SPEC 26411
HVTECK CU 1/C 260TRXLPE TS PVC AIA PVC 25kV 100% CSA
Single Conductor, 260 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Conductor Shield:Semi-conducting cross-linked copolymer
- Insulation:260 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 25kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL) and 105°C for use in harsh Canadian environments. For installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 260 TRXLPE AIA 25kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Dia. Over Inner Jacket | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | inch | inch | mil | inch | inch | inch | mil | inch | lb/1000ft | |
TBA | 1 | 19 | 0.322 | 0.879 | 260 | 0.939 | 1.119 | 1.439 | 50 | 1.539 | 1123 |
TBA | 1/0 | 19 | 0.362 | 0.919 | 260 | 0.979 | 1.159 | 1.479 | 50 | 1.579 | 1228 |
TBA | 2/0 | 19 | 0.405 | 0.962 | 260 | 1.022 | 1.202 | 1.522 | 50 | 1.622 | 1352 |
TBA | 3/0 | 19 | 0.456 | 1.013 | 260 | 1.073 | 1.253 | 1.573 | 50 | 1.673 | 1507 |
TBA | 4/0 | 19 | 0.512 | 1.069 | 260 | 1.129 | 1.309 | 1.629 | 50 | 1.729 | 1694 |
TBA | 250 | 37 | 0.558 | 1.124 | 260 | 1.184 | 1.364 | 1.684 | 50 | 1.784 | 1863 |
TBA | 350 | 37 | 0.661 | 1.227 | 260 | 1.287 | 1.467 | 1.787 | 60 | 1.907 | 2304 |
TBA | 500 | 37 | 0.789 | 1.355 | 260 | 1.415 | 1.595 | 1.925 | 60 | 2.045 | 2948 |
TBA | 750 | 61 | 0.968 | 1.543 | 260 | 1.603 | 1.843 | 2.173 | 60 | 2.293 | 4025 |
TBA | 1000 | 61 | 1.117 | 1.692 | 260 | 1.752 | 1.992 | 2.322 | 60 | 2.442 | 4950 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 2 – Electrical and Engineering Data
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity in Vented Cable Tray 90°C‡ | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
1 | 10.8 | 670 | 0.129 | 0.161 | 0.068 | 0.058 | 0.520+j0.371 | 0.162+j0.058 | 6.0 | 245 | 244 |
1/0 | 11.1 | 845 | 0.102 | 0.128 | 0.063 | 0.056 | 0.485+j0.356 | 0.129+j0.055 | 7.6 | 278 | 272 |
2/0 | 11.4 | 1065 | 0.081 | 0.101 | 0.059 | 0.054 | 0.456+j0.340 | 0.102+j0.054 | 9.6 | 316 | 303 |
3/0 | 11.7 | 1342 | 0.0642 | 0.080 | 0.054 | 0.052 | 0.431+j0.323 | 0.081+j0.051 | 12.1 | 356 | 333 |
4/0 | 12.1 | 1693 | 0.051 | 0.064 | 0.050 | 0.050 | 0.411+j0.305 | 0.065+j0.050 | 15.2 | 403 | 367 |
250 | 12.5 | 2000 | 0.0431 | 0.054 | 0.048 | 0.048 | 0.397+j0.289 | 0.055+j0.048 | 18.0 | 455 | 411 |
350 | 13.3 | 2800 | 0.0308 | 0.039 | 0.042 | 0.046 | 0.373+j0.262 | 0.040+j0.046 | 25.2 | 537 | 459 |
500 | 14.3 | 4000 | 0.0216 | 0.028 | 0.037 | 0.044 | 0.350+j0.233 | 0.029+j0.043 | 36.0 | 616 | 499 |
750 | 16.1 | 6000 | 0.0144 | 0.019 | 0.032 | 0.042 | 0.323+j0.199 | 0.020+j0.041 | 53.9 | 716 | 557 |
1000 | 17.1 | 8000 | 0.0108 | 0.015 | 0.028 | 0.040 | 0.305+j0.176 | 0.016+j0.040 | 71.9 | 825 | 608 |
* Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
Table 3 – Weights and Measurements (Metric)
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Dia. Over Inner Jacket | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | mm | mm | mm | mm | mm | mm | mm | mm | kg/km | |
TBA | 1 | 19 | 8.18 | 22.33 | 6.60 | 23.85 | 28.42 | 36.55 | 1.27 | 39.09 | 1671 |
TBA | 1/0 | 19 | 9.19 | 23.34 | 6.60 | 24.87 | 29.44 | 37.57 | 1.27 | 40.11 | 1827 |
TBA | 2/0 | 19 | 10.29 | 24.43 | 6.60 | 25.96 | 30.53 | 38.66 | 1.27 | 41.20 | 2012 |
TBA | 3/0 | 19 | 11.58 | 25.73 | 6.60 | 27.25 | 31.83 | 39.95 | 1.27 | 42.49 | 2243 |
TBA | 4/0 | 19 | 13.00 | 27.15 | 6.60 | 28.68 | 33.25 | 41.38 | 1.27 | 43.92 | 2521 |
TBA | 250 | 37 | 14.17 | 28.55 | 6.60 | 30.07 | 34.65 | 42.77 | 1.27 | 45.31 | 2772 |
TBA | 350 | 37 | 16.79 | 31.17 | 6.60 | 32.69 | 37.26 | 45.39 | 1.52 | 48.44 | 3429 |
TBA | 500 | 37 | 20.04 | 34.42 | 6.60 | 35.94 | 40.51 | 48.89 | 1.52 | 51.94 | 4387 |
TBA | 750 | 61 | 24.59 | 39.19 | 6.60 | 40.72 | 46.81 | 55.19 | 1.52 | 58.24 | 5990 |
TBA | 1000 | 61 | 28.37 | 42.98 | 6.60 | 44.50 | 50.60 | 58.98 | 1.52 | 62.03 | 7366 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 4 – Electrical and Engineering Data (Metric)
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity in Vented Cable Tray 90°C‡ | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
1 | 274.32 | 2982 | 0.4232 | 0.53 | 0.0207 | 0.1903 | 0.520+j0.371 | 0.162+j0.058 | 6.0 | 245 | 244 |
1/0 | 281.94 | 3760 | 0.3346 | 0.42 | 0.0192 | 0.1837 | 0.485+j0.356 | 0.129+j0.055 | 7.6 | 278 | 272 |
2/0 | 289.56 | 4739 | 0.2657 | 0.33 | 0.0180 | 0.1772 | 0.456+j0.340 | 0.102+j0.054 | 9.6 | 316 | 303 |
3/0 | 297.18 | 5972 | 0.2106 | 0.26 | 0.0165 | 0.1706 | 0.431+j0.323 | 0.081+j0.051 | 12.1 | 356 | 333 |
4/0 | 307.34 | 7534 | 0.1673 | 0.21 | 0.0152 | 0.1640 | 0.411+j0.305 | 0.065+j0.050 | 15.2 | 403 | 367 |
250 | 317.50 | 8900 | 0.1414 | 0.18 | 0.0146 | 0.1575 | 0.397+j0.289 | 0.055+j0.048 | 18.0 | 455 | 411 |
350 | 337.82 | 12460 | 0.1010 | 0.13 | 0.0128 | 0.1509 | 0.373+j0.262 | 0.040+j0.046 | 25.2 | 537 | 459 |
500 | 363.22 | 17800 | 0.0709 | 0.09 | 0.0113 | 0.1444 | 0.350+j0.233 | 0.029+j0.043 | 36.0 | 616 | 499 |
750 | 408.94 | 26700 | 0.0472 | 0.06 | 0.0098 | 0.1378 | 0.323+j0.199 | 0.020+j0.041 | 53.9 | 716 | 557 |
1000 | 434.34 | 35600 | 0.0354 | 0.05 | 0.0085 | 0.1312 | 0.305+j0.176 | 0.016+j0.040 | 71.9 | 825 | 608 |
* Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
Revision: 3.0.00C