SPEC 42220

FEP/FEP Power Tray Cable

Flexible Power Cable, 600 Volts, 200°C Dry Special Applications

...

Construction:

  1. Conductor:Class B stranding per ASTM B8. Tinned, annealed copper per ASTM B33
  2. Insulation:Extruded fluorinated ethylene propylene (FEP) ICEA Method 4
  3. Ground:Uninsulated ground wire
  4. Binder:Binder tape is applied over the core
  5. Overall Jacket:Extruded fluorinated ethylene propylene (FEP)

Applications and Features:

For use as a 600 volt, Multi conductor control cable where flame retardance, Moisture/Chemical resistance, and high temperature rating is critical. Cable can be installed in free air, in raceways or direct burial. The cable is also approved for damp or dry locations as well as Class 1 Division II industrial hazardous locations per NEC 501-4(b) for (UL) Type tray cables (TC).

Temperature rating of 200°C dry for special applications. Excellent electrical properties, chemical resistance, resistance to fluids, and flame resistance. Resistant to crush, compression and deformation. Low coefficient of friction makes installation easier. Good mechanical strength. Flexible. Available with insulated ground wires. Per ICEA Method 4. Available with E1 or E2 color code.

Specifications:

  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • UL 1277 Vertical Cable Tray Flame Tests (70,000 BTU/Hr)
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 Flame Test (70,000 BTU/hr) 350kcmil and Larger
  • RoHS-3 Complies with European Directive 2015/863
  • VW-1 (Vertical-Wire) Flame Test
  • Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightTemp. RatingStandard (UL or other)
    AWG/KcmilNo.milmilinchlb/1000ft°CStyle/Type
    C5F30212220450.34890200UL Type TC
    C5F30612320450.408118200UL Type TC
    C5F31112420450.445148200UL Type TC
    C5F40210220450.431124200UL Type TC
    C5F40610320450.459165200UL Type TC
    C5F41110420450.502210200UL Type TC
    C5F5008230450.580200200UL Type TC
    C5F5058330600.615307200UL Type TC
    C5F5108430600.673379200UL Type TC
    C5F5256230600.660321200UL Type TC
    C5F5306330600.691444200UL Type TC
    C5F5356430600.785551200UL Type TC
    C5F5504230600.749470200UL Type TC
    C5F5554330600.791607200UL Type TC
    C5F5604430800.910800200UL Type TC
    C5F5752230800.950680200UL Type TC
    C5F5802330800.953941200UL Type TC
    C5F5852430801.0471189200UL Type TC
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeCond. NumberInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightTemp. RatingStandard (UL or other)
    AWG/KcmilNo.mmmmmmkg/km°CStyle/Type
    C5F3021220.511.148.84134200UL Type TC
    C5F3061230.511.1410.36176200UL Type TC
    C5F3111240.511.1411.30220200UL Type TC
    C5F4021020.511.1410.95185200UL Type TC
    C5F4061030.511.1411.66246200UL Type TC
    C5F4111040.511.1412.75313200UL Type TC
    C5F500820.761.1414.73298200UL Type TC
    C5F505830.761.5215.62457200UL Type TC
    C5F510840.761.5217.09564200UL Type TC
    C5F525620.761.5216.76478200UL Type TC
    C5F530630.761.5217.55661200UL Type TC
    C5F535640.761.5219.94820200UL Type TC
    C5F550420.761.5219.02699200UL Type TC
    C5F555430.761.5220.09903200UL Type TC
    C5F560440.762.0323.111191200UL Type TC
    C5F575220.762.0324.131012200UL Type TC
    C5F580230.762.0324.211400200UL Type TC
    C5F585240.762.0326.591769200UL Type TC

    Revision: 3.0.00M