SPEC 46121
1/C Compact CU 5kV 115 NLEPR 133% CPE MV-105
Type MV-105 Single Conductor Compact Copper, 5kV/8kV 115 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133%/100% Insulation Level, Tape Shield, Chlorinated Polyethylene (CPE) Jacket, Dual Rated UL/CSA

Construction:
- Conductor:Class B compact stranded per ASTM B496
- Conductor Shield:Semi-conducting cross-linked copolymer
- Insulation:115 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Overall Jacket: Thermoplastic Chlorinated Polyethylene (CPE)
Applications and Features:
Southwire’s 5KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, and where supe- rior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend. ST1 (low smoke) Rated for sizes 1/0 and larger. Rated for 1000 lbs./FT maximum sidewall pressure.
Specifications:
Sample Print Legend:
SOUTHWIRE [SYMBOL - LIGHTING BOLT] #P# (UL/CSA) 1/C [#AWG or #kcmil] CU 115 MILS NL-EPR 5KV 133%/ 8KV 100% INS LEVEL 25% TS MV-105 FOR CT USE SUN. RES. TC-ER(CSA 1/0 LARGER) FOR DIRECT BURIAL FT4 -ST1 YEAR (NESC) [SEQUENTIAL FEET MARKS]
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Diameter Over Conductor | Diameter Over Insulation | Diameter Over Insulation Shield | Jacket Thickness1 | Approx. OD | Approx. Weight | Max Pull Tension | Min Bending Radius | Conduit Size* |
---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | inch | inch | mil | inch | lb/1000ft | lb | inch | inch | |
TBA | 2 | 0.268 | 0.535 | 0.595 | 65 | 0.745 | 445 | 531 | 8.9 | 2.5 |
TBA | 1 | 0.299 | 0.566 | 0.626 | 65 | 0.776 | 512 | 670 | 9.3 | 2.5 |
TBA | 1/0 | 0.336 | 0.603 | 0.663 | 65 | 0.813 | 597 | 845 | 9.8 | 2.5 |
TBA | 2/0 | 0.376 | 0.643 | 0.703 | 65 | 0.853 | 700 | 1065 | 10.2 | 2.5 |
TBA | 3/0 | 0.423 | 0.690 | 0.750 | 80 | 0.930 | 854 | 1342 | 11.2 | 3 |
TBA | 4/0 | 0.475 | 0.742 | 0.802 | 80 | 0.982 | 1013 | 1693 | 11.8 | 3 |
TBA | 250 | 0.520 | 0.796 | 0.856 | 80 | 1.036 | 1156 | 2000 | 12.4 | 3 |
TBA | 350 | 0.616 | 0.892 | 0.952 | 80 | 1.132 | 1509 | 2800 | 13.6 | 3.5 |
TBA | 500 | 0.736 | 1.012 | 1.072 | 80 | 1.252 | 2026 | 4000 | 15.0 | 3.5 |
TBA | 750 | 0.908 | 1.215 | 1.275 | 80 | 1.455 | 2873 | 6000 | 17.5 | 4 |
TBA | 1000 | 1.060 | 1.367 | 1.427 | 80 | 1.607 | 3701 | 8000 | 19.3 | 5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Conduit size based on 3 phase 40% fill-factor without ground
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 2 – Electrical and Engineering Data
Cond. Size | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Shield Short Circuit Current 6 Cycles | Allowable Ampacity In Duct 90/105°C† | Allowable Ampacity In Air 90/105°C‡ |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
2 | 0.162 | 0.203 | 0.037 | 0.045 | 0.698 + j0.521 | 0.335 + j0.045 | 1968 | 145/155 | 190/215 |
1 | 0.129 | 0.161 | 0.034 | 0.044 | 0.632 + j0.503 | 0.266 + j0.044 | 2069 | 170/180 | 225/250 |
1/0 | 0.102 | 0.128 | 0.032 | 0.042 | 0.580 + j0.482 | 0.212 + j0.042 | 2189 | 195/210 | 260/290 |
2/0 | 0.081 | 0.101 | 0.029 | 0.041 | 0.538 + j0.461 | 0.168 + j0.040 | 2320 | 220/235 | 300/330 |
3/0 | 0.064 | 0.081 | 0.026 | 0.040 | 0.503 + j0.437 | 0.133 + j0.040 | 2473 | 250/270 | 345/385 |
4/0 | 0.051 | 0.064 | 0.024 | 0.038 | 0.476 + j0.413 | 0.106 + j0.038 | 2642 | 290/310 | 400/445 |
250 | 0.043 | 0.054 | 0.023 | 0.038 | 0.459 + j0.390 | 0.090 + j0.037 | 2817 | 320/345 | 445/495 |
350 | 0.031 | 0.039 | 0.020 | 0.036 | 0.429 + j0.353 | 0.064 + j0.036 | 3130 | 385/415 | 550/615 |
500 | 0.022 | 0.028 | 0.017 | 0.034 | 0.402 + j0.312 | 0.046 + j0.034 | 3520 | 470/505 | 695/775 |
750 | 0.014 | 0.020 | 0.016 | 0.033 | 0.369 + j0.257 | 0.031 + j0.032 | 4180 | 585/630 | 900/1000 |
1000 | 0.011 | 0.016 | 0.014 | 0.031 | 0.347 + j0.224 | 0.024 + j0.031 | 4675 | 670/720 | 1075/1200 |
* Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on TABLE 310.60(C)(77) Detail 1. of the 2014 National Electrical Code (20°C Ambient Earth Temperature, Thermal Resistance ROH of 90)
‡ Ampacities are based on TABLE 310.60(C)(69) of the 2014 National Electrical Code (40°C Ambient Air Temperature)
† Ampacities are based on TABLE 310.60(C)(77) Detail 1. of the 2014 National Electrical Code (20°C Ambient Earth Temperature, Thermal Resistance ROH of 90)
‡ Ampacities are based on TABLE 310.60(C)(69) of the 2014 National Electrical Code (40°C Ambient Air Temperature)
Revision: 3.0.00M