SPEC 46117
1/C CU 5kV 115 NLEPR 133% Thermoset SOLONON® LSZH-TS MV-105
Type MV-105 Single Conductor Copper, 115 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level, Tape Shield, Thermoset SOLONON® Low Smoke Zero Halogen (LSZH-TS) Jacket, Dual Rated UL/CSA. Silicone Free

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8 (Tinned Copper per ASTM B33 optional)
- Conductor Shield:Semi-conducting cross-linked copolymer
- Insulation:115 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Overall Jacket:Thermoset SOLONON® Low Smoke Zero Halogen (LSZH-TS)
Applications and Features:
Southwire’s 5KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), and where supe- rior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -25°C for cold bend. ST1 (low smoke) Rated for sizes 1/0 and larger. Rated for 1000 lbs./FT maximum sidewall pressure. Thermoset Solonon® jacket (XL LSZH).
Specifications:
Sample Print Legend:
{SQFTG_DUAL} SOUTHWIRE{R} POWER CABLE SOLONON{R} MASTER-DESIGN {UL} XXX AWG CU 115 MILS NL-EPR TSET SOLONON{R} 5KV 133%/8KV 100% INS LEVEL 25%TS MV-105 ST-1 FOR CT USE {NESC} --
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Diameter Over Conductor | Diameter Over Insulation | Diameter Over Insulation Shield | Jacket Thickness1 | Approx. OD | Approx. Weight | Max Pull Tension | Min Bending Radius | Conduit Size* |
---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | inch | inch | mil | inch | lb/1000ft | lb | inch | inch | |
TBA | 2 | 0.283 | 0.550 | 0.610 | 65 | 0.760 | 462 | 531 | 9.1 | 2.5 |
TBA | 1 | 0.322 | 0.589 | 0.649 | 65 | 0.799 | 531 | 670 | 9.6 | 2.5 |
TBA | 1/0 | 0.362 | 0.629 | 0.689 | 65 | 0.839 | 618 | 845 | 10.1 | 2.5 |
644045 | 2/0 | 0.405 | 0.672 | 0.732 | 65 | 0.882 | 723 | 1065 | 10.6 | 2.5 |
TBA | 3/0 | 0.456 | 0.723 | 0.783 | 80 | 0.963 | 884 | 1342 | 11.6 | 3 |
TBA | 4/0 | 0.512 | 0.779 | 0.839 | 80 | 1.019 | 1048 | 1693 | 12.2 | 3 |
TBA | 250 | 0.558 | 0.834 | 0.894 | 80 | 1.074 | 1194 | 2000 | 12.9 | 3 |
TBA | 350 | 0.661 | 0.937 | 0.997 | 80 | 1.177 | 1556 | 2800 | 14.1 | 3.5 |
TBA | 500 | 0.789 | 1.065 | 1.125 | 80 | 1.305 | 2085 | 4000 | 15.7 | 4 |
TBA | 750 | 0.968 | 1.253 | 1.313 | 80 | 1.493 | 2953 | 6000 | 17.9 | 5 |
TBA | 1000 | 1.117 | 1.402 | 1.462 | 80 | 1.642 | 3800 | 8000 | 19.7 | 5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Conduit size based on 3 phase 40% fill-factor without ground
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 2 – Electrical and Engineering Data
Cond. Size | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Shield Short Circuit Current 6 Cycles | Allowable Ampacity In Duct 90/105°C† | Allowable Ampacity In Air 90/105°C‡ |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
2 | 0.162 | 0.203 | 0.036 | 0.044 | 0.568 + j0.512 | 0.203 + j0.044 | 2017 | 145/155 | 190/215 |
1 | 0.129 | 0.161 | 0.033 | 0.043 | 0.530 + j0.490 | 0.162 + j0.043 | 2144 | 170/180 | 225/250 |
1/0 | 0.102 | 0.128 | 0.030 | 0.041 | 0.498 + j0.468 | 0.128 + j0.041 | 2274 | 195/210 | 260/290 |
2/0 | 0.081 | 0.101 | 0.027 | 0.040 | 0.473 + j0.446 | 0.102 + j0.040 | 2414 | 220/235 | 300/330 |
3/0 | 0.064 | 0.081 | 0.025 | 0.039 | 0.452 + j0.422 | 0.081 + j0.039 | 2580 | 250/270 | 345/385 |
4/0 | 0.051 | 0.064 | 0.023 | 0.038 | 0.434 + j0.397 | 0.065 + j0.037 | 2762 | 290/310 | 400/445 |
250 | 0.043 | 0.054 | 0.022 | 0.037 | 0.423 + j0.375 | 0.055 + j0.037 | 2941 | 320/345 | 445/495 |
350 | 0.031 | 0.039 | 0.019 | 0.035 | 0.402 + j0.336 | 0.040 + j0.035 | 3276 | 385/415 | 550/615 |
500 | 0.022 | 0.028 | 0.016 | 0.033 | 0.381 + j0.296 | 0.029 + j0.033 | 3693 | 470/505 | 695/775 |
750 | 0.014 | 0.020 | 0.014 | 0.032 | 0.355 + j0.247 | 0.020 + j0.032 | 4304 | 585/630 | 900/1000 |
1000 | 0.011 | 0.016 | 0.012 | 0.031 | 0.336 + j0.216 | 0.016 + j0.030 | 4789 | 670/720 | 1075/1200 |
* Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on TABLE 310.60(C)(77) Detail 1. of the 2020 National Electrical Code (20°C Ambient Earth Temperature, Thermal Resistance ROH of 90)
‡ Ampacities are based on TABLE 310.60(C)(69) of the 2020 National Electrical Code (40°C Ambient Air Temperature)
† Ampacities are based on TABLE 310.60(C)(77) Detail 1. of the 2020 National Electrical Code (20°C Ambient Earth Temperature, Thermal Resistance ROH of 90)
‡ Ampacities are based on TABLE 310.60(C)(69) of the 2020 National Electrical Code (40°C Ambient Air Temperature)
Revision: 3.0.00C