SPEC 42037

PFA 250°C 600V UL Type PFAH

Flexible UL/NEC Approved Lead Wire, Temp Rating 250°C

...

Construction:

  1. Conductor:Stranded tinned, annealed nickel plated copper per ASTM B33
  2. Insulation:Extruded PFA fluoropolymer

Applications and Features:

Dry locations only. Only for leads within apparatus or within raceways connected to apparatus (nickel or nickel-coated copper only).

Excellent chemical resistance, excellent resistance to fluids, and low coefficient of friction makes installation easier. Flexible. Good mechanical strength. Available in all colors.

Specifications:

  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • UL AWM Appliance wire approvals as listed in Table 1
  • CSA AWM I A/B FT1
  • RoHS-3 Complies with European Directive 2015/863
  • Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. StrandsInsul. ThicknessApprox. ODApprox. WeightTemp. RatingStandard (UL or other)
    AWG/Kcmilstrandmilinchlb/1000ft°CStyle/Type
    CP146H1419/.0147200.11017250NEC Style PFAH
    CP126H1219/.0186200.13025250NEC Style PFAH
    CP106H1037/.0159200.14535250NEC Style PFAH
    CP086H8133/.0111300.23070250NEC Style PFAH
    CP066H6133/.0141300.27095250NEC Style PFAH
    CP046H4133/.0177300.325160250NEC Style PFAH
    CP026H2133/.0223300.395235250NEC Style PFAH
    CP016H1259/.0177450.470320250NEC Style PFAH
    CP1T6H1/0259/.0202450.515400250NEC Style PFAH
    CP2T6H2/0259/.0229450.570495250NEC Style PFAH
    CP3T6H3/0259/.0255450.610565250NEC Style PFAH
    CP4T6H4/0259/.0286450.690730250NEC Style PFAH
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Dimensions and weights for other cable configurations are available upon request.
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeCond. StrandsInsul. ThicknessApprox. ODApprox. WeightTemp. RatingStandard (UL or other)
    AWG/Kcmilstrandmmmmkg/km°CStyle/Type
    CP146H1419/.01470.512.7925250NEC Style PFAH
    CP126H1219/.01860.513.3037250NEC Style PFAH
    CP106H1037/.01590.513.6852250NEC Style PFAH
    CP086H8133/.01110.765.84104250NEC Style PFAH
    CP066H6133/.01410.766.86141250NEC Style PFAH
    CP046H4133/.01770.768.25238250NEC Style PFAH
    CP026H2133/.02230.7610.03350250NEC Style PFAH
    CP016H1259/.01771.1411.94476250NEC Style PFAH
    CP1T6H1/0259/.02021.1413.08595250NEC Style PFAH
    CP2T6H2/0259/.02291.1414.48737250NEC Style PFAH
    CP3T6H3/0259/.02551.1415.49841250NEC Style PFAH
    CP4T6H4/0259/.02861.1417.531086250NEC Style PFAH

    Revision: 1.000.000

    Updated On: Dec. 11, 2023, 9:29 p.m. UTC