SPEC 81152

25kV AL 133% TRXLPE One-Third Neutral LLDPE Primary UD

Single Conductor, 320 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, One-third Concentric Neutral, Linear Low Density Polyethylene (LLDPE) Jacket. Silicone Free

...

Construction:

  1. Conductor:Moisture blocked class B compressed Aluminum ASTM B231 1350 ¾ hard H16/H26 ( Non Moisture Blocked Optional )
  2. Conductor Shield:Conventional Semi-conducting cross-linked copolymer; Supersmooth conductor shield optional; A conductor tape is used for cable size larger than or equal to 1500 Kcmil
  3. Insulation:320 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Neutral:Helically applied soft drawn bare copper one-third concentric neutral
  6. Overall Jacket:Linear Low Density Polyethylene (LLDPE) Jacket, black with red extruded stripes; PowerGlide® LLDPE jacket optional

Applications and Features:

Southwire's 25kV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, sunlight, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation. 130°C for emergency overload, and 250°C for short circuit conditions. Jacket types available that can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.

Specifications:

  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B609 Standard Specification for Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
  • ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5 - 46kV
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • UL 1072 Listed as MV 90 When Specified
  • Optional CSA: CSA 68.5 and -40C optional marking available upon request
  • Sample Print Legend:

    SOUTHWIRE HI-DRI(R) [CONDUCTOR SIZE] [AWG or KCMIL] AL 25000 VOLTS TRXLPE INSULATION 320 MILS -- (NESC) -- SOUTHWIRE {MMM} {YYYY} NON-CONDUCTING JACKET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension*
    AWG/KcmilinchinchmilinchNo. x AWGΩ/1000ftmilinchlb/1000ftinchlb
    TBA1 (1)0.2890.9663201.0466x140.438501.27464315.3502
    TBA1 (19)0.3220.9993201.0796x140.438501.30767615.7502
    TBA1/0 (1)0.3251.0023201.0826x140.438501.31068615.7634
    TBA1/0 (19)0.3521.0293201.1096x140.438501.33771316.0634
    TBA2/0 (19)0.3951.0723201.1727x140.376501.40080116.8799
    TBA3/0 (19)0.4431.1203201.2209x140.292501.44889017.41007
    TBA4/0 (19)0.4981.1753201.27511x140.239501.50399318.01270
    TBA250 (37)0.5581.2443201.34413x140.202501.572111218.91500
    TBA350 (37)0.6611.3473201.44718x140.146801.735140620.82100
    TBA500 (37)0.7891.4753201.57516x120.104801.895177622.73000
    TBA750 (61)0.9681.6633201.79324x120.069802.113236525.44500
    TBA1000 (61)1.1171.8123201.94220x100.052802.306293727.76000
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftA/1000ftW/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    1 (1)0.2110.2650.0740.0530.1950.8460.578+j0.2380.266+j0.0532196.1140175
    1 (19)0.2110.2650.0700.0510.2070.8970.578+j0.2360.266+j0.0512196.1140175
    1/0 (1)0.1680.2110.0690.0510.2080.9020.524+j0.2360.212+j0.0512196.1155195
    1/0 (19)0.1680.2110.0660.0500.2180.9440.523+j0.2350.212+j0.0502196.1155195
    2/0 (19)0.1330.1670.0620.0490.2331.0110.457+j0.1960.168+j0.0492562.1180225
    3/0 (19)0.1050.1320.0580.0470.2501.0840.381+j0.1430.133+j0.0473294.2200255
    4/0 (19)0.08360.1050.0540.0450.2701.1670.321+j0.1110.106+j0.0454026.2235285
    250 (37)0.07070.0890.0490.0440.2941.2710.278+j0.0890.091+j0.0434758.3
    350 (37)0.05050.0640.0440.0420.3291.4250.207+j0.0610.066+j0.0426588.4310375
    500 (37)0.03540.0450.0390.0410.3731.6140.151+j0.0450.048+j0.0409304.6370450
    750 (61)0.02360.0300.0330.0380.4371.8900.102+j0.0320.035+j0.03713956.9460545
    1000 (61)0.01770.0230.0300.0370.4872.1080.077+j0.0290.029+j0.03418488.1520620
    * Calculations are based on three cables triplexed / concentric shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Figure 7 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
    ‡ Ampacities are based on Figure 1 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension*
    AWG/KcmilmmmmmmmmNo. x AWGΩ/kmmmmmkg/kmmmnewton
    TBA1 (1)7.3424.548.1326.576x141.441.2732.36957388.622234
    TBA1 (19)8.1825.378.1327.416x141.441.2733.201006398.782234
    TBA1/0 (1)8.2525.458.1327.486x141.441.2733.271021398.782821
    TBA1/0 (19)8.9426.148.1328.176x141.441.2733.961061406.402821
    TBA2/0 (19)10.0327.238.1329.777x141.231.2735.561192426.723556
    TBA3/0 (19)11.2528.458.1330.999x140.961.2736.781324441.964481
    TBA4/0 (19)12.6529.858.1332.3911x140.781.2738.181478457.205652
    TBA250 (37)14.1731.608.1334.1413x140.661.2739.931655480.066675
    TBA350 (37)16.7934.218.1336.7518x140.482.0344.072092528.329345
    TBA500 (37)20.0437.478.1340.0016x120.342.0348.132643576.5813350
    TBA750 (61)24.5942.248.1345.5424x120.232.0353.673520645.1620025
    TBA1000 (61)28.3746.028.1349.3320x100.172.0358.574371703.5826700
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilΩ/kmΩ/kmMΩ*kmΩ/kmA/kmW/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    1 (1)0.69230.870.02260.17390.6402.77560.578+j0.2380.266+j0.0532196.1140175
    1 (19)0.69230.870.02130.16730.6792.94290.578+j0.2360.266+j0.0512196.1140175
    1/0 (1)0.55120.690.02100.16730.6822.95930.524+j0.2360.212+j0.0512196.1155195
    1/0 (19)0.55120.690.02010.16400.7153.09710.523+j0.2350.212+j0.0502196.1155195
    2/0 (19)0.43640.550.01890.16080.7643.31690.457+j0.1960.168+j0.0492562.1180225
    3/0 (19)0.34450.430.01770.15420.8203.55640.381+j0.1430.133+j0.0473294.2200255
    4/0 (19)0.27430.340.01650.14760.8863.82870.321+j0.1110.106+j0.0454026.2235285
    250 (37)0.23200.290.01490.14440.9654.16990.278+j0.0890.091+j0.0434758.3
    350 (37)0.16570.210.01340.13781.0794.67520.207+j0.0610.066+j0.0426588.4310375
    500 (37)0.11610.150.01190.13451.2245.29530.151+j0.0450.048+j0.0409304.6370450
    750 (61)0.07740.100.01010.12471.4346.20080.102+j0.0320.035+j0.03713956.9460545
    1000 (61)0.05810.080.00910.12141.5986.91600.077+j0.0290.029+j0.03418488.1520620
    * Calculations are based on three cables triplexed / concentric shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Figure 7 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
    ‡ Ampacities are based on Figure 1 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)

    Revision: 3.0.00C