SPEC 85013

Multi-Conductor CU 600 V PE/PVC Insulation PVC Jacket Control Cable Color Method 1 Table 1

Control Cable 600 Volt Copper Conductors, Polyethylene and Polyvinyl Chloride (PE/PVC) Insulation Polyvinyl Chloride (PVC) Jacket, Control Cable Conductor Identification Method 1 Table 1. Silicone Free

...

Construction:

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  2. Insulation:Polyethylene (PE) and Polyvinyl Chloride (PVC)
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Rip Cord:Rip cord for ease of jacket removal
  6. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C for normal operation in wet and dry locations, 90°C for emergency overload, and 150°C for short circuit conditions.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA CSA marking is available upon request
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 1
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Sample Print Legend:

    Non UL Listed
    SOUTHWIRE XX AWG X/C PE/PVC CDRS 75C PVC JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V {MM/DD/YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberDiameter Over Cond.Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 90°CMin Bending RadiusAllowable Ampacity At 60°C *Allowable Ampacity 75°C *
    AWGNo.inchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    18 AWG
    606786^^1870.04625450.38235876.678.681.5--
    606787^^18120.04625450.492611366.678.682.0--
    16 AWG
    6191281640.05730450.38232814.1815.4391.5--
    14 AWG
    TBA1420.07030450.34926682.6303.2881.41515
    TBA1430.07030450.37038872.6303.2881.51515
    6206461440.07030450.403511092.6303.2881.61415
    TBA1450.07030450.440641322.6303.2881.81415
    TBA1460.07030450.479771552.6303.2881.91415
    6067761470.07030450.479901712.6303.2881.91215
    TBA1480.07030450.5191021952.6303.2882.11215
    TBA1490.07030600.5881152362.6303.2882.41215
    TBA14100.07030600.6381282662.6303.2882.6911
    60677714120.07030600.6591543032.6303.2882.6911
    TBA14150.07030600.7301923712.6303.2882.9911
    TBA14190.07030600.7682434462.6303.2883.1911
    TBA14200.07030600.8082564752.6303.2883.2911
    TBA14250.07030800.9373206192.6303.2883.789
    TBA14300.07030800.9913847192.6303.2884.089
    TBA14370.07030801.0674748622.6303.2885.378
    12 AWG
    6187211220.08730450.38441901.6602.0751.52020
    TBA1230.08730450.408611181.6602.0751.62020
    6168561240.08730450.445811481.6602.0751.81620
    6174161250.08730600.5371021881.6602.0752.01620
    6191731260.08730450.5321222141.6602.0752.11620
    6174211270.08730600.5821432471.6602.0752.31417
    577810#1270.08745600.6681432721.6602.0752.71417
    TBA1280.08730600.6071632881.6602.0752.41417
    6193821290.08730600.6511833241.6602.0752.61417
    TBA12100.08730600.7092043651.6602.0752.81012
    619993^12120.08730600.7522443961.6602.0752.91012
    61742012120.08730600.7592443961.6602.0752.91012
    TBA12150.08730600.8133055161.6602.0753.31012
    TBA12190.08730800.8963876571.6602.0753.61012
    TBA12200.08730800.9424076991.6602.0753.81012
    TBA12250.08730801.0435098601.6602.0755.2911
    TBA12300.08730801.10461110051.6602.0755.5911
    TBA12370.08730801.19175312111.6602.0756.0810
    10 AWG
    6187191020.11130450.440651181.0401.3001.73030
    6067781020.11130450.448651251.0401.3001.73030
    6067791030.11130450.467971651.0401.3001.93030
    6191171030.11130450.459971651.0401.3001.83030
    6187201040.11130600.5401302231.0401.3002.22428
    6167331040.11130600.5521302251.0401.3002.22428
    6067811050.11130600.5861622681.0401.3002.32428
    TBA1050.11130600.5811622731.0401.3002.32428
    TBA1060.11130600.6321943231.0401.3002.52428
    6189681070.11130600.6322273581.0401.3002.52124
    6191791080.11130600.6852594101.0401.3002.72124
    6067821090.11130600.7452914371.0401.3002.92124
    61918110100.11130600.8033245191.0401.3003.21517
    61891110120.11130800.8883895981.0401.3003.51517
    TBA10150.11130800.9644867771.0401.3003.91517
    TBA10190.11130801.0146159411.0401.3005.11517
    TBA10200.11130801.06764810011.0401.3005.31517
    TBA10250.11130801.18481012361.0401.3005.91315
    TBA10300.11130801.25497114501.0401.3006.31315
    TBA10370.11130801.355119817551.0401.3006.81214
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)
    ^ 19 Strand Class C
    ^^ 3 Stripe Insulation
    # 1000 Volts

    Revision: 3.0.00C