SPEC 85022

Multi-Conductor CU 600 V XLPE XHHW-2 Shielded CPE Jacket Control Cable Color Method 1 Table 1

Control Cable 600 Volt Copper Conductors, Cross Linked Polyethylene (XLPE) Insulation XHHW-2 Shielded Chlorinated Polyethylene Chloride (CPE) Jacket, Control Cable Conductor Identification Method 1 Table 1

...

Construction:

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE) XHHW-2, 30 Mils thick for all cable sizes
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Shielding:5 mils tape shield
  6. Rip Chord:Rip chord for ease of jacket removal
  7. Overall Jacket:Chlorinated Polyethylene Chloride (CPE)

Applications and Features:

Southwire’s 600 Volt Type TC-ER control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)
  • VW-1 (Vertical-Wire) Flame Test
  • Sample Print Legend:

    SOUTHWIRE E75755 {UL} XX AWG X/C XHHW-2 CDRS SHIELDED 90C PVC JKT TYPE TC-ER 600V SUN. RES. DIRECT BURIAL {MM/DD/YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberDiameter Over Cond.Insul. ThicknessJacket ThicknessApprox. ODApprox. Weight
    AWGNo.inchmilmilinchlb/1000ft
    14 AWG
    TBA1420.07030450.34968
    TBA1430.07030450.37087
    1234561440.07030450.430135
    TBA1450.07030450.440132
    TBA1460.07030450.479155
    TBA1470.07030450.479171
    TBA1480.07030450.519195
    TBA1490.07030600.588236
    TBA14100.07030600.638266
    TBA14150.07030600.730371
    TBA14120.07030600.755383
    TBA14190.07030600.768446
    TBA14200.07030800.876475
    TBA14250.07030800.937619
    TBA14300.07030800.991719
    TBA14370.07030801.067862
    12 AWG
    TBA1220.08730450.38490
    TBA1230.08730450.408118
    TBA1240.08730450.445148
    TBA1250.08730450.487181
    TBA1260.08730450.532214
    TBA1270.08730450.532237
    TBA1280.08730600.607288
    TBA1290.08730600.651324
    TBA12100.08730600.709365
    TBA12120.08730600.732419
    TBA12150.08730600.813516
    TBA12190.08730800.896657
    TBA12200.08730800.942699
    TBA12250.08730801.043860
    TBA12300.08730801.1041005
    TBA12370.08730801.1911211
    10 AWG
    TBA1020.11130450.460154
    TBA1030.11130450.479197
    TBA1040.11130600.561210
    TBA1050.11130600.610304
    TBA1060.11130600.632323
    TBA1070.11130600.661395
    TBA1080.11130600.685410
    TBA1090.11130600.736461
    TBA10100.11130600.803519
    TBA10120.11130800.899670
    TBA10150.11130800.964777
    TBA10190.11130801.014941
    TBA10200.11130801.0671001
    TBA10250.11130801.1841236
    TBA10300.11130801.2541450
    TBA10370.11130801.3551755
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    † Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)

    Revision: 3.0.00C