SPEC 26515

HVTECK CU 1/C 280TRXLPE CB PVC AIA PVC 28kV 100% CSA

Single Conductor, 280 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:280 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
  6. Neutral Separator:Mylar tape
  7. Inner Jacket:PVC inner jacket
  8. Armour:Aluminum Interlocked Armour (AIA)
  9. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 28kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL) and 105°C for use in harsh Canadian environments. For installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable. When used in a 3 phase system, the combination of each bond conductor from each single conductor cable provide a 100% bonded system to ground.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 280 TRXLPE AIA 28kV 100% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralDia. Over Inner JacketDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchNo. x AWGinchinchmilinchlb/1000ft
    TBA1190.3220.9192800.99917x161.2611.581501.6811285
    TBA1/0190.3620.9592801.03917x161.3011.621501.7211389
    TBA2/0190.4051.0022801.08217x161.3441.664501.7641512
    TBA3/0190.4561.0532801.15321x161.4151.735501.8351723
    TBA4/0190.5121.1092801.20921x161.4711.791601.9111944
    TBA250370.5581.1642801.26427x161.5261.846601.9662160
    TBA350370.6611.2672801.36721x141.6551.975602.0952626
    TBA500370.7891.3952801.49527x141.7832.113602.2333348
    TBA750610.9681.5832801.71333x142.0612.391602.5114564
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity in Vented Cable Tray 90°C‡Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    111.86700.1290.1610.0710.0600.383+j0.1180.164+j0.0596.0245244
    1/012.08450.1020.1280.0660.0580.350+j0.1160.131+j0.0577.6278272
    2/012.310650.0810.1010.0620.0560.323+j0.1150.104+j0.0559.6316303
    3/012.813420.06420.0800.0570.0540.268+j0.0880.083+j0.05312.1356333
    4/013.416930.0510.0640.0530.0520.252+j0.0870.067+j0.05115.2403367
    25013.820000.04310.0540.0500.0510.206+j0.0650.058+j0.05018.0455411
    35014.728000.03080.0390.0440.0480.164+j0.0530.044+j0.04725.2537459
    50015.640000.02160.0280.0390.0460.127+j0.0410.034+j0.04436.0616499
    75017.660000.01440.0190.0330.0440.101+j0.0340.025+j0.04153.9716557
    * Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralDia. Over Inner JacketDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmkg/km
    TBA1198.1823.347.1125.3717x1632.0340.161.2742.701912
    TBA1/0199.1924.367.1126.3917x1633.0541.171.2743.712067
    TBA2/01910.2925.457.1127.4817x1634.1442.271.2744.812250
    TBA3/01911.5826.757.1129.2921x1635.9444.071.2746.612564
    TBA4/01913.0028.177.1130.7121x1637.3645.491.5248.542893
    TBA2503714.1729.577.1132.1127x1638.7646.891.5249.943214
    TBA3503716.7932.187.1134.7221x1442.0450.171.5253.213908
    TBA5003720.0435.437.1137.9727x1445.2953.671.5256.724982
    TBA7506124.5940.217.1143.5133x1452.3560.731.5263.786792
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity in Vented Cable Tray 90°C‡Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftkAmpAmpAmp
    1299.7229820.42320.530.02160.19690.383+j0.1180.164+j0.0596.0245244
    1/0304.8037600.33460.420.02010.19030.350+j0.1160.131+j0.0577.6278272
    2/0312.4247390.26570.330.01890.18370.323+j0.1150.104+j0.0559.6316303
    3/0325.1259720.21060.260.01740.17720.268+j0.0880.083+j0.05312.1356333
    4/0340.3675340.16730.210.01620.17060.252+j0.0870.067+j0.05115.2403367
    250350.5289000.14140.180.01520.16730.206+j0.0650.058+j0.05018.0455411
    350373.38124600.10100.130.01340.15750.164+j0.0530.044+j0.04725.2537459
    500396.24178000.07090.090.01190.15090.127+j0.0410.034+j0.04436.0616499
    750447.04267000.04720.060.01010.14440.101+j0.0340.025+j0.04153.9716557
    * Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I

    Revision: 3.0.00C