SPEC 81141

25kV AL 100% TRXLPE Full Neutral LLDPE Primary UD

Single Conductor, 260 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Full Concentric Neutral, Linear Low Density Polyethylene (LLDPE) Jacket. Silicone Free

...

Construction:

  1. Conductor:Moisture blocked class B compressed Aluminum ASTM B231 1350 ¾ hard H16/H26 ( Non Moisture Blocked Optional )
  2. Conductor Shield:Conventional Semi-conducting cross-linked copolymer; Supersmooth conductor shield optional; A conductor tape is used for cable size larger than or equal to 1500 Kcmil
  3. Insulation:260 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Neutral:Helically applied soft drawn bare copper full concentric neutral
  6. Overall Jacket:Linear Low Density Polyethylene (LLDPE) Jacket, black with red extruded stripes; PowerGlide® LLDPE jacket optional

Applications and Features:

Southwire's 25kV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, sunlight, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation. 130°C for emergency overload, and 250°C for short circuit conditions. Jacket types available that can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.

Specifications:

  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B609 Standard Specification for Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
  • ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5 - 46kV
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • UL 1072 Listed as MV 90 When Specified
  • Optional CSA: CSA 68.5 and -40C optional marking available upon request
  • Sample Print Legend:

    SOUTHWIRE HI-DRI(R) [CONDUCTOR SIZE] [AWG or KCMIL] AL 25000 VOLTS TRXLPE INSULATION 260 MILS -- (NESC) -- SOUTHWIRE {MMM} {YYYY} NON-CONDUCTING JACKET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension*
    AWG/KcmilinchinchmilinchNo. x AWGΩ/1000ftmilinchlb/1000ftinchlb
    6147871 (1)0.2890.8462600.92613x140.202501.15462813.8502
    619983§1 (1)0.2890.8462600.92613x140.202501.15462813.8502
    6117331 (19)0.3220.8792600.95913x140.202501.18765814.2502
    TBA1/0 (1)0.3250.8822600.96216x140.164501.19070114.3634
    586925^1/0 (19)0.3520.9092600.98916x140.164501.21772714.6634
    6103081/0 (19)0.3520.9092600.98916x140.164501.21772714.6634
    6279282/0 (19)0.3950.9522601.03213x120.128501.29787615.5799
    TBA3/0 (19)0.4431.0002601.08016x120.104501.34097416.11007
    6141254/0 (19)0.4981.0552601.15513x100.080501.464121017.51270
    TBA250 (37)0.5581.1242601.22416x100.065501.528137418.31500
    TBA350 (37)0.6611.2272601.32716x90.052501.656168819.92100
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    ^ SuperSmooth conductor shield
    § Black jacket. CSA Listed
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftA/1000ftW/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    1 (1)0.2110.2650.0650.0510.2220.9630.456+j0.0930.267+j0.0504758.3140175
    1 (1)0.2110.2650.0650.0510.2220.9630.456+j0.0930.267+j0.0504758.3140175
    1 (19)0.2110.2650.0610.0490.2371.0260.456+j0.0920.267+j0.0494758.3140175
    1/0 (1)0.1680.2110.0610.0490.2381.0310.371+j0.0740.213+j0.0495856.3155195
    1/0 (19)0.1680.2110.0580.0480.2501.0820.371+j0.0730.213+j0.0485856.3155195
    1/0 (19)0.1680.2110.0580.0480.2501.0820.371+j0.0730.213+j0.0485856.3155195
    2/0 (19)0.1330.1670.0540.0470.2681.1620.296+j0.0590.170+j0.0467560.0180225
    3/0 (19)0.1050.1320.0500.0450.2891.2510.238+j0.0480.136+j0.0449304.6205250
    4/0 (19)0.08360.1050.0460.0450.3121.3530.186+j0.0420.110+j0.04312017.3235285
    250 (37)0.07070.0890.0420.0430.3421.4790.156+j0.0360.094+j0.04114790.5
    350 (37)0.05050.0640.0380.0410.3851.6660.117+j0.0320.070+j0.03818652.0305370
    * Calculations are based on three cables triplexed / concentric shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Figure 7 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
    ‡ Ampacities are based on Figure 1 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension*
    AWG/KcmilmmmmmmmmNo. x AWGΩ/kmmmmmkg/kmmmnewton
    6147871 (1)7.3421.496.6023.5213x140.661.2729.31935350.522234
    619983§1 (1)7.3421.496.6023.5213x140.661.2729.31935350.522234
    6117331 (19)8.1822.336.6024.3613x140.661.2730.15979360.682234
    TBA1/0 (1)8.2522.406.6024.4316x140.541.2730.231043363.222821
    586925^1/0 (19)8.9423.096.6025.1216x140.541.2730.911082370.842821
    6103081/0 (19)8.9423.096.6025.1216x140.541.2730.911082370.842821
    6279282/0 (19)10.0324.186.6026.2113x120.421.2732.941304393.703556
    TBA3/0 (19)11.2525.406.6027.4316x120.341.2734.041449408.944481
    6141254/0 (19)12.6526.806.6029.3413x100.261.2737.191801444.505652
    TBA250 (37)14.1728.556.6031.0916x100.211.2738.812045464.826675
    TBA350 (37)16.7931.176.6033.7116x90.171.2742.062512505.469345
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    ^ SuperSmooth conductor shield
    § Black jacket. CSA Listed
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilΩ/kmΩ/kmMΩ*kmΩ/kmA/kmW/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    1 (1)0.69230.870.01980.16730.7283.15940.456+j0.0930.267+j0.0504758.3140175
    1 (1)0.69230.870.01980.16730.7283.15940.456+j0.0930.267+j0.0504758.3140175
    1 (19)0.69230.870.01860.16080.7783.36610.456+j0.0920.267+j0.0494758.3140175
    1/0 (1)0.55120.690.01860.16080.7813.38250.371+j0.0740.213+j0.0495856.3155195
    1/0 (19)0.55120.690.01770.15750.8203.54990.371+j0.0730.213+j0.0485856.3155195
    1/0 (19)0.55120.690.01770.15750.8203.54990.371+j0.0730.213+j0.0485856.3155195
    2/0 (19)0.43640.550.01650.15420.8793.81230.296+j0.0590.170+j0.0467560.0180225
    3/0 (19)0.34450.430.01520.14760.9484.10430.238+j0.0480.136+j0.0449304.6205250
    4/0 (19)0.27430.340.01400.14761.0244.43900.186+j0.0420.110+j0.04312017.3235285
    250 (37)0.23200.290.01280.14111.1224.85240.156+j0.0360.094+j0.04114790.5
    350 (37)0.16570.210.01160.13451.2635.46590.117+j0.0320.070+j0.03818652.0305370
    * Calculations are based on three cables triplexed / concentric shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Figure 7 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
    ‡ Ampacities are based on Figure 1 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)

    Revision: 3.0.00C