SPEC 26371

HVTECK AL 3/C 175TRXLPE TS PVC AIA PVC 15kV 100% CSA

3 Conductor, 175 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:175 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Filler:Interstices filled with non-hydroscoping/non-wicking fillers
  7. Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
  8. Binder:Polypropylene tape
  9. Inner Jacket:PVC inner jacket
  10. Armour:Aluminum Interlocked Armour (AIA)
  11. Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CPT AL 175 TRXLPE AIA 15kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGround SizeInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchAWGmilinchmilinchlb/1000ft
    270.2680.6561750.71681102.166602.2861998
    1190.2980.6861750.74661102.231602.3512141
    1/0190.3360.7241750.78461102.313752.4632382
    2/0190.3760.7641750.82461102.399752.5492574
    3/0190.4220.8101750.87061102.498752.6482807
    4/0190.4740.8621750.92261102.611752.7613082
    250370.5200.9161750.97641102.727752.8773375
    350370.6151.0111751.07141102.933753.0833944
    500370.7351.1311751.19131253.222853.3924911
    750610.9081.3141751.37421253.617853.7876250
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    216.011940.2670.3360.0560.0450.711 + j0.4650.336 + j0.0452249135157
    116.515060.2110.2660.0520.0430.642 + j0.4480.266 + j0.0422342154178
    1/017.219000.1680.2110.0480.0420.586 + j0.4290.211 + j0.0402459176202
    2/017.823950.1330.1670.0440.0400.542 + j0.4100.167 + j0.0392584204229
    3/018.530200.1050.1330.0410.0390.506 + j0.3900.133 + j0.0372726234260
    4/019.338080.0840.1050.0370.0370.475 + j0.3690.105 + j0.0362887268294
    25020.145000.0710.0900.0350.0370.457 + j0.3480.090 + j0.0353054296323
    35021.663000.0500.0650.0300.0300.425 + j0.3160.065 + j0.0333349363386
    50023.790000.0350.0460.0300.0300.395 + j0.2800.046 + j0.0323721447465
    75026.5135000.0200.0300.0200.0300.364 + j0.2360.034 + j0.0304288566563
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGround SizeInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmAWGmmmmmmmmkg/km
    276.8116.664.4418.1982.7955.021.5258.062973
    1197.5717.424.4418.9562.7956.671.5259.723186
    1/0198.5318.394.4419.9162.7958.751.9162.563545
    2/0199.5519.414.4420.9362.7960.931.9164.743831
    3/01910.7220.574.4422.1062.7963.451.9167.264177
    4/01912.0421.894.4423.4262.7966.321.9170.134587
    2503713.2123.274.4424.7942.7969.271.9173.085023
    3503715.6225.684.4427.2042.7974.501.9178.315869
    5003718.6728.734.4430.2533.1881.842.1686.167308
    7506123.0633.384.4434.9023.1891.872.1696.199301
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2406.4053130.87601.100.01710.14760.711 + j0.4650.336 + j0.0452249135157
    1419.1067020.69230.870.01580.14110.642 + j0.4480.266 + j0.0422342154178
    1/0436.8884550.55120.690.01460.13780.586 + j0.4290.211 + j0.0402459176202
    2/0452.12106580.43640.550.01340.13120.542 + j0.4100.167 + j0.0392584204229
    3/0469.90134390.34450.440.01250.12800.506 + j0.3900.133 + j0.0372726234260
    4/0490.22169460.27560.340.01130.12140.475 + j0.3690.105 + j0.0362887268294
    250510.54200250.23290.300.01070.12140.457 + j0.3480.090 + j0.0353054296323
    350548.64280350.16400.210.00910.09840.425 + j0.3160.065 + j0.0333349363386
    500601.98400500.11480.150.00910.09840.395 + j0.2800.046 + j0.0323721447465
    750673.10600750.06560.100.00610.09840.364 + j0.2360.034 + j0.0304288566563
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.

    Revision: 1.000.000

    Updated On: Dec. 11, 2023, 9:29 p.m. UTC