SPEC 42025
FEP 200°C 600V UL Type FEPB
UL/CSA Approved Lead Wire, Temp Rating 200°C

Construction:
- Conductor:Stranded tinned, annealed copper per ASTM B33
- Insulation:Extruded FEP fluoropolymer
- Jacket:Treated fiberglass braid
Applications and Features:
For use in accordance with the National Electric Code, Article 310. 200°C dry locations - special applications. 90°C dry and damp locations. Excellent chemical resistance, excellent resistance to fluids, and low coefficient of friction makes installation easier. Good mechanical strength. Available in all colors.
Specifications:
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Cond. Strands | Insul. Thickness | Approx. OD | Approx. Weight | Temp. Rating | Standard (UL or other) |
---|---|---|---|---|---|---|---|
AWG/Kcmil | strand | mil | inch | lb/1000ft | °C | Style/Type | |
C3146G | 14 | 7/.0242 | 14 | 0.110 | 16 | 200 | FEPB |
C3126G | 12 | 19/.0179 | 14 | 0.130 | 25 | 200 | FEPB |
C3106G | 10 | 37/.0159 | 14 | 0.160 | 35 | 200 | FEPB |
C3086G | 8 | 54/.0179 | 14 | 0.205 | 60 | 200 | FEPB |
C3066G | 6 | 84/.0179 | 14 | 0.220 | 95 | 200 | FEPB |
C3046G | 4 | 133/.0177 | 14 | 0.280 | 145 | 200 | FEPB |
C3026G | 2 | 133/.0223 | 14 | 0.320 | 220 | 200 | FEPB |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
Dimensions and weights for other cable configurations are available upon request.
Table 2 – Weights and Measurements (Metric)
Stock Number | Cond. Size | Cond. Strands | Insul. Thickness | Approx. OD | Approx. Weight | Temp. Rating | Standard (UL or other) |
---|---|---|---|---|---|---|---|
AWG/Kcmil | strand | mm | mm | kg/km | °C | Style/Type | |
C3146G | 14 | 7/.0242 | 0.36 | 2.79 | 24 | 200 | FEPB |
C3126G | 12 | 19/.0179 | 0.36 | 3.30 | 37 | 200 | FEPB |
C3106G | 10 | 37/.0159 | 0.36 | 4.06 | 52 | 200 | FEPB |
C3086G | 8 | 54/.0179 | 0.36 | 5.21 | 89 | 200 | FEPB |
C3066G | 6 | 84/.0179 | 0.36 | 5.59 | 141 | 200 | FEPB |
C3046G | 4 | 133/.0177 | 0.36 | 7.11 | 216 | 200 | FEPB |
C3026G | 2 | 133/.0223 | 0.36 | 8.13 | 327 | 200 | FEPB |
Revision: 3.0.00M