SPEC 26101

HVTECK CU 1/C 90NLEPR TS PVC AIA PVC 5kV 100% CSA

Single Conductor, 90 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:90 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Inner Jacket:PVC inner jacket
  7. Armour:Aluminum Interlocked Armour (AIA)
  8. Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 5kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 90 NLEPR AIA 5kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo.inchinchmilinchmilinchmilinchlb/1000ftlb/1000ft
    270.2820.500900.560650.932501.032215609
    1190.3220.540900.600650.972501.072270688
    1/0190.3610.579900.639651.011501.111338780
    2/0190.4050.623900.683801.085501.185424926
    3/0190.4560.674900.734801.136501.2365771110
    4/0190.5120.730900.790801.192501.2927171286
    250370.5580.784900.844801.356501.4568391458
    350370.6610.887900.947801.459501.55911571843
    500370.7891.015901.075801.587601.70716302433
    750610.9681.204901.264801.800601.92024173391
    1000611.1171.353901.413801.949602.06932014376
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    212.45300.1620.2040.0260.0510.553 + j0.5340.205 + j0.0521766215221
    112.96690.1280.1620.0230.0490.516 + j0.5110.163 + j0.0501889245247
    1/013.38440.1020.1280.0210.0470.486 + j0.4890.129 + j0.0482010278275
    2/014.210640.0810.1020.0200.0460.463 + j0.4660.103 + j0.0472147317306
    3/08.613420.0640.0810.0200.0450.443 + j0.4460.082 + j0.0452274357335
    4/09.016920.0510.0650.0180.0430.429 + j0.420.066 + j0.0432447404369
    25010.120000.0430.0560.0170.0440.418 + j0.3970.057 + j0.0442614456412
    35010.928000.0310.0410.0150.0410.4 + j0.3570.042 + j0.0412934537456
    50011.940000.0220.0300.0130.0390.381 + j0.3140.031 + j0.043330616497
    75013.460000.0140.0230.0110.0370.359 + j0.2620.024 + j0.0373916706551
    100014.480000.0110.0190.0100.0360.342 + j0.2290.02 + j0.0364377813596
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo.mmmmmmmmmmmmmmmmkg/kmkg/km
    277.1612.702.2914.221.6523.671.2726.21320906
    1198.1813.722.2915.241.6524.691.2727.234021024
    1/0199.1714.712.2916.231.6525.681.2728.225031161
    2/01910.2915.822.2917.352.0327.561.2730.106311378
    3/01911.5817.122.2918.642.0328.851.2731.398591652
    4/01913.0018.542.2920.072.0330.281.2732.8210671914
    2503714.1719.912.2921.442.0334.441.2736.9812492170
    3503716.7922.532.2924.052.0337.061.2739.6017222743
    5003720.0425.782.2927.302.0340.311.5243.3624263621
    7506124.5930.582.2932.112.0345.721.5248.7735975046
    10006128.3734.372.2935.892.0349.501.5252.5547646512
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2314.9623590.53150.670.00790.16730.553 + j0.5340.205 + j0.0521766215221
    1327.6629770.41990.530.00700.16080.516 + j0.5110.163 + j0.0501889245247
    1/0337.8237560.33460.420.00640.15420.486 + j0.4890.129 + j0.0482010278275
    2/0360.6847350.26570.330.00610.15090.463 + j0.4660.103 + j0.0472147317306
    3/0218.4459720.21000.270.00610.14760.443 + j0.4460.082 + j0.0452274357335
    4/0228.6075290.16730.210.00550.14110.429 + j0.420.066 + j0.0432447404369
    250256.5489000.14110.180.00520.14440.418 + j0.3970.057 + j0.0442614456412
    350276.86124600.10170.130.00460.13450.4 + j0.3570.042 + j0.0412934537456
    500302.26178000.07220.100.00400.12800.381 + j0.3140.031 + j0.043330616497
    750340.36267000.04590.080.00340.12140.359 + j0.2620.024 + j0.0373916706551
    1000365.76356000.03610.060.00300.11810.342 + j0.2290.02 + j0.0364377813596
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.

    Revision: 1.000.000