SPEC 26622

HVTECK AL 1/C 420NLEPR TS PVC AIA PVC 35kV 133% CSA

Single Conductor, 420 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:420 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Inner Jacket:PVC inner jacket
  7. Armour:Aluminum Interlocked Armour (AIA)
  8. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 35kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL) and 105°C for use in harsh Canadian environments. For installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable.

Specifications:

  • ASTM B800 8000 Series Aluminum Alloy Wire
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 420 NLEPR AIA 35kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldDia. Over Inner JacketDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchinchinchmilinchlb/1000ft
    TBA1/0190.3361.2134201.2731.4531.773601.8931499
    6793452/0190.3761.2534201.3131.4931.813601.9331574
    TBA3/0190.4231.3004201.3601.5401.860601.9801666
    TBA4/0190.4751.3524201.4121.5921.912602.0321773
    TBA250370.5201.4064201.4661.6461.976602.0961942
    TBA350370.6161.5024201.5621.8022.132602.2522280
    TBA500370.7361.6224201.6821.9222.252602.3722584
    TBA750610.9081.8254201.8852.1252.455752.6053179
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity in Vented Cable Tray 90°C‡Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    1/013.36340.1680.2110.0690.0610.546+j0.2810.212+j0.0614.7221219
    2/013.57990.1330.1670.0650.0590.498+j0.2700.168+j0.0595.9253246
    3/013.910070.1050.1320.0610.0570.459+j0.2580.133+j0.0577.4288275
    4/014.212700.08360.1050.0560.0550.427+j0.2460.106+j0.0559.4327305
    25014.715000.07070.0890.0540.0540.406+j0.2340.090+j0.05411.1367343
    35015.821000.05050.0640.0480.0520.371+j0.2150.065+j0.05115.5443399
    50016.630000.03540.0450.0430.0490.341+j0.1950.046+j0.04822.1529451
    75018.245000.02360.0300.0380.0460.308+j0.1670.031+j0.04633.2633505
    * Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldDia. Over Inner JacketDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmmmmmmmmmkg/km
    TBA1/0198.5330.8110.6732.3336.9145.031.5248.082231
    6793452/0199.5531.8310.6733.3537.9246.051.5249.102342
    TBA3/01910.7433.0210.6734.5439.1247.241.5250.292479
    TBA4/01912.0734.3410.6735.8640.4448.561.5251.612639
    TBA2503713.2135.7110.6737.2441.8150.191.5253.242890
    TBA3503715.6538.1510.6739.6745.7754.151.5257.203393
    TBA5003718.6941.2010.6742.7248.8257.201.5260.253845
    TBA7506123.0646.3610.6747.8853.9762.361.9166.174731
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity in Vented Cable Tray 90°C‡Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftkAmpAmpAmp
    1/0337.8228210.55120.690.02100.20010.546+j0.2810.212+j0.0614.7221219
    2/0342.9035560.43640.550.01980.19360.498+j0.2700.168+j0.0595.9253246
    3/0353.0644810.34450.430.01860.18700.459+j0.2580.133+j0.0577.4288275
    4/0360.6856520.27430.340.01710.18040.427+j0.2460.106+j0.0559.4327305
    250373.3866750.23200.290.01650.17720.406+j0.2340.090+j0.05411.1367343
    350401.3293450.16570.210.01460.17060.371+j0.2150.065+j0.05115.5443399
    500421.64133500.11610.150.01310.16080.341+j0.1950.046+j0.04822.1529451
    750462.28200250.07740.100.01160.15090.308+j0.1670.031+j0.04633.2633505
    * Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I

    Revision: 3.0.00C