SPEC 26542

HVTECK CU 3/C 345NLEPR TS PVC AIA PVC 28kV 133% CSA

3 Conductor, 345 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:345 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Filler:Interstices filled with non-hydroscoping/non-wicking fillers
  7. Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
  8. Binder:Polypropylene tape
  9. Inner Jacket:PVC inner jacket
  10. Armour:Aluminum Interlocked Armour (AIA)
  11. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 28kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL) and 105°C for use in harsh Canadian environments. For installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CU 345 NLEPR AIA 28kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGround SizeDia. Over Inner JacketDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchAWGinchinchmilinchlb/1000ft
    TBA1190.3221.0493451.10962.6713.001753.1514393
    TBA1/0190.3621.0893451.14962.7573.087753.2374757
    TBA2/0190.4051.1323451.19262.8503.180753.3305186
    TBA3/0190.4561.1833451.24343.0103.340853.5105989
    TBA4/0190.5121.2393451.29943.1313.461853.6316634
    TBA250370.5581.2943451.35443.2503.580853.7507224
    TBA350370.6611.3973451.45733.4723.802853.9728636
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity in Vented Cable Tray 90°C‡Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    122.120090.1290.1610.0640.0510.517+j0.3200.161+j0.0505.7202226
    1/022.725340.1020.1280.0590.0490.481+j0.3070.128+j0.0497.2231256
    2/023.331940.0810.1010.0550.0470.450+j0.2940.101+j0.0479.0265290
    3/024.640270.06420.0800.0510.0450.424+j0.2790.080+j0.04511.4303327
    4/025.450780.0510.0640.0480.0430.402+j0.2650.064+j0.04314.3348369
    25026.360000.04310.0540.0450.0420.387+j0.2510.055+j0.04216.9384408
    35027.884000.03080.0390.0400.0400.361+j0.2290.040+j0.04023.7468485
    * Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGround SizeDia. Over Inner JacketDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmAWGmmmmmmmmkg/km
    TBA1198.1826.648.7628.17667.8476.231.9180.046538
    TBA1/0199.1927.668.7629.18670.0378.411.9182.227079
    TBA2/01910.2928.758.7630.28672.3980.771.9184.587718
    TBA3/01911.5830.058.7631.57476.4584.842.1689.158913
    TBA4/01913.0031.478.7632.99479.5387.912.1692.239872
    TBA2503714.1732.878.7634.39482.5590.932.1695.2510750
    TBA3503716.7935.488.7637.01388.1996.572.16100.8912852
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity in Vented Cable Tray 90°C‡Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftkAmpAmpAmp
    1561.3489400.42320.530.01950.16730.517+j0.3200.161+j0.0505.7202226
    1/0576.58112760.33460.420.01800.16080.481+j0.3070.128+j0.0497.2231256
    2/0591.82142130.26570.330.01680.15420.450+j0.2940.101+j0.0479.0265290
    3/0624.84179200.21060.260.01550.14760.424+j0.2790.080+j0.04511.4303327
    4/0645.16225970.16730.210.01460.14110.402+j0.2650.064+j0.04314.3348369
    250668.02267000.14140.180.01370.13780.387+j0.2510.055+j0.04216.9384408
    350706.12373800.10100.130.01220.13120.361+j0.2290.040+j0.04023.7468485
    * Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I

    Revision: 3.0.00C