SPEC 81324

46kV CU 100% EPR One-Third Neutral LLDPE Primary UD

Single Conductor, 445 Mils Ethylene Propylene Rubber (EPR), 100% Insulation Level, One-third Concentric Neutral, Linear Low Density Polyethylene (LLDPE) Jacket. Silicone Free

...

Construction:

  1. Conductor:Class B compressed stranded soft drawn bare copper per ASTM B3 and ASTM B8; Conductor moisture block (optional)
  2. Conductor Shield:Conventional Semi-conducting cross-linked copolymer; Supersmooth conductor shield optional; A conductor tape is used for cable size larger than or equal to 1500 Kcmil
  3. Insulation:445 Mils Ethylene Propylene Rubber (EPR) 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Neutral:Helically applied soft drawn bare copper one-third concentric neutral
  6. Overall Jacket:Linear Low Density Polyethylene (LLDPE) Jacket, Black (red extruded stripes optional); PowerGlide® LLDPE jacket optional

Applications and Features:

Southwire's 46kV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, sunlight, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation. 140°C for emergency overload, and 250°C for short circuit conditions. Jacket types available that can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5 - 46kV
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Optional CSA: CSA 68.5 and -40C optional marking available upon request
  • Sample Print Legend:

    SOUTHWIRE HI-DRI(R) [CONDUCTOR SIZE] [AWG or KCMIL] CU 46000 VOLTS EPR INSULATION 445 MILS -- (NESC) -- SOUTHWIRE {MMM} {YYYY} NON-CONDUCTING JACKET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension*
    AWG/KcmilinchinchmilinchNo. x AWGΩ/1000ftmilinchlb/1000ftinchlb
    628122350 (37)0.6611.5974451.72718x120.092802.047286024.62800
    628126500 (37)0.7891.7254451.85517x100.061802.219369626.64000
    TBA750 (61)0.9681.9134452.04320x90.041802.432497229.26000
    628129750 (61)0.9681.9134452.04325x100.041802.432497229.26000
    6281181000 (61)1.1172.0624452.19221x80.031802.609621331.38000
    6281141250 (91)1.2502.2174452.34726x80.025802.764742133.210000
    6281081500 (91)1.3702.3374452.46731x80.021802.884858134.612000
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftA/1000ftW/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    350 (37)0.03080.0390.0460.0460.583309.7090.134+j0.0470.043+j0.0459929.2400470
    500 (37)0.02160.0280.0410.0440.655347.8280.091+j0.0380.033+j0.04214906.4470555
    750 (61)0.01440.0190.0350.0420.759403.1850.062+j0.0310.026+j0.03822115.5560650
    750 (61)0.01440.0190.0350.0420.759403.1850.062+j0.0310.026+j0.03822115.5560650
    1000 (61)0.01080.0150.0320.0400.841446.6950.047+j0.0280.022+j0.03429288.2
    1250 (91)0.008630.0120.0290.0390.926491.7190.038+j0.0250.020+j0.03136261.6
    1500 (91)0.007190.0110.0270.0380.991526.4490.033+j0.0240.019+j0.02943235.0
    * Calculations are based on three cables triplexed / concentric shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Figure 7 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
    ‡ Ampacities are based on Figure 1 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension*
    AWG/KcmilmmmmmmmmNo. x AWGΩ/kmmmmmkg/kmmmnewton
    628122350 (37)16.7940.5611.3043.8718x120.302.0351.994256624.8412460
    628126500 (37)20.0443.8211.3047.1217x100.202.0356.365500675.6417800
    TBA750 (61)24.5948.5911.3051.8920x90.132.0361.777399741.6826700
    628129750 (61)24.5948.5911.3051.8925x100.132.0361.777399741.6826700
    6281181000 (61)28.3752.3711.3055.6821x80.102.0366.279246795.0235600
    6281141250 (91)31.7556.3111.3059.6126x80.082.0370.2111044843.2844500
    6281081500 (91)34.8059.3611.3062.6631x80.072.0373.2512770878.8453400
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilΩ/kmΩ/kmMΩ*kmΩ/kmA/kmW/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    350 (37)0.10100.130.01400.15091.9131016.10560.134+j0.0470.043+j0.0459929.2400470
    500 (37)0.07090.090.01250.14442.1491141.16800.091+j0.0380.033+j0.04214906.4470555
    750 (61)0.04720.060.01070.13782.4901322.78540.062+j0.0310.026+j0.03822115.5560650
    750 (61)0.04720.060.01070.13782.4901322.78540.062+j0.0310.026+j0.03822115.5560650
    1000 (61)0.03540.050.00980.13122.7591465.53480.047+j0.0280.022+j0.03429288.2
    1250 (91)0.02830.040.00880.12803.0381613.25130.038+j0.0250.020+j0.03136261.6
    1500 (91)0.02360.040.00820.12473.2511727.19490.033+j0.0240.019+j0.02943235.0
    * Calculations are based on three cables triplexed / concentric shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Figure 7 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)
    ‡ Ampacities are based on Figure 1 of ICEA T-117-734 (Single circuit trefoil, 100% load factor, 90°C conductor temperature, earth RHO 90, 36" burial depth)

    Revision: 3.0.00C