SPEC 42022

FEP 200°C 600V UL 1330

Flexible UL/CSA Approved Lead Wire, Temp Rating 200°C

...

Construction:

  1. Conductor:Stranded tinned, annealed copper per ASTM B33
  2. Insulation:Extruded FEP fluoropolymer

Applications and Features:

Used for wiring of electric heaters, appliances, thermocouples, gas igniters, electrical and electronic components, and other products that require a temperature rating up to 200° C.

Excellent chemical resistance, excellent resistance to fluids, and low coefficient of friction makes installation easier. Flexible. Good mechanical strength. Available in all colors.

Specifications:

  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • UL AWM Appliance wire approvals as listed in Table 1
  • CSA AWM I A/B 600 FT1 FT2
  • RoHS-3 Complies with European Directive 2015/863
  • Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. StrandsInsul. ThicknessApprox. ODApprox. WeightTemp. RatingStandard (UL or other)
    AWG/Kcmilstrandmilinchlb/1000ft°CStyle/Type
    C3246Z*24*7/.008200.06542001330
    C3226Z*22*7/.010200.07052001330
    C3206Z*20*7/.0126200.08072001330
    C3186A187/.0159200.090102001330
    C3166A167/.0192200.100132001330
    C3146A147/.0242200.110172001330
    C3126A1219/.0179200.130252001330
    C3106A1037/.0159200.160352001330
    C3086A854/.0179300.220602001330
    C3066A684/.0179300.235952001330
    C3046A4133/.0177300.2951452001330
    C3026A2133/.0223300.3402202001330
    C3016A1259/.0177450.4603202001330
    C31T6A1/0259/.0202450.4853602001330
    C32T6A2/0259/.0229450.5154602001330
    C33T6A3/0259/.0255450.5755652001330
    C34T6A4/0259/.0286450.6757552001330
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Dimensions and weights for other cable configurations are available upon request.
    *NPC Conductor required for 200°C Rating
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeCond. StrandsInsul. ThicknessApprox. ODApprox. WeightTemp. RatingStandard (UL or other)
    AWG/Kcmilstrandmmmmkg/km°CStyle/Type
    C3246Z*24*7/.0080.511.6562001330
    C3226Z*22*7/.0100.511.7872001330
    C3206Z*20*7/.01260.512.03102001330
    C3186A187/.01590.512.29152001330
    C3166A167/.01920.512.54192001330
    C3146A147/.02420.512.79252001330
    C3126A1219/.01790.513.30372001330
    C3106A1037/.01590.514.06522001330
    C3086A854/.01790.765.59892001330
    C3066A684/.01790.765.971412001330
    C3046A4133/.01770.767.492162001330
    C3026A2133/.02230.768.643272001330
    C3016A1259/.01771.1411.684762001330
    C31T6A1/0259/.02021.1412.325362001330
    C32T6A2/0259/.02291.1413.086852001330
    C33T6A3/0259/.02551.1414.608412001330
    C34T6A4/0259/.02861.1417.1511242001330

    Revision: 1.000.000

    Updated On: Dec. 11, 2023, 9:29 p.m. UTC