SPEC 85013

Multi-Conductor CU 600 V PE/PVC Insulation PVC Jacket Control Cable Color Method 1 Table 1

Control Cable 600 Volt Copper Conductors, Polyethylene and Polyvinyl Chloride (PE/PVC) Insulation Polyvinyl Chloride (PVC) Jacket, Control Cable Conductor Identification Method 1 Table 1. Silicone Free

...

Construction:

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  2. Insulation:20 mils Polyethylene (PE) and 10 mils Polyvinyl Chloride (PVC) for cable sizes 16 AWG and larger
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Rip Cord:Rip cord for ease of jacket removal
  6. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C for normal operation in wet and dry locations, 90°C for emergency overload, and 150°C for short circuit conditions.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA CSA marking is available upon request
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 1
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Sample Print Legend:

    Non UL Listed
    SOUTHWIRE XX AWG X/C PE/PVC CDRS 75C PVC JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V {MM/DD/YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberDiameter Over Cond.Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 90°CMin Bending RadiusAllowable Ampacity At 60°C *Allowable Ampacity 75°C *
    AWGNo.inchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    18 AWG
    606786^^1870.04625450.38235876.678.681.5--
    606787^^18120.04625450.492611366.678.682.0--
    16 AWG
    6191281640.05730450.38232814.1815.4391.5--
    6690661650.05730450.506321624.1815.4392.0--
    14 AWG
    TBA1420.07030450.34926682.6303.2881.41515
    TBA1430.07030450.37038872.6303.2881.51515
    6206461440.07030450.403511092.6303.2881.61415
    TBA1450.07030450.440641322.6303.2881.81415
    TBA1460.07030450.479771552.6303.2881.91415
    6067761470.07030450.479901712.6303.2881.91215
    TBA1480.07030450.5191021952.6303.2882.11215
    TBA1490.07030600.5881152362.6303.2882.41215
    TBA14100.07030600.6381282662.6303.2882.6911
    60677714120.07030600.6591543032.6303.2882.6911
    TBA14150.07030600.7301923712.6303.2882.9911
    TBA14190.07030600.7682434462.6303.2883.1911
    TBA14200.07030600.8082564752.6303.2883.2911
    TBA14250.07030800.9373206192.6303.2883.789
    TBA14300.07030800.9913847192.6303.2884.089
    TBA14370.07030801.0674748622.6303.2885.378
    12 AWG
    TBA1220.08730450.38441901.6602.0751.52020
    TBA1230.08730450.408611181.6602.0751.62020
    6168561240.08730450.445811481.6602.0751.81620
    6174161250.08730600.5371021881.6602.0752.01620
    6191731260.08730450.5321222141.6602.0752.11620
    6174211270.08730600.5821432471.6602.0752.31417
    577810#1270.08745600.6681432721.6602.0752.71417
    TBA1280.08730600.6071632881.6602.0752.41417
    6193821290.08730600.6511833241.6602.0752.61417
    TBA12100.08730600.7092043651.6602.0752.81012
    619993^12120.08730600.7522443961.6602.0752.91012
    61742012120.08730600.7592443961.6602.0752.91012
    TBA12150.08730600.8133055161.6602.0753.31012
    TBA12190.08730800.8963876571.6602.0753.61012
    TBA12200.08730800.9424076991.6602.0753.81012
    TBA12250.08730801.0435098601.6602.0755.2911
    TBA12300.08730801.10461110051.6602.0755.5911
    TBA12370.08730801.19175312111.6602.0756.0810
    10 AWG
    6187191020.11130450.440651181.0401.3001.73030
    6067781020.11130450.448651251.0401.3001.73030
    6067791030.11130450.467971651.0401.3001.93030
    6191171030.11130450.459971651.0401.3001.83030
    6187201040.11130600.5401302231.0401.3002.22428
    6167331040.11130600.5521302251.0401.3002.22428
    6067811050.11130600.5861622681.0401.3002.32428
    6193011040.11130600.5411302241.0401.3002.22428
    TBA1050.11130600.5811622731.0401.3002.32428
    TBA1060.11130600.6321943231.0401.3002.52428
    6191781070.11130630.6432273491.0401.3002.62124
    6189681070.11130600.6322273581.0401.3002.52124
    6191791080.11130600.6852594101.0401.3002.72124
    6067821090.11130600.7452914371.0401.3002.92124
    61918110100.11130600.8033245191.0401.3003.21517
    61891110120.11130800.8883895981.0401.3003.51517
    606783^^10120.11130800.8883896031.0401.3003.51517
    TBA10150.11130800.9644867771.0401.3003.91517
    TBA10190.11130801.0146159411.0401.3005.11517
    TBA10200.11130801.06764810011.0401.3005.31517
    TBA10250.11130801.18481012361.0401.3005.91315
    TBA10300.11130801.25497114501.0401.3006.31315
    TBA10370.11130801.355119817551.0401.3006.81214
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)
    ^ 19 Strand Class C
    ^^ 3 Stripe Insulation
    # 1000 Volts