.069x140.961.2726.851194322.583760
    6280772/0 (19)10.2920.124.4422.1511x140.781.2727.941390335.284739
    TBA2/0 (19)10.2920.124.4422.1511x140.781.2727.941390335.284739
    TBA3/0 (19)11.5821.414.4423.4414x140.621.2729.241647350.525972
    6233524/0 (19)13.0022.834.4424.8718x140.481.2730.661966368.307534
    TBA4/0 (19)13.0022.834.4424.8718x140.481.2730.661966368.307534
    TBA250 (37)14.1724.234.4426.2621x140.411.2732.052243383.548900
    628080350 (37)16.7926.854.4429.3918x120.301.2735.993003431.8012460
    619989500 (37)20.0430.104.4432.6426x120.201.2739.404049485.1417800
    621464^500 (37)20.0430.104.4432.6417x100.201.2740.364125485.1417800
    628083500 (37)20.0430.104.4432.6417x100.201.2740.364125485.1417800
    628084750 (61)24.5934.874.4437.4125x100.132.0347.295973566.4226700
    6235071000 (61)28.3738.664.4441.2026x90.102.0351.797701622.3035600
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    ^ Solid Black Jacket
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilΩ/kmΩ/kmMΩ*kmΩ/kmA/kmW/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2 (1)0.53150.670.01340.16080.650112.54590.523+j0.2300.204+j0.0492025.6160195
    2 (7)0.53150.670.01250.15420.689119.14370.522+j0.2290.204+j0.0472025.6160195
    2 (7)0.53150.670.01250.15420.689119.14370.522+j0.2290.204+j0.0472025.6160195
    1 (1)0.42320.530.01250.15420.696120.72180.456+j0.1890.162+j0.0472363.3180220
    1 (19)0.42320.530.01160.15090.748129.37010.456+j0.1880.162+j0.0462363.3180220
    1/0 (1)0.33460.420.01160.15090.751130.15420.381+j0.1370.129+j0.0453038.5200250
    1/0 (19)0.33460.420.01070.14440.807139.79660.380+j0.1360.129+j0.0443038.5200250
    1/0 (19)0.33460.420.01070.14440.807139.79660.380+j0.1360.129+j0.0443038.5200250
    2/0 (19)0.26570.330.01010.14110.873150.94820.319+j0.1040.103+j0.0423713.7230285
    2/0 (19)0.26570.330.01010.14110.873150.94820.319+j0.1040.103+j0.0423713.7230285
    3/0 (19)0.21060.270.00910.13450.948164.11420.260+j0.0770.083+j0.0414726.5260325
    4/0 (19)0.16730.210.00850.13121.030178.51380.208+j0.0560.067+j0.0396076.9300365
    4/0 (19)0.16730.210.00850.13121.030178.51380.208+j0.0560.067+j0.0396076.9300365
    250 (37)0.14140.180.00790.12801.112192.61150.180+j0.0470.057+j0.0387089.8
    350 (37)0.10100.130.00670.12471.263218.92060.134+j0.0370.043+j0.0379655.1390475
    500 (37)0.07090.090.00610.11811.453251.49930.091+j0.0290.034+j0.03414494.9455555
    500 (37)0.07090.090.00610.11811.453251.49930.091+j0.0290.034+j0.03414494.9455555
    500 (37)0.07090.090.00610.11811.453251.49930.091+j0.0290.034+j0.03414494.9455555
    750 (61)0.04720.060.00490.11481.726299.19620.062+j0.0230.026+j0.03121505.0545650
    1000 (61)0.03540.050.00460.11151.946336.91600.047+j0.0210.023+j0.02828479.8
    * Calculations are based on three cables triplexed / concentric shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Figure 7 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
    ‡ Ampacities are based on Figure 1 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)

    Revision: 3.0.00C