SPEC 85011

Multi-Conductor CU 600 V FR-XLPE Thermoplastic CPE-TP Jacket Control Cable Color Method 1 Table 2

Control Cable 600 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket, Control Cable Conductor Identification Method 1 Table 2. Silicone Free

...

Construction:

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  2. Insulation:Flame Retardant Cross Linked Polyethylene (FR-XLPE), 30 Mils thick for all cable sizes
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Rip Cord:Rip cord for ease of jacket removal
  6. Overall Jacket:Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket

Applications and Features:

Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated constructions can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)
  • VW-1 (Vertical-Wire) Flame Test
  • Sample Print Legend:

    UL Listed
    SOUTHWIRE E75755 {UL} XX AWG X/C FR-XLPE XHHW-2 TYPE TC CDRS 90C CPE JKT 600V SUNLIGHT RESISTANT MM/YYYY{SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Non UL Listed
    SOUTHWIRE XX AWG X/C FR-XLPE CDRS 90C CPE JKT 600V SUN. RES. DIRECT BURIAL YEAR SEQUENTIAL FOOTAGE MARKS SEQ FEET

    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusAllowable Ampacity At 60°CAllowable Ampacity 75°CAllowable Ampacity 90°C
    AWGNo.strandsinchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmpAmp
    14 AWG
    TBA14370.07030450.37238852.6313.1700.0581.4152025
    TBA14470.07030450.406511022.6313.1700.0581.6121620
    TBA14570.07030450.443631222.6313.1700.0581.7121620
    TBA14670.07030450.482761432.6313.1700.0581.9121620
    TBA14770.07030450.482891612.6313.1700.0581.9101417
    TBA14870.07030600.5521021992.6313.1700.0582.2101417
    TBA14970.07030600.5911152222.6313.1700.0582.3101417
    TBA141070.07030600.6421272452.6313.1700.0582.571012
    604289141270.07030600.6671532962.6313.1700.0582.671012
    TBA141570.07030600.7341913432.6313.1700.0582.971012
    TBA141970.07030600.7722434202.6313.1700.0583.071012
    TBA142070.07030600.8122554422.6313.1700.0583.271012
    TBA142570.07030800.9423195772.6313.1700.0583.76911
    TBA143070.07030800.9953836742.6313.1700.0583.96911
    TBA143770.07030801.0724738102.6313.1700.0585.36810
    619661142190.07230450.35625652.6313.1700.0581.4152025
    6196631412190.07230600.6691542922.6313.1700.0582.771012
    12 AWG
    606668^12270.08830450.40440891.6622.0020.0541.6202530
    66194412370.08830450.416611161.6622.0020.0541.6202530
    TBA12470.08830450.450811401.6622.0020.0541.8162024
    624834!12470.08830450.476811531.6622.0020.0541.9162024
    TBA12570.08830450.4911011681.6622.0020.0541.9162024
    TBA12670.08830600.5661222161.6622.0020.0542.2162024
    TBA12770.08830600.5661422421.6622.0020.0542.2141721
    604308127190.08830600.5781422501.6622.0020.0542.3141721
    TBA12870.08830600.6111622731.6622.0020.0542.4141721
    TBA12970.08830600.6561833051.6622.0020.0542.6141721
    TBA121070.08830600.7142033371.6622.0020.0542.8101215
    662211121270.08830600.7402444011.6622.0020.0542.9101215
    662180^121270.08830600.7592444141.6622.0020.0543.0101215
    TBA121570.08830600.8193054811.6622.0020.0543.2101215
    606714^121970.08830800.9123866541.6622.0020.0543.6101215
    TBA122070.08830800.9474066581.6622.0020.0543.7101215
    TBA122570.08830801.0505088051.6622.0020.0545.291113
    TBA123070.08830801.1106109451.6622.0020.0545.591113
    TBA123770.08830801.19875211421.6622.0020.0545.981012
    10 AWG
    604290^10270.11330450.440641181.0401.2530.0501.7303540
    TBA10370.11330450.465971621.0401.2530.0501.8303540
    60429110470.11330450.5061292041.0401.2530.0502.0242832
    606503^10470.11330450.5401292221.0401.2530.0502.1242832
    TBA10570.11330600.5891612581.0401.2530.0502.3242832
    TBA10670.11330600.6411943041.0401.2530.0502.5242832
    62225410770.11330600.6412263521.0401.2530.0502.5212428
    TBA10870.11330600.6942583891.0401.2530.0502.7212428
    TBA10970.11330600.7462914351.0401.2530.0502.9212428
    TBA101070.11330600.8143234821.0401.2530.0503.2151720
    606610^101270.11330800.8753886071.0401.2530.0503.5151720
    TBA101570.11330800.9764857311.0401.2530.0503.9151720
    TBA101970.11330801.0276148961.0401.2530.0505.1151720
    TBA102070.11330801.0806469441.0401.2530.0505.4151720
    TBA102570.11330801.20080811601.0401.2530.0506.0131518
    TBA103070.11330801.27097013681.0401.2530.0506.3131518
    TBA103770.11330801.373119616591.0401.2530.0506.8121416
    619664102190.11730450.452641211.0401.2530.0501.8303540
    619665104190.11730600.5581292331.0401.2530.0502.2242832
    6196661012190.11730800.9093886261.0401.2530.0503.6151720
    8 AWG
    6618668270.14145600.5921022100.6530.7860.0522.3405055
    6 AWG
    6229916470.17745600.7753275010.4110.4950.0513.1445260
    603629$64190.17745600.7793275010.4110.4950.0513.1445260
    4 AWG
    603628$44190.22545800.9305207770.2580.3100.0483.7566876
    6619464470.22545800.9335217680.2580.3100.0483.7566876
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    ^ UL listed part number
    ! Tinned copper conductor per ASTM B33
    † 19 strand Class C conductor per ASTM B8
    $ 19 strand combination unilay conductor per ASTM B787
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements. Ampacities have been adjusted for stock numbers containing more than Three Current-Carrying Conductors.

    Revision: 1.000.007

    Updated On: April 10, 2024, 1:08 p.m. UTC