SPEC 25250

1/C CU 1000V/2000V RPVU90 XLPE

Single Copper Conductors, 1000V/2000V, 90°C MAX - 40°C MIN, Sunlight Resistant

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE)

Applications and Features:

Single copper conductor with low temperature, moisture resisting XLPE (cross linked polyethylene) insulation. Sunlight Resistant. This product meets the current RoHS requirements. No lead is added or used in manufacturing.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables Type RW90
  • RoHS Compliant Lead-Free, Silicone-Free
  • CSA Standard C22.2 No. 271 Photovoltaic Cables
  • Sample Print Legend:

    SOUTHWIRE LL90458 {CSA} AWG XX (XX.X{mm2}) CU XLPE RPVU90 1000V/2000V -40{D}C SR DIRECT BURIAL --- {MM/DD/YYYY} --- RoHS {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeDiameter Over ConductorInsul. ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C†
    AWG/Kcmilinchmilinchlb/1000ftinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmp
    TBA140.0276600.194240.8332.633.420.04425
    TBA120.0915600.213400.9521.662.160.04130
    583670100.113600.233530.9831.041.350.03840
    TBA100.113600.233530.9831.041.350.03840
    584430!100.113600.233470.9831.041.350.03840
    TBA80.146800.305801.21320.6530.8490.03955
    TBA60.178800.3381132.72100.4030.5350.03675
    TBA40.225800.3851673.13340.2530.3360.03495
    TBA20.283800.4432513.55310.1560.2110.032130
    TBA10.322950.5123234.16700.1260.1670.032145
    TBA1/00.362950.5523964.48450.10.1330.031170
    TBA2/00.405950.5954894.810650.080.1050.031195
    TBA3/00.456950.6466045.213420.0630.0840.03225
    TBA4/00.512950.7027495.616930.050.0660.029260
    TBA2500.5581100.7788916.220000.0420.0560.029290
    TBA3500.6611100.881121728000.030.040.028350
    TBA5000.7891101.00917068.140000.0210.0330.027430
    TBA6000.8661251.1120518.948000.0180.0270.027475
    TBA7500.9861251.23625349.960000.0140.0220.027535
    TBA10001.1171251.367333610.980000.0110.0160.026615
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Ampacities based on 2017 NEC Table 310.15(B)(16): Allowable Ampacities of Insulated Conductors Rated Up to and Including 2000 Volts, 60°C Through 90°C (140°F Through 194°F), Not More Than Three Current-Carrying Conductors in Raceway, Cable, or Earth (Directly Buried), Based on Ambient Temperature of 30°C (86°F)
    ! Bunch unilay 19 strand tinned copper
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeDiameter Over ConductorInsul. ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C†
    AWG/Kcmilmmmmmmkg/kmmmnewtonΩ/kmΩ/kmΩ/kmAmp
    TBA140.701.524.933620.321478.628611.220.144425
    TBA122.321.525.416022.862315.44627.090.134530
    583670102.871.525.927922.863693.41214.430.124740
    TBA102.871.525.927922.863693.41214.430.124740
    584430!102.871.525.927022.863693.41214.430.124740
    TBA83.712.037.7511930.485872.14242.790.128055
    TBA64.522.038.5916868.589351.32221.760.118175
    TBA45.722.039.7824978.7414860.83011.100.111595
    TBA27.192.0311.2537488.9023630.51180.690.1050130
    TBA18.182.4113.00481104.1429820.41340.550.1050145
    TBA1/09.192.4114.02589111.7637600.32810.440.1017170
    TBA2/010.292.4115.11728121.9247390.26250.340.1017195
    TBA3/011.582.4116.41899132.0859720.20670.280.0984225
    TBA4/013.002.4117.831115142.2475340.16400.220.0951260
    TBA25014.172.7919.761326157.4889000.13780.180.0951290
    TBA35016.792.7922.38180177.80124600.09840.130.0919350
    TBA50020.042.7925.632539205.74178000.06890.110.0886430
    TBA60022.003.1828.193052226.06213600.05910.090.0886475
    TBA75025.043.1831.393771251.46267000.04590.070.0886535
    TBA100028.373.1834.724965276.86356000.03610.050.0853615
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Ampacities based on 2017 NEC Table 310.15(B)(16): Allowable Ampacities of Insulated Conductors Rated Up to and Including 2000 Volts, 60°C Through 90°C (140°F Through 194°F), Not More Than Three Current-Carrying Conductors in Raceway, Cable, or Earth (Directly Buried), Based on Ambient Temperature of 30°C (86°F)
    ! Bunch unilay 19 strand tinned copper

    Stock Code and Color (other than Black)

    Stock CodeSize AWGColor
    58367110Red