SPEC 81069

15kV AL 133% EPR (EAM) One-Third Neutral LLDPE Primary UD Patented POWERGLIDE® MV CABLE (PATENT: www.patentsw.com)

Single Conductor, 220 Mils Ethylene Propylene Rubber (EPR) / Ethylene Alkene Copolymer (EAM), 133% Insulation Level, One-third Concentric Neutral, Linear Low Density Polyethylene (LLDPE) Jacket. Silicone Free

...

Construction:

  1. Conductor:Moisture blocked class B compressed Aluminum ASTM B231 1350 ¾ hard H16/H26 ( Non Moisture Blocked Optional )
  2. Conductor Shield:Conventional Semi-conducting cross-linked copolymer; Supersmooth conductor shield optional; A conductor tape is used for cable size larger than or equal to 1500 Kcmil
  3. Insulation:220 Mils Ethylene Propylene Rubber (EPR) / Ethylene Alkene Copolymer (EAM) 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Neutral:Helically applied soft drawn bare copper one-third concentric neutral
  6. Overall Jacket:Linear Low Density Polyethylene (LLDPE) Jacket with PowerGlide® Technology. Black with red extruded stripes

Applications and Features:

Southwire's 15kV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, sunlight, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation. 140°C for emergency overload, and 250°C for short circuit conditions. Jacket can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.

Specifications:

  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B609 Standard Specification for Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
  • ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5 - 46kV
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Rural Utility Standard RUS 1728F-U1 or 1728.204 (Electric standards and specifications for materials and construction)
  • UL 1072 Listed as MV 90 When Specified
  • Optional CSA 68.5: -40ºC and MV 90ºC optional marking available upon request
  • Sample Print Legend:

    SOUTHWIRE HI-DRI-PLUS(R) XXX AWG AL 15000 VOLTS EPR INSULATION 220 MILS (NESC) POWERGLIDE(R) MV PAT www.patentSW.com -- SOUTHWIRE {MMM} {YYYY} NON-CONDUCTING JACKET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension*
    AWG/KcmilinchinchmilinchNo. x AWGΩ/1000ftmilinchlb/1000ftinchlb
    TBA2 (1)0.2580.7352200.8156x140.438501.0435058.3398
    TBA2 (7)0.2830.7602200.8406x140.438501.0685318.5398
    TBA1 (1)0.2890.7662200.8466x140.438501.0745408.5502
    TBA1 (19)0.3220.7992200.8796x140.438501.1075718.8502
    TBA1/0 (1)0.3250.8022200.8826x140.438501.1105818.0634
    TBA1/0 (19)0.3520.8292200.9096x140.438501.1376079.0634
    TBA2/0 (19)0.3950.8722200.9527x140.376501.1806729.0799
    TBA3/0 (19)0.4430.9202201.0009x140.292501.2287589.81007
    662264^4/0 (19)0.4980.9752201.05511x140.239501.28385810.21270
    TBA250 (37)0.5581.0442201.14413x140.202501.37299410.91500
    TBA350 (37)0.6611.1472201.24718x140.146501.47512201102100
    TBA500 (37)0.7891.2752201.37516x120.104501.635157413.3000
    TBA750 (61)0.9681.4632201.56324x120.069801.883217015.04500
    TBA1000 (61)1.1171.6122201.74220x100.052802.106277516.86000
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    ^ HI-DRI-PLUS.
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftA/1000ftW/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    2 (1)0.2660.3340.0510.0510.17029.3950.652+j0.2330.335+j0.0512025.6120150
    2 (7)0.2660.3340.0480.0490.17931.0230.651+j0.2320.335+j0.0492025.6120150
    1 (1)0.2110.2650.0480.0490.18131.4120.582+j0.2320.266+j0.0492025.6140175
    1 (19)0.2110.2650.0450.0480.19433.5420.581+j0.2300.266+j0.0482025.6140175
    1/0 (1)0.1680.2110.0440.0470.19533.7350.527+j0.2300.212+j0.0472025.6155195
    1/0 (19)0.1680.2110.0420.0460.20535.4660.527+j0.2300.212+j0.0462025.6155195
    2/0 (19)0.1330.1670.0390.0450.22138.2060.459+j0.1900.168+j0.0452363.3180225
    3/0 (19)0.1050.1320.0360.0430.23841.2470.383+j0.1370.133+j0.0433038.5200255
    4/0 (19)0.08360.1050.0340.0420.25844.7120.322+j0.1050.107+j0.0423713.7235285
    250 (37)0.07070.0890.0310.0410.28349.0370.279+j0.0850.091+j0.0404388.9
    350 (37)0.05050.0640.0270.0390.32055.4580.208+j0.0570.066+j0.0386076.9310375
    500 (37)0.03540.0450.0240.0370.36663.3990.151+j0.0420.048+j0.0368582.3370450
    750 (61)0.02360.0300.0200.0360.43375.0100.102+j0.0290.035+j0.03412873.4460545
    1000 (61)0.01770.0230.0180.0350.48684.1840.077+j0.0260.029+j0.03217052.9520620
    * Calculations are based on three cables triplexed / concentric shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Figure 7 of ICEA P-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
    ‡ Ampacities are based on Figure 1 of ICEA P-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension*
    AWG/KcmilmmmmmmmmNo. x AWGΩ/kmmmmmkg/kmmmnewton
    TBA2 (1)6.5518.675.5920.706x141.441.2726.49752210.821771
    TBA2 (7)7.1919.305.5921.346x141.441.2727.13790215.901771
    TBA1 (1)7.3419.465.5921.496x141.441.2727.28804215.902234
    TBA1 (19)8.1820.295.5922.336x141.441.2728.12850223.522234
    TBA1/0 (1)8.2520.375.5922.406x141.441.2728.19865203.202821
    TBA1/0 (19)8.9421.065.5923.096x141.441.2728.88903228.602821
    TBA2/0 (19)10.0322.155.5924.187x141.231.2729.971000228.603556
    TBA3/0 (19)11.2523.375.5925.409x140.961.2731.191128248.924481
    662264^4/0 (19)12.6524.765.5926.8011x140.781.2732.591277259.085652
    TBA250 (37)14.1726.525.5929.0613x140.661.2734.851479276.866675
    TBA350 (37)16.7929.135.5931.6718x140.481.2737.4718162794.009345
    TBA500 (37)20.0432.395.5934.9316x120.341.2741.532342330.2013350
    TBA750 (61)24.5937.165.5939.7024x120.232.0347.833229381.0020025
    TBA1000 (61)28.3740.945.5944.2520x100.172.0353.494130426.7226700
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    ^ HI-DRI-PLUS.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilΩ/kmΩ/kmMΩ*kmΩ/kmA/kmW/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2 (1)0.87271.100.01550.16730.55896.44030.652+j0.2330.335+j0.0512025.6120150
    2 (7)0.87271.100.01460.16080.587101.78150.651+j0.2320.335+j0.0492025.6120150
    1 (1)0.69230.870.01460.16080.594103.05770.582+j0.2320.266+j0.0492025.6140175
    1 (19)0.69230.870.01370.15750.636110.04590.581+j0.2300.266+j0.0482025.6140175
    1/0 (1)0.55120.690.01340.15420.640110.67910.527+j0.2300.212+j0.0472025.6155195
    1/0 (19)0.55120.690.01280.15090.673116.35830.527+j0.2300.212+j0.0462025.6155195
    2/0 (19)0.43640.550.01190.14760.725125.34780.459+j0.1900.168+j0.0452363.3180225
    3/0 (19)0.34450.430.01100.14110.781135.32480.383+j0.1370.133+j0.0433038.5200255
    4/0 (19)0.27430.340.01040.13780.846146.69290.322+j0.1050.107+j0.0423713.7235285
    250 (37)0.23200.290.00940.13450.928160.88250.279+j0.0850.091+j0.0404388.9
    350 (37)0.16570.210.00820.12801.050181.94880.208+j0.0570.066+j0.0386076.9310375
    500 (37)0.11610.150.00730.12141.201208.00200.151+j0.0420.048+j0.0368582.3370450
    750 (61)0.07740.100.00610.11811.421246.09580.102+j0.0290.035+j0.03412873.4460545
    1000 (61)0.05810.080.00550.11481.594276.19420.077+j0.0260.029+j0.03217052.9520620
    * Calculations are based on three cables triplexed / concentric shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Figure 7 of ICEA P-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
    ‡ Ampacities are based on Figure 1 of ICEA P-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)

    Revision: 3.0.00C