SPEC 83230

Triplex XLPE Service Drop. ACSR Neutral - Messenger

Aluminum Conductors With Crosslinked Polyethylene Insulation.

...

Construction:

  1. Conductor:Conductors are stranded, compressed 1350-H19 aluminum
  2. Insulation:Cross Linked Polyethylene (XLPE)
  3. Messenger:ACSR Neutral

Applications and Features:

Primarily used for 120 volt overhead service applications such as street lighting, outdoor lighting, and temporary service for construction. To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures not to exceed 90°C for crosslinked polyethylene (XLP) insulated conductors.

Specifications:

  • ASTM B230 Aluminum, 1350-H19 Wire for Electrical Purposes
  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B400 Standard Specification for Compact Round Concentric-Lay-Stranded, Aluminum 1350 Conductors
  • ASTM B901 Standard Specification for Compressed Round Stranded Aluminum Conductors Using Single Input Wire Construction. (The number of strands for both phase and neutral may differ)
  • ICEA S-76-474 Standard for Neutral-Supported Power Cable Assemblies with Weather-Resistant Extruded Insulation Rated 600V
  • Table 1 – Weights and Measurements
    Stock NumberCode WordPhase Cond. SizePhase StrandDia. Over Phase ConductorPhase Insul. ThicknessDia. Over Phase InsulationNeutral Cond. SizeApprox. ODApprox. Weight
    AWG/KcmilNo.inchmilinchAWG/Kcmilinchlb/1000ft
    104802Paludina610.162450.25260.544109
    104810Voluta670.178450.26860.579114
    TBAWhelk410.204450.29440.636164
    104836Periwinkle470.225450.31540.68172
    104844Conch270.283450.37320.806262
    TBACenia1/090.352600.4721/01.02414
    104851Neritina1/070.357600.4771/01.03420
    104885Triton2/0110.395600.5152/01.112512
    104877Runcina2/070.402600.5222/01.128521
    104893Mursia3/0170.443600.5633/01.216635
    104901Zuzara4/0180.498600.6184/01.335789
    245845Limpet336.4190.645800.805336.41.7391167
    All dimensions are nominal and subject to normal manufacturing tolerances
    1. The actual number of strands may differ for single input wire per ASTM B901
    Table 2 – Electrical and Engineering Data
    Code WordPhase Cond. SizeNeutral Rated Breaking StrengthDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzGMRAllowable Ampacity In Air 90°C
    AWG/KcmillbΩ/1000ftΩ/1000ftΩ/1000ftftAmp
    Paludina611900.65230.83630.03180.005385
    Voluta611900.66530.8530.03270.005485
    Whelk418600.410.52580.03010.0066115
    Periwinkle418600.41830.53630.0310.0068115
    Conch228500.26310.33730.02960.0086150
    Cenia1/043800.16530.2120.02990.0107205
    Neritina1/043800.16530.2120.02990.0108205
    Triton2/053100.13120.16820.0290.0121235
    Runcina2/053100.13120.16820.02930.0122235
    Mursia3/066200.1040.13350.0280.0139275
    Zuzara4/083500.08250.10590.02730.0157315
    Limpet336.486800.05190.06670.02740.0204420
    Notes:
    1. DC resistances include a 1% length factor for plexing.
    2. Inductive reactance assumes the neutral is carrying current.
    3. Phase conductors assumed to be reverse lay stranded, compressed construction.
    4. Phase spacing assumes cables are touching.
    5. Resistances shown are for the phase conductor only.
    6. Ampacity based on conductor temperature of 90°; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun.

    Neutral Code Word

    SizeCode WordOD (inches)
    #6Turkey0.198
    #4Swan0.250
    #2Sparrow0.316
    1/0Raven0.398
    2/0Quail0.447
    3/0Pigeon0.502
    4/0Penguin0.684
    336.4Merlin0.563

    Revision: 1.000.000

    Updated On: Dec. 11, 2023, 9:29 p.m. UTC