SPEC 85028

Multi-Conductor CU 600 V FR-XLPE Shielded Drain Wire Thermoset CPE-TS Jacket Control Cable Color Method 1 Table 1

Control Cable 600 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation Shielded Drain Wire Thermoset Chlorinated Polyethylene Chloride (CPE-TS) Jacket, Control Cable Conductor Identification Method 1 Table 1. Silicone Free

...

Construction:

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8. Tinned copper available upon request.
  2. Insulation:Cross Linked Polyethylene (XLPE) XHHW-2, 30 Mils thick for all cable sizes
  3. DrainWire:Bare copper drain wire. Tinned copper drain wire available upon request.
  4. Filler:Polypropylene filler on cables with 5 or less conductors
  5. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  6. Shielding:5 mils tape shield
  7. Rip Cord:Rip cord for ease of jacket removal
  8. Overall Jacket:Thermoset Chlorinated Polyethylene Chloride (CPE-TS)

Applications and Features:

Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated constructions can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 1
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)
  • VW-1 (Vertical-Wire) Flame Test
  • Sample Print Legend:

    UL Listed
    SOUTHWIRE E75755 {UL} XX AWG X/C FR-XLPE CDRS SHIELDED 90C CPE JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V {MM/DD/YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Non UL Listed
    SOUTHWIRE XX AWG X/C FR-XLPE CDRS SHIELDED 90C CPE JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V {MM/DD/YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET<

    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberDiameter Over Cond.Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 90°CMin Bending RadiusAllowable Ampacity At 60°C *Allowable Ampacity 75°C *Allowable Ampacity 90°C *
    AWGNo.inchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftinchAmpAmpAmp
    14 AWG
    TBA1420.07030450.34926682.6303.2884.18151515
    TBA1430.07030450.37038872.6303.2884.44151515
    TBA1440.07030450.403511092.6303.2884.83141515
    TBA1450.07030450.440641322.6303.2885.28141515
    TBA1460.07030450.479771552.6303.2885.74141515
    TBA1470.07030450.479901712.6303.2885.74121515
    TBA1480.07030450.5191021952.6303.2886.22121515
    TBA1490.07030600.5881152362.6303.2887.05121515
    TBA14100.07030600.6381282662.6303.2887.6591112
    TBA14120.07030600.6591543032.6303.2887.9091112
    TBA14150.07030600.7301923712.6303.2888.7691112
    TBA14190.07030600.7682434462.6303.2889.2191112
    TBA14200.07030600.8082564752.6303.2889.6991112
    TBA14250.07030800.9373206192.6303.28811.248911
    TBA14300.07030800.9913847192.6303.28811.898911
    TBA14370.07030801.0674748622.6303.28812.807810
    12 AWG
    TBA1220.08730450.38441901.6602.0754.61202020
    TBA1230.08730450.408611181.6602.0754.9202020
    TBA1240.08730450.445811481.6602.0755.34162020
    TBA1250.08730450.4871021811.6602.0755.84162020
    TBA1260.08730450.5321222141.6602.0756.38162020
    TBA1270.08730450.5321432371.6602.0756.38141720
    TBA1280.08730600.6071632881.6602.0757.28141720
    TBA1290.08730600.6511833241.6602.0757.81141720
    TBA12100.08730600.7092043651.6602.0758.50101215
    TBA12120.08730600.7322444191.6602.0758.78101215
    TBA12150.08730600.8133055161.6602.0759.75101215
    TBA12190.08730800.8963876571.6602.07510.75101215
    TBA12200.08730800.9424076991.6602.07511.30101215
    TBA12250.08730801.0435098601.6602.07512.5191113
    TBA12300.08730801.10461110051.6602.07513.2491113
    TBA12370.08730801.19175312111.6602.07514.2981012
    10 AWG
    TBA1020.11130450.431651241.0401.3005.17303030
    TBA1030.11130450.459971651.0401.3005.50303030
    607190#1040.11130450.5021302101.0401.3006.02242830
    TBA1050.11130600.5811622731.0401.3006.97242830
    TBA1060.11130600.6321943231.0401.3007.58242830
    TBA1070.11130600.6322273581.0401.3007.58212428
    TBA1080.11130600.6852594101.0401.3008.22212428
    TBA1090.11130600.7362914611.0401.3008.83212428
    TBA10100.11130600.8033245191.0401.3009.63151720
    626415#10120.11130800.9154526831.0401.30011151720
    TBA10150.11130800.9644867771.0401.30011.56151720
    TBA10190.11130801.0146159411.0401.30012.16151720
    TBA10200.11130801.06764810011.0401.30012.80151720
    TBA10250.11130801.18481012361.0401.30014.20131518
    TBA10300.11130801.25497114501.0401.30015.04131518
    TBA10370.11130801.355119817551.0401.30016.26121416
    626436#830.14245600.6752033340.6530.8498.1405055
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)
    ^ UL Listed part number
    # Tinned Copper